background image

IOM2723 Input/Output Module Installation

Guide

Application

The MS-IOM2723 input/output expansion module

is part of the 

Metasys

®

 system Field Equipment

Controller family. Input/Output expansion modules

(IOMs) expand the number of Input/Output points

connected to either a Network Automation Engine

(NAE), Network Control Engine (NCE), Advanced

Application Field Equipment Controller (FAC), Field

Equipment Controller (FEC), or Variable Air Volume

Modular Assembly (VMA) to monitor and control a

wide variety of HVAC equipment.

Note: 

The IOM2723 model is only available

in certain regions. Contact your local Johnson

Controls representative for more information.

IOMs operate on an RS-485 BACnet

®

 MS/TP Bus

and integrate into Johnson Controls

®

 and third-

party BACnet systems. IOMs communicate using the

BACnet MS/TP protocol when directly connected to

the FC Bus.

Note: 

With Release 10.1 or later of the

Controller Configuration Tool (CCT), VMAs, FECs,

and FACs can be configured to communicate

using either the BACnet MS/TP or the N2 field

bus networking protocol. The operation of

the IOM is not affected by the selection of the

BACnet MS/TP or the N2 protocol in the host

controller, when the IOM is connected to the

host controller using the SA bus.

North American emissions
compliance

United States

This equipment has been tested and found to

comply with the limits for a Class A digital device

pursuant to Part 15 of the FCC Rules. These limits

are designed to provide reasonable protection

against harmful interference when this equipment

is operated in a commercial environment. This

equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications.

Operation of this equipment in a residential area

may cause harmful interference, in which case the

users will be required to correct the interference at

their own expense.

Canada

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte

toutes les exigences du Règlement sur le matériel

brouilleur du Canada.

Installation

Observe these guidelines when installing an

expansion module:
• To minimize vibration and shock damage,

transport the expansion module in the original

container.

• Verify that all parts shipped with the expansion

module.

• Do not drop the expansion module or subject it to

physical shock.

Parts included

• One MS-IOM expansion module with removable

terminal blocks (Power and SA/FC bus are

removable)

• One installation instructions sheet

Materials and special tools needed

• Three fasteners appropriate for the mounting

surface (M4 screws or #8 screws)

• One 20 cm (8 in.) or longer piece of 35 mm DIN

rail and appropriate hardware for DIN rail mount

• Small straight-blade screwdriver for securing

wires in the terminal blocks

Physical features

The following figure displays the physical features

of the IOM, and the accompanying table provides a

*24101431108E*

Part No.  24-10143-1108 Rev. E

2019-10-18

(barcode for factory use only)

MS-IOM2723

Содержание IOM2723

Страница 1: ...sonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed an...

Страница 2: ...e can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm DIN rail whenever possible Mount the expansion module in the proper mountin...

Страница 3: ...tion shown in Figure 2 2 Pull the two bottom mounting clips outward from the expansion module to the extended position Figure 3 3 Hang the expansion module on the DIN rail by the hooks at the top of t...

Страница 4: ...a on incor recte risquent d endommager irr m diablement l quipement Important Do not exceed the expansion module electrical ratings Exceeding expansion module electrical ratings can result in permanen...

Страница 5: ...ray removable 3 terminal plug that fits into a board mounted jack on the top right of the expansion module Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the t...

Страница 6: ...outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted...

Страница 7: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 8: ...re See Figure 7 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 9: ...IOM expansion module does not supply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0...

Страница 10: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal...

Страница 11: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 12: ...sitions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 127 are the valid addresses for these expansion modules The following table describes the...

Страница 13: ...ress is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting w...

Страница 14: ...is a terminating device on the FC bus set the EOL switch to ON If the expansion module is not a terminating device on the bus set the EOL switch to OFF When an expansion module is connected to power w...

Страница 15: ...puter server that is running CCT For additional information about the firmware package files refer to the CCT Installation Instructions LIT 12011259 Troubleshooting Observe the Status LEDs on the fron...

Страница 16: ...VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additio...

Страница 17: ...y Input 15 bit resolution Output 15 bit resolution 200 mV accuracy in 0 10 VDC applications Terminations Input Output Fixed Screw Terminal Blocks SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable...

Страница 18: ...N CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MIL...

Отзывы: