![Johnson Controls Frick RXB Plus 12 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/johnson-controls/frick-rxb-plus-12/frick-rxb-plus-12_installation-operation-and-maintenance_2023231050.webp)
RXB PLUS ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
070.101-IOM (JAN 13)
Page 50
R-717 TX VALVE SIZES
TX VALVE MODE PORT SIZE
DISCHARGE TUBE SIZE
.
DAE..-...1.
1/16.
1/32
.
DAE..-...2.
1/16.
1/16
.
DAE..-...5.
7/64.
5/64
.
DAE..-..10.
3/16.
7/64
.
DAE..-..15.
3/16.
5/32
.
AAE..-...20.
5/16.
1/8
.
AAE..-...30.
5/16.
5/32
.
AAE..-...50.
3/8.
3/16
.
AAE..-...75.
3/8.
NONE
.
AAE..-..100.
7/16.
NONE
JORDAN TEMPERATURE REGULATOR
VALVE
To.increase.or.decrease.the.discharge.temperature/oil.tem-
perature,.adjust.the.knurled.nut.located.on.the.actuator.stem.
of.the.Jordan.Temperature.regulator.valve..The.temperature.
is.allowed.to.increase.as.the.nut.is.turned.higher.on.the.stem.
and.decreases.as.the.nut.is.turned.lower.
In.situations.where.system.load.conditions.increase.or.de-
crease.over.extended.periods.of.time.and.the.liquid.injection.
thermal.expansion.valve.is.not.adequate.for.the.new.condi-
tions,.an.improvement.in.valve.perfor.mance.may.be.achieved.
by.increasing.or.decreasing.discharge.tube.size.
NOTE: DO NOT ATTEMPT TO ADJUST SUPERHEAT
ADJUSTMENT STEM ON BOTTOM OF VALVE IN AN EF-
FORT TO CHANGE THE VALVE’S PERFORMANCE. THIS
ADJUSTMENT IS PRESET AT THE FACTORY. ONLY AD-
JUST 1/4” BLEED VALVE ON EQUALIZING LINE.
THERMAL EXPANSION VALVES
JORDAN TEMPERATURE REGULATOR VALVE
(For low differential pressure applications)
TYPE D THERMAL EXPANSION VALVE (1-15 TONS)
R-717
TYPE A THERMAL EXPANSION VALVE (20-100 TONS)
R-717
Содержание Frick RXB Plus 12
Страница 65: ...RXB PLUS ROTARY SCREW COMPRESSOR UNITS MAINTENANCE 070 101 IOM JAN 13 Page 65 OPERATING LOG SHEET ...
Страница 66: ......
Страница 67: ......