RXB PLUS ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
070.101-IOM (JAN 13)
Page 42
TROUBLESHOOTING
THE RXB PLUS MICROPROCESSOR
This. section. contains. information. on. troubleshooting. and.
making. corrections. to. the. microprocessor. and. control. cir-
cuits. of. the.
RXB PLUS
. unit..The. section. is. composed. of.
four.parts:.a.general.information.section,.a.trouble.shoot.ing.
guide,.a.repair.procedure.guide,.and.a.section.with.illustra.tive.
schematics.and.data.
GENERAL INFORMATION
THE COMPONENTS WITHIN THE
MICRO PROCESSOR CONSOLE
CAN BE INADVERTENTLY DAM-
AGED BY STATIC ELECTRICITY OR MIS HANDLING.
ONLY QUALIFIED TECH NICIANS SHOULD DIRECTLY
HANDLE THESE COMPONENTS.
1. DO NOT REMOVE
.the.microprocessor.console.cover.or.
attempt. to. make. corrections. to. the. microprocessor. power.
supply. without. shutting. off. the. control. power.. . Accidental.
shorts.can.irreparably.damage.the.SBC.(single.board.com-
puter).or.the.display.screen.
2. DO NOT HANDLE
.the.SBC.or.the.display.screen.board.
when.their.cables.are.disconnected.without.first.attaching.
a. ground. strap. to. prevent. static. electrcial. discharge. from.
your.body.
Most. problems. encountered. with. the. microprocessor. and.
control.circuits.will.be.the.result.of.a.wiring.fault,.blown.fuse,.
or.failure.of.a.peripheral.control.such.as.a.sole.noid.coil.or.a.
pressure.transducer...Faults.in.the.com.puter,.while.pos.sible,.
are.unlikely..If.a.fault.devel.ops.in.the.computer,.the.prob-
ability.is.that.all.func.tions.will.cease.and.the.display.screen.
will.go.blank.
The.control.system.of.the.
RXB PLUS
.compressor.con.sists.
of.a.120.volt.AC.(high.voltage).side.and.a.DC.(low.voltage).
side..The.120.volt.side.actuates.sole.noids,.relays,.alarms,.
and.other.electro.mechanical.functions..The.DC.side.operates.
the.computer.and.its.various.sensors..The.micro.proces.sor.
console.contains.the.SBC.(single.board.com.puter).and.one.
display.screen.
When working within the micropro-
cessor con sole, 120 VOLTS CAN
CAUSE INJURY OR DEATH.
To.troubleshoot.the.low-voltage.side.of.the.
RXB PLUS
.control.
circuits,.it.is.necessary.to.have.the.following.tools:
.
1..Accurate.digital.multimeter.*
.
2..Small.wire.stripper.
.
3..Small.screwdriver.
.
4..Small.snip.nose.pliers.
.
5..15.watt.soldering.iron.(no.larger).
.
6...032,60/40.rosin.core.solder.
.
7..IC.chip.extraction.and.insertion.tools.*
.
8..Grounding.strap.*
.
9..Static.free.grounded.work.surface.
.
*.Available.from.Frick..Order.kit.no..111Q0451862
TROUBLESHOOTING FRICK SBC MICROPROC ESSOR SYSTEM
(REFER TO WIRING DIAGRAMS)
.
SYMPTOM
PROBABLE CAUSES and CORRECTIONS
. DISPLAY.IS.INOPERATIVE.
Check.the.10.amp.fuse.(2FU).which.controls.all.voltage.going.to.the.microprocessor.
. .
Shut.off.power.to.the.microprocessor.and.confirm.that.all.cable.and.wire.connections
. .
are.made.
. COMPRESSOR.AUXILIARY.
Output.1.controls.the.Compressor.Start.Relay.(2CR)..If.the.compressor.does.not.start
. SHUTDOWN.
and.the.LED.for.Output.1.is.on,.check.the.fuse.FU1.(1.5.amp)..If.the.problem.persists,
. .
check.the.interposing.relay.(2CR).
. .
The.Compressor.Starter.Auxiliary.Contacts.turn.on.Input.5.when.they.are.closed.
. .
These.contacts.are.located.on.the.Compressor.Starter.
. OIL.HEATERS.DO.NOT.
The.oil.heaters.should.operate.only.when.the.compres.sor.is.NOT.running.and.the.oil.in.the
. OPERATE.
separator.sump.is.cold.
. .
If.the.oil.heaters.do.not.work,.check.fuse.1FU.(10.amp)..If.the.fuse.is.not.blown,.check.between
. .
Wires.25.and.2..If.120VAC.is.not.found,.check.between.wires.26.and.2..If.120VAC.is.found
. .
between.wires.26.and.2,.the.Oil.Heater.Relay.is.defective..Next,.check.the.voltage.between
. .
Wires.11.and.2..If.120.VAC.is.present,.the.Oil.Heater.Relay.is.defective.
. .
If.you.do.not.read.120VAC.between.Wires.9.and.2.when.the.LED.for.output.10.is.on,.check.the
. .
fuse.(FU10).
Содержание Frick RXB Plus 12