Table 7: UI Inputs and Jumper Labels

Universal Input Label

Jumper Label on Circuit Board

Label

IN4

J4

IN5

J5

IN6

J6

IN7

J7

IN8

J8

Commissioning

You commission expansion modules with Controller

Configuration Tool (CCT) software, using a

Bluetooth Wireless Commissioning Converter

(BTCVT), through Mobile Access Portal (MAP)

Gateway at version 4.2 or above, or in BACnet router

mode when connected to a Supervisory Controller.

Refer to the 

Controller Tool Help (LIT-12011147)

 for

detailed information on commissioning expansion

modules.

Note: 

The MAP Gateway serves as a

replacement for the BTCVT, which is no longer

available for purchase, but continues to be

supported.

Firmware Package File

The MS-FCP-0 equipment controller firmware

package files are required for CCT to configure and

commission the controllers. The firmware package

files also allow you to upgrade an existing controller

to the latest firmware release available for that

controller.
Beginning at CCT Release 13, the firmware package

files are orderable separately; they are not included

with CCT. They are obtained from the 

Metasys 

software licensing portal, and are loaded and

licensed on the computer/server that is running

CCT.
For additional information about the firmware

package files, refer to the 

CCT Installation Instructions

(LIT-12011259)

.

Troubleshooting

Observe the Status LEDs on the front of the

expansion module. Table 8 provides LED status

indicator information for troubleshooting the

expansion module.

Table 8: Status LEDs and description of LED states

LED label

LED color

Normal LED state Description of LED states

POWER

Green

On Steady

Off Steady = No Supply Power or the expansion module’s polyswitch/resettable

fuse is open. Check Output wiring for short circuits and cycle power to expansion

module.
On Steady = Power Connected

FAULT

Red

Off Steady

Off Steady = No Faults
On Steady = Device Fault
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation

SA/FC BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring

EOL

Amber

Off (Except on

terminating devices)

On Steady = EOL switch in ON position
Off Steady = EOL switch in OFF position

Repair information

If an expansion module fails to operate within its

specifications, replace the expansion module. For

a replacement expansion module, contact your

Johnson Controls representative.

IOM2723 Input/Output Module Installation Guide

15

Содержание IOM2723

Страница 1: ...sonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed an...

Страница 2: ...e can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm DIN rail whenever possible Mount the expansion module in the proper mountin...

Страница 3: ...tion shown in Figure 2 2 Pull the two bottom mounting clips outward from the expansion module to the extended position Figure 3 3 Hang the expansion module on the DIN rail by the hooks at the top of t...

Страница 4: ...a on incor recte risquent d endommager irr m diablement l quipement Important Do not exceed the expansion module electrical ratings Exceeding expansion module electrical ratings can result in permanen...

Страница 5: ...ray removable 3 terminal plug that fits into a board mounted jack on the top right of the expansion module Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the t...

Страница 6: ...outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted...

Страница 7: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 8: ...re See Figure 7 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 9: ...IOM expansion module does not supply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0...

Страница 10: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal...

Страница 11: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 12: ...sitions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 127 are the valid addresses for these expansion modules The following table describes the...

Страница 13: ...ress is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting w...

Страница 14: ...is a terminating device on the FC bus set the EOL switch to ON If the expansion module is not a terminating device on the bus set the EOL switch to OFF When an expansion module is connected to power w...

Страница 15: ...puter server that is running CCT For additional information about the firmware package files refer to the CCT Installation Instructions LIT 12011259 Troubleshooting Observe the Status LEDs on the fron...

Страница 16: ...VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additio...

Страница 17: ...y Input 15 bit resolution Output 15 bit resolution 200 mV accuracy in 0 10 VDC applications Terminations Input Output Fixed Screw Terminal Blocks SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable...

Страница 18: ...N CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MIL...

Отзывы: