background image

2. Pivot the top of the cover further to release it

from the lower two latches.

3. Replace the cover by placing it squarely over

the base, and then gently and evenly push the

cover on to the latches until they snap into the

latched position.

Figure 9: Controller with cover removed

Setting the End-of-Line (EOL) switch

Each expansion module has an EOL switch. When

the EOL switch is set to ON, it sets the expansion

module as a terminating device on the bus. See

Figure 10 for the EOL switch location. The default

EOL switch position is OFF.

Figure 10: End-of-Line switch positions

To set the EOL switch on an expansion module,

complete the following steps:

1. Determine the physical location of the

expansion module on the SA or FC bus.

2. Determine if the expansion module must be set

as a terminating device on the bus.

Note: 

The EOL termination rules for SA

buses and FC buses are different. Refer to

the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

 for detailed information

regarding EOL termination rules and EOL

switch settings on SA and FC buses.

3. If the expansion module is a terminating device

on the FC bus, set the EOL switch to ON. If the

expansion module is not a terminating device

on the bus, set the EOL switch to OFF.

When an expansion module is connected to power

with its EOL switch set to ON, the amber EOL LED on

the expansion module cover is lit.

UI current loop jumpers

The UI current loop fail-safe jumpers are on the

circuit board under the expansion module cover

near the UI terminals. When a UI is defined (in the

system software) as a 4 to 20 mA Analog Input

and the UI’s current loop jumper is in the Disabled

(default) position (Figure 11), the 4 to 20 mA current

loop circuit opens whenever power to the expansion

module is interrupted or off.

Figure 11: Current loop jumper positions

Setting the current loop jumper to the Enabled

position (Figure 11) connects an internal 100 ohm

resistor across the UI terminals, which maintains the

4 to 20 mA current loop circuit even when power to

the expansion module is interrupted or off.

Important: 

Current Loop jumpers must be in

the Disabled (default) position for all UIs that

are not set up to operate as 4 to 20 mA analog

inputs.

Table 7: UI Inputs and Jumper Labels

Universal Input Label

Jumper Label on Circuit Board

Label

IN1

J1

IN2

J2

IN3

J3

IOM2723 Input/Output Module Installation Guide

14

Содержание IOM2723

Страница 1: ...sonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed an...

Страница 2: ...e can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm DIN rail whenever possible Mount the expansion module in the proper mountin...

Страница 3: ...tion shown in Figure 2 2 Pull the two bottom mounting clips outward from the expansion module to the extended position Figure 3 3 Hang the expansion module on the DIN rail by the hooks at the top of t...

Страница 4: ...a on incor recte risquent d endommager irr m diablement l quipement Important Do not exceed the expansion module electrical ratings Exceeding expansion module electrical ratings can result in permanen...

Страница 5: ...ray removable 3 terminal plug that fits into a board mounted jack on the top right of the expansion module Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the t...

Страница 6: ...outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted...

Страница 7: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 8: ...re See Figure 7 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 9: ...IOM expansion module does not supply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0...

Страница 10: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal...

Страница 11: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 12: ...sitions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 127 are the valid addresses for these expansion modules The following table describes the...

Страница 13: ...ress is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting w...

Страница 14: ...is a terminating device on the FC bus set the EOL switch to ON If the expansion module is not a terminating device on the bus set the EOL switch to OFF When an expansion module is connected to power w...

Страница 15: ...puter server that is running CCT For additional information about the firmware package files refer to the CCT Installation Instructions LIT 12011259 Troubleshooting Observe the Status LEDs on the fron...

Страница 16: ...VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additio...

Страница 17: ...y Input 15 bit resolution Output 15 bit resolution 200 mV accuracy in 0 10 VDC applications Terminations Input Output Fixed Screw Terminal Blocks SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable...

Страница 18: ...N CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MIL...

Отзывы: