RXB PLUS ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.101-IOM (JAN 13)
Page 21
unauthorized.tam.pering.with.the.various.adjustable.set.points..
When.enabled,.the.microprocessor.keyboard.is.fully.opera-
tive.and.the.security.lockout.is.not.in.ef.fect..When.disabled,.
the.keyboard.is.rendered.partially.nonfunctional..All.displays.
will.still.be.accessible.through.the.keyboard..If.any.attempt.
is. made. to. enter. new. adjustable. set.points,. how.ever,. the.
microprocessor.will.default.to.the.Se.curity.display..
TO ENABLE THE KEYBOARD,
.press.the.
[STEP]
.key.so.that.
the.brackets.beside.Enter.Access.Code.flash;.key.the.proper.
five.digit.access.code.and.press.
[ENTER]
..The.Setpoints.
Access.will.toggle.from.disabled.to.enabled.and.adjus.table.
setpoint.entry.is.now.possible.
TO DISABLE THE KEYBOARD,
. press. the.
[F2]
. function.
key. to. call. up. the. Security. display;. press. the.
[STEP]
. key.
until.the.brackets.beside.Enter.Access.Code.flash;.key.the.
proper.five.digit.access.code.and.press.
[ENTER]
...Now.press.
the.
[STEP]
.key.until.the.brackets.beside.Set.points.Access.
flash;.and.press.the.
[CHANGE]
.key.to.toggle.from.enabled.
to.disabled.
TO CHANGE THE ACCESS CODE,
.press.the.
[F2]
.function.
key.to.call.up.the.Security.display;.press.the.
[STEP]
.key.until.
the.brackets.beside.Enter.Access.Code.flash;.key.the.proper.
five.digit.access.code.and.press.
[ENTER]
...Now,.select.the.
Enter.Access.Code.a.second.time.by.pressing.the.
[STEP]
.key.
until.the.brackets.beside.Setpoints.Access.flash;.key.in.the.
new.five.digit.access.code.and.press.
[ENTER]
.
NOTE: Power loss will not effect the Security display.
NOTE: IF NO ACCESS CODE WAS ENTERED AND THE
DIS ABLED COMMAND WAS SELECTED, THE ACCESS
CODE IS [00000].
LOST OR FORGOTTEN ACCESS CODE:
. Consult. Frick.
Com.pany.for.assistance.
SETBACK DISPLAY *
. SETBACK.DISPLAY.
Thu.03-01-89.15:33:36
. Setback.Setpoint-[05.0.g.].Active-[No.]
. .
Mon.Start.Time-[-.-:-.-]
. F1.To.Exit.
Stop..Time-[-.-:-.-]
The.
[F3]
.function.key.will.call.up.the.Setback.display..The.
Setback.feature.enables.automatic.operation.at.two.separate.
suction.conditions.on.a.preset.time.schedule..Having.entered.
the.desired.Setback.setpoint,.enter.the.start.and.stop.time.
or.times.and.select.Active:.(Yes).or.(No).
NOTE: To change the Setback setpoints, refer to “TO
CHANGE THE ADJUSTABLE SETPOINTS”
.*Display.for.illustrative.purposes.only.
AUTO CYCLE DISPLAY *
. AUTO.CYCLE.
Compressor.Start.---[20.0.g.]..
. F1.To.Exit.
Compressor.Stop.---[18.0.hg]..
. Suct.Press..
Min..Cap..Control.----[050%].....
. =[03.5.g.].
Auto.Cycle.Active.---[No.]
The.Auto.Cycle.display.is.accessed.by.pressing.
[F4]
..The.
Auto. Cycle. display. provides. for. independent.ly. adjust.able.
setpoints.to.turn.the.compressor.on.and.off.in.re.sponse.to.
the.suction.pressure.or.as.an.adjustable.setpoint.to.limit.the.
minimum.slide.valve.position.
NOTE: To change the Auto Cycle setpoints, refer to “TO
CHANGE THE ADJUSTABLE SETPOINTS”
SUCT.PRESS.
.-.Constantly.monitors.and.dis.plays.the.suc-
tion.pressure.in.pounds.per.square.inch.gauge.(g).or.inches.
of.mercury.(hg).
COMPRESSOR START
.-..Compressor.Start-up.will.bring.
the.compressor.back.on.line.when.the.suction.pres.sure.rises.
to.the.displayed.setpoint.
COMPRESSOR STOP
.-..Compressor.Stop.will.shut.down.the.
unit.if.the.suction.pressure.drops.to.or.below.the.displayed.
setpoint.limit..
NOTE: This limit must be set higher than Low
Suction Pressure Cut out and the Low Suction Pressure
Alarm setpoints.
MIN. CAP. CONTROL
-.Minimum.Capacity.Control,.shown.
as. a. percentage,. will. limit. the. slide. valve. position. to. the.
displayed.setpoint.
AUTO CYCLE ACTIVE
.-..Indicates.whether.Auto.Cycle.is.
active.(YES).or.not.active.(NO)..Press.the.
[CHANGE]
.key.
while.at.this.setpoint.to.change.the.status..Upon.deactiva.tion,.
the.com.pressor.will.return.to.the.previous.mode.of.operation.
ANALOG OFFSET DISPLAY*
. ANALOG.OFFSET:
. .
Suc. Disch. Oil. Sep.
Filt. Spare. Econ
. Temp. +0.
+0.
+0.
+0.
.
+0.0
. Pres. +0.0.
+0.
+0.
.
+0.
.
+0
The.Analog.Offset.Display.is.accessed.by.pressing
[+/-]
key..
All.analog.values.can.be..or.-.3.to.9.units.depending.
on.which.value.is.being.adjusted..Use.the.
[STEP]
.key.to.step.
through.the.desired.setpoint..Press.the.
[CHANGE]
.key.to.
change.the.value.of.the.offset.by.1..The.actual.analog.value.
will.be.displayed.on.the.top.line.of.the.display..The.“Econ”.
and.channels.10,.12,.and.13.are.displayed.but.do.not.pertain.
to.the.program.