15
DN1670-2201
IP Link Installation Manual
5- Powering Up the IP Link
1. Power up the IP Link.
2. Make sure the IP Link is in
Factory Default (DHCP)
mode before starting the configuration. See
Table 2 on page 5
for the heartbeat patterns for each state.
3. Connect the network cable.
6- Defining the EntraPass Site
Before you start
These items must be completed and verified:
•
The detachable
Network Configuration Information Sheet
is fully completed.
•
You are running EntraPass version 4.03 or higher.
Note:
If you are running EntraPass Corporate Edition or EntraPass Global Edition; the following system
components must have been installed and configured:
-
an EntraPass Workstation,
-
an EntraPass Corporate Gateway.
The IP Link communicates locally with EntraPass through a10/100 Base-T Ethernet connection.
1. From the
Devices
menu, go to
Site
, or click on
Devices
>
Site
.
2. Click on
New
, located in the top left corner of the Site/Loop screen, to create a new site.
3. Enter the site name for both languages.
4. Under the
General
tab, click
Secure IP (IP Link)
from the
Connection type
menu.
5. Enter the
Number of controllers
.
Note:
The maximum number of controllers for each IP Link is 32.
6. Complete the other settings as required.
7. Click on the
IP Device IP Configuration
tab.
8. Look on the IP Link for the MAC address sticker next to the terminal strip and complete the
MAC
address
of the IP Link.
Note:
The 1st 6 digits are already displayed and cannot be modified:
00:50:F9
:00:00:00.
9. Make sure the
Online
option is checked.
10.Enter the required information as specified in the
Network Configuration Information Sheet
.
•
For a Static IP address, click
Use the following IP address
and enter the information.