Table 6: System 350 Accessories

Item

Product Code
Number

Description

Enclosure

BOX10A-600R

Outdoor PVC sensor enclosure; includes wire nuts

Wall Mount Plate

TE-6001-4

Includes sensor mounting clip

Cover

T-4000-2644

For wall mount plate

Mounting Clip

A99-CLP-1

Surface mounting clip for the A99B Temperature Sensor

Duct Mounting

TE-6001-1

Duct-mounting hardware with handy box for A99B sensor

Duct Mounting

TE-6001011

Duct-mounting hardware without handy box for A99B sensor

Conduit Adaptor

ADP11A-600R

1/2 in. Snap-fit EMT conduit adaptor (box of 10)

Immersion Well

WEL11A-601R

For liquid sensing applications

Sun Shield

SHL10A-603R

For use with outside sensors in sunny locations

DIN Rail Sections

BKT287-1R
BKT287-2R

12 in. (0.3 m) long
39-1/3 in.(1.0 m) long

DIN Rail End Clamp

PLT344-1R

Consists of two end clamps

Cables for Remote Mounting
of D350 Display Module

WHA29A-600R
WHA29A-603R
WHA29A-604R

3 ft (0.9 m) This can also be used to daisy chain S350 Stage Modules together.
25 ft (7.6 m)
50 ft (15.2 m)

S

pecifications

Product

A350A/B Electronic Temperature Control

Supply Voltage

Y350R Power Module:

Input: 

120/240 VAC 50/60 Hz

Output: 24 VDC, unfiltered, 10 VA, Class 2

External Source:

24 VAC, 50/60 Hz Class 2 (20-30 VAC)

Note:

Only one supply voltage source may be used.

Power Consumption

1.4 VA

Ambient Temperatures

Operating: -30 to 150°F (-34 to 66°C)
Shipping:

-40 to 185°F (-40 to 85°C)

Humidity

0 to 95% RH non-condensing; maximum dew point: 85°F (29°C)

Setpoint Adjustment Range

See Table 5.

Differential Adjustment Range

See Table 5.

SPDT Relay Output

120V

208 to 240V

Horsepower:

1/2

1/2

Full Load:

9.8A 

4.9A

Locked Rotor:

58.8A 

29.4A

Non-Inductive:

10A at 24 to 240 VAC

Pilot Duty:

125 VA at 24 to 240 VAC

Sensor

Replaceable positive temperature coefficient sensor
Reference resistance: 1035 ohms at 77°F (25°C)

Material

Case and cover: NEMA 1 high-impact thermoplastic

Agency Listings

UL Listed, CCN XAPX, File E27734
UL Listed for Canada, CCN XAPX7, File E27734

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.

Controls Group

507 E. Michigan Street
P.O. Box 423

Printed in U.S.A.

Milwaukee, WI   53201

www.johnsoncontrols.com

Содержание System 350 A350A

Страница 1: ...res and Benefits Modular Design Enables stage display and power modules to be purchased and installed as needed Plug together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules and reduces installation costs Two Standard Models Cover Wide Setpoint Ranges 30 to 130 F 34 to 55 C or 90 to 250 F 32 to 121 C Reduces inventory by encompassing temperature ranges required to support ...

Страница 2: ...rvisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperature at which the A350A B s relay de energizes Use the Setpoint Dial on the front of the A350A B to adjust setpoint See Figure 2 Differential Adjustment Differential is defined as the change in sensor temperature between energization and de energization of the relay Adjustment of the A350A B differen...

Страница 3: ... power and sensor input from the A350 control S350C Slave Stage Modules perform switching functions based upon the A350 s sensor information Setpoint and differential are selected independently at the S350C For more information on these modules refer to the System 350 TM S350C Temperature Slave Stage Module Product Technical Bulletin LIT 930084 S350P Proportional Stage Modules S350P Proportional S...

Страница 4: ...into the right side of the A350A B control Note When mounting the System 350 modules to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure WARNING Risk of Electrical Shock Disconnect power supply before wiring connections are made to avoid electrical shock or damage to equipment All wiring must conform to the National Electrical Code and or local regulatio...

Страница 5: ...with A350 Series Controls See Tables 3 and 6 The sensor must be connected to the COM and SEN terminals on the four position terminal strip located at the top left of the printed circuit board Refer to Figures 2 4 and 5 The sensors are not polarity sensitive The sensor must be mounted so that it can accurately sense the temperature of the controlled medium Table 3 Sensors Included With A350A B Cont...

Страница 6: ... The A350A B setpoint is factory calibrated at midscale to a tolerance of 1F 0 6C Setpoint tolerance at the extreme ends of the setpoint ranges in relation to the printed scale can be 3F 1 7C The D350 Display Module is unaffected by this tolerance shift Use the D350 for the most accurate setpoint selection Checkout Procedure Follow this procedure to verify that the A350A B is connected and functio...

Страница 7: ...etpoint Dial Setting Heating On Closed Ts Sp Diff Heating Off Open Ts Sp Cooling On Closed Ts Sp Diff Cooling Off Open Ts Sp Ts is sensed temperature and Sp is setpoint temperature Repairs and Replacement Do not make field repairs or perform calibration Replacement controls and A99B Temperature Sensors are available through the nearest Johnson Controls representative See Tables 5 and 6 for orderin...

Страница 8: ...emperature Control Supply Voltage Y350R Power Module Input 120 240 VAC 50 60 Hz Output 24 VDC unfiltered 10 VA Class 2 External Source 24 VAC 50 60 Hz Class 2 20 30 VAC Note Only one supply voltage source may be used Power Consumption 1 4 VA Ambient Temperatures Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Humidity 0 to 95 RH non condensing maximum dew point 85 F 29 C Setpoint ...

Отзывы: