RXB PLUS ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.101-IOM (JAN 13)
Page 24
LEAD-LAG OPTION
The. lead-lag. compressor. sequencing. option. provides. the.
controls.for.operating.two.RXB.compressors.in.one.system..
AUTO CYCLE DISPLAY *
. AUTO.CYCLE.
Start[40.0.g.].
Timer[01.min]..
. F1.To.Exit.
Stop.[25.0.g.].
Timer[01.min]..
. Suct.Press.
Min.SV-[50%].
Lead.[Yes].....
. =[35.5.g.].
Active-[No.]
The.software.includes.user.adjustable.setpoints.on.the.Auto.
Cycle.setpoints.screen.(F4.on.Main.Menu).for.the.following:
START -
The.suction.pressure.must.be.greater.than.or.equal.
to.the.“START”.setpoint.in.order.to.start.the.compressor..This.
setpoint.works.in.conjunction.with.the.“Timer”.setpoint.located.
to.the.right.of.it.on.the.Auto.Cycle.setpoints.screen.
(Start) TIMER -
This.is.a.time.delay.used.to.start.the.compres-
sor..The.timer.only.accumulates.time.whenever.the.pressure.
rises.to.or.above.the.“START”.setpoint.and.will.reset.if.the.
pressure.drops.below.the.“START”.setpoint.
STOP -
The.suction.pressure.must.be.less.than.or.equal.to.
the.“STOP”.setpoint.in.order.to.stop.the.compressor..This.
setpoint.works.in.conjunction.with.the.“Timer”.setpoint.located.
to.the.right.of.it.on.the.Auto.Cycle.setpoints.screen.
(Stop) TIMER -
.This.is.a.time.delay.used.to.stop.the.compres-
sor..The.timer.only.accumulates.time.whenever.the.pressure.
drops.to.or.below.the.“STOP”.setpoint.and.will.reset.if.the.
pressure.rises.above.the.“STOP”.setpoint.
MIN SV -
This.setpoint.is.the.minimum.slide.valve.position.and.
is.shown.as.a.percentage..It.will.limit.the.slide.valve.position.
to.the.displayed.setpoint.
LEAD -
This.setpoint.assigns.the.compressor.as.the.lead.or.
the.lag.unit..Press.the.
[CHANGE]
.key.while.at.this.setpoint.
to.change.the.status.
ACTIVE -
.This. setpoint. indicates. whether. the. Auto. Cycle.
Mode.is.active.or.not..Press.the.
[CHANGE]
.key.while.at.this.
setpoint.to.change.the.status.
OPERATION
For.operation.of.the.LEAD-LAG.sequence,.both.units.must.
be.in.Auto.Cycle.compressor.mode.-.one.compressor.micro.
selected. as. the. LEAD. compressor,. the. other. compressor.
selected.as.the.LAG.compressor.-.and.the.slide.valves.must.
be.in.Auto.mode.
With NO Compressor Running
The.lead.will.start.when.its.“START”.setpoint.is.reached.for.
the.amount.of.time.selected.for.the.“TIME”.setpoint.
With ONE Compressor Running
If the load rises:
The. lag. compressor. will. start. when. its. “START”. setpoint.
is.reached.for.the.amount.of.time.selected.for.the.“TIME”.
setpoint.and.the.lead.compressor.is.running.at.100%.slide.
valve.or.running.with.the.motor.load.inhibit.
If the load falls:
The. lead. compressor. will. stop. when. its. “STOP”. setpoint.
is.reached.for.the.amount.of.time.selected.for.the.“TIME”.
setpoint.
With TWO Compressors Running
If the load rises:
The.lead.and.lag.compressor.will.load.independently.
If the load falls:
The.lag.compressor.will.unload.to.its.“MIN.SV”.setpoint..Then.
the.lead.compressor.will.unload.to.its.“MIN.SV”.setpoint..The.
lag.compressor.will.stop.when.the.suction.pressure.drops.
below.the.“STOP”.setpoint.for.the.amount.of.time.selected.
for.the.“TIME”.setpoint.
NOTE: Be careful not to select both compressors as
lead compressors or as lag compressors as improper
operation will result.
NOTE: One compressor will operate as a normal auto
cycle compressor when any one of the following oc-
curs:
a..Power.is.removed.from.one.of.the.two.compressors,
b..Either.of.the.compressors.is.NOT.selected.to.“AUTO”,.or
c.. If. communication. is. lost. between. the. compressors. for.
any.reason.
COMMUNICATIONS TROUBLESHOOTING
Troubleshooting the communications:
Go.to.the.SETPOINTS.DISPLAY.FIXED.Page.2.by.using.the.
[CHANGE]
key.and.the
[ * ]
key..The.display.will.appear.as:
SETPOINTS DISPLAY *
.
. FIXED.
PAGE.2.
Comm..Activity-[...]..
. Hi.Oil.Temp. Cutout.--- [167F].
Alarm.-- [158F]..
. Lo.Oil.Temp. Cutout.-----[49F].
Alarm.----[58F]..
. Lo.Oil.Press..Cutout.----- [005].
Alarm.---- [010]
...........................................
If. the. microprocessor. is. receiving. information. in. the. com-
munications.port.from.the.other.compressor,.a.“1”.will.flash.
between.the.brackets..During.normal.operation.a.“1”.will.flash.
every.5.seconds.
At.the.same.time.information.is.displayed.on.the.lower.right.
hand.corner.of.the.Auto.Cycle.display.concerning.the.lead-
lag.information:
AUTO CYCLE DISPLAY *
. AUTO.CYCLE. Start[20.0.g].
Timer[01.min]..
. F1.to.Exit.
Stop-[25.0.g]. Timer[01.min]..
. Suct.Press.
Min.SV-[50%]. Lead-[Yes].....
. =[35.5.g.].
Active-[Yes]........0101
............................................
This.information.is.either.“0”.or.“1”.and.represents.what.is.
being.sent.from.the.other.compressor..Consult.Frick.Controls.
if.additional.information.is.required.
....*Display.for.illustrative.purposes.only.