Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and output wiring guidelines

Table 2 provides information and guidelines about

the functions, ratings, and requirements for the

expansion module input and output terminals, and

references guidelines for determining proper wire

sizes and cable lengths.
In addition to the wiring guidelines in Table 2,

observe the following guidelines when wiring

expansion module inputs and outputs:
• Run 

all

 low-voltage wiring and cables separate

from high-voltage wiring.

• All input and output cables, regardless of wire

size or number of wires, should consist of

stranded, insulated, and twisted copper wires.

• Shielded cable is not required for input or output

cables.

• Shielded cable is recommended for input

and output cables that are exposed to high

electromagnetic or radio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)

typically do not require an offset in the software

setup. Cable-runs over 30 m (100 ft) may require

an offset in the input/output software setup.

IOM2723 Input/Output Module Installation Guide

6

Содержание IOM2723

Страница 1: ...sonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed an...

Страница 2: ...e can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm DIN rail whenever possible Mount the expansion module in the proper mountin...

Страница 3: ...tion shown in Figure 2 2 Pull the two bottom mounting clips outward from the expansion module to the extended position Figure 3 3 Hang the expansion module on the DIN rail by the hooks at the top of t...

Страница 4: ...a on incor recte risquent d endommager irr m diablement l quipement Important Do not exceed the expansion module electrical ratings Exceeding expansion module electrical ratings can result in permanen...

Страница 5: ...ray removable 3 terminal plug that fits into a board mounted jack on the top right of the expansion module Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the t...

Страница 6: ...outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted...

Страница 7: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 8: ...re See Figure 7 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 9: ...IOM expansion module does not supply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0...

Страница 10: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal...

Страница 11: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 12: ...sitions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 127 are the valid addresses for these expansion modules The following table describes the...

Страница 13: ...ress is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting w...

Страница 14: ...is a terminating device on the FC bus set the EOL switch to ON If the expansion module is not a terminating device on the bus set the EOL switch to OFF When an expansion module is connected to power w...

Страница 15: ...puter server that is running CCT For additional information about the firmware package files refer to the CCT Installation Instructions LIT 12011259 Troubleshooting Observe the Status LEDs on the fron...

Страница 16: ...VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additio...

Страница 17: ...y Input 15 bit resolution Output 15 bit resolution 200 mV accuracy in 0 10 VDC applications Terminations Input Output Fixed Screw Terminal Blocks SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable...