DN1670-2201
24
Upgrading the IP Link Firmware
Warning:
You lose communication with all your controllers for
up to 5 minutes
during this
upgrade. This must be planned accordingly.
1. Verify the communication status between the IP Link and the Gateway. From the EntraPass
workstation
Operation
menu, click
Site
.
2. Click the Gateway from the
Gateway List
.
Note:
For the EntraPass Special Edition application, there is no
Gateway List
selection.
The
Communication status
must read as follows:
IP Link communication OK
.
3. Confirm the firmware version before proceeding. Right click on the site name to view the contextual
menu.
4. Click
Full status
to view the firmware version.
5. Click
Close
.