A350A/B Electronic Temperature Control Product/Technical Bulletin

A

djustments

Follow this procedure to set up the A350A/B for the
desired operation.

1. Remove the A350 cover by loosening the

four captive cover screws.

2. Set the heating/cooling jumper blocks to the

desired mode of operation. Position the jumper
blocks vertically for heating or horizontally for
cooling. (See Figure 2.)

IMPORTANT:

Verify that the heating/cooling
jumper blocks are in the proper
position before powering the
System 350 modules. If the
jumper blocks on the control or
staging modules are installed in
the wrong position, the device will
activate the relay in response to
the opposite signal. The heating
or cooling equipment will remain
energized until the error is
corrected.

3. Adjust the differential potentiometer (DIFF) on the

A350 as needed. (Figure 6 is an example of a
multistage application.) The stage module’s offset
and differential can be set independently.

ON

OFF

Di

ffe

re

nt

ia

l

ON

OFF

S350A

Stage 2

A350

Stage 1

Setpoint

Temperature

(+)

(-)

Di

ffe

re

nt

ia

l

ON

OFF

D

iffe

re

nt

ia

l

ON

OFF

S350A

Stage 4

S350A

Stage 3

D

iff

er

en

tial

ON

OFF

Di

ffe

re

nt

ia

l

ON = Energized

OFF= De-energized

Stage 5

S350A

Heating

Cooling

Jumper Set To

OFFSET

OFFSET

OFFSET

OFFSET

Figure 6: Typical Multistage

Heating/Cooling Application

4. Replace the cover, and secure in place with the

four captive screws. Move the setpoint dial to the
desired position.

Note:

The A350A/B setpoint is factory calibrated at
midscale to a tolerance of +/- 1F° (0.6C°).
Setpoint tolerance at the extreme ends of the
setpoint ranges in relation to the printed scale
can be +/- 3F° (1.7C°). The D350 Display
Module is unaffected by this tolerance shift.
Use the D350 for the most accurate setpoint
selection.

C

heckout P

rocedure

Follow this procedure to verify that the A350A/B is
connected and functioning properly.

1. Make sure installation and wiring connections are

according to job specifications before applying
power. (Refer to Figure 6 for an example of a
multistage application.)

2. Make the necessary adjustments and electrical

connections.

3. Put the system in operation and observe at least

three complete operating cycles before leaving the
installation.

T

roubleshooting

If the control system does not function properly, verify
that the proper mode is selected on each module
(Heat/Cool, Direct Acting/Reverse Acting). Proceed as
follows to determine the cause of the problem:
1. Make sure proper voltage is applied to the A350

control.
a. Connect a digital voltmeter (DVM) between

the 24V and COM terminals located on the
control’s left side terminal block (See Figure 2.)

If an external transformer is used

, select AC

volts on the DVM and verify that the voltage is
between 20 and 30 VAC.

If a Y350R Power Module is used

, select DC

volts on the DVM and verify that the voltage is
between 16 and 38 VDC.

b. If the DVM reading is within the indicated

voltage range, proceed to Step 2.

c. If the DVM reading is 

not

 within the indicated

voltage range, correct the wiring, replace the
Y350R, or replace the external transformer.

Содержание System 350 A350A

Страница 1: ...res and Benefits Modular Design Enables stage display and power modules to be purchased and installed as needed Plug together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules and reduces installation costs Two Standard Models Cover Wide Setpoint Ranges 30 to 130 F 34 to 55 C or 90 to 250 F 32 to 121 C Reduces inventory by encompassing temperature ranges required to support ...

Страница 2: ...rvisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperature at which the A350A B s relay de energizes Use the Setpoint Dial on the front of the A350A B to adjust setpoint See Figure 2 Differential Adjustment Differential is defined as the change in sensor temperature between energization and de energization of the relay Adjustment of the A350A B differen...

Страница 3: ... power and sensor input from the A350 control S350C Slave Stage Modules perform switching functions based upon the A350 s sensor information Setpoint and differential are selected independently at the S350C For more information on these modules refer to the System 350 TM S350C Temperature Slave Stage Module Product Technical Bulletin LIT 930084 S350P Proportional Stage Modules S350P Proportional S...

Страница 4: ...into the right side of the A350A B control Note When mounting the System 350 modules to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure WARNING Risk of Electrical Shock Disconnect power supply before wiring connections are made to avoid electrical shock or damage to equipment All wiring must conform to the National Electrical Code and or local regulatio...

Страница 5: ...with A350 Series Controls See Tables 3 and 6 The sensor must be connected to the COM and SEN terminals on the four position terminal strip located at the top left of the printed circuit board Refer to Figures 2 4 and 5 The sensors are not polarity sensitive The sensor must be mounted so that it can accurately sense the temperature of the controlled medium Table 3 Sensors Included With A350A B Cont...

Страница 6: ... The A350A B setpoint is factory calibrated at midscale to a tolerance of 1F 0 6C Setpoint tolerance at the extreme ends of the setpoint ranges in relation to the printed scale can be 3F 1 7C The D350 Display Module is unaffected by this tolerance shift Use the D350 for the most accurate setpoint selection Checkout Procedure Follow this procedure to verify that the A350A B is connected and functio...

Страница 7: ...etpoint Dial Setting Heating On Closed Ts Sp Diff Heating Off Open Ts Sp Cooling On Closed Ts Sp Diff Cooling Off Open Ts Sp Ts is sensed temperature and Sp is setpoint temperature Repairs and Replacement Do not make field repairs or perform calibration Replacement controls and A99B Temperature Sensors are available through the nearest Johnson Controls representative See Tables 5 and 6 for orderin...

Страница 8: ...emperature Control Supply Voltage Y350R Power Module Input 120 240 VAC 50 60 Hz Output 24 VDC unfiltered 10 VA Class 2 External Source 24 VAC 50 60 Hz Class 2 20 30 VAC Note Only one supply voltage source may be used Power Consumption 1 4 VA Ambient Temperatures Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Humidity 0 to 95 RH non condensing maximum dew point 85 F 29 C Setpoint ...

Отзывы: