100.210-IOM (FEB 2015)
Page 65
VYPER
™
VARIABLE SPEED DRIVE
MAINTENANCE
Load Inhibit - VSD Phase C Baseplate Temperature
Occurs.when.the.Phase.C.baseplate.temperature.reaches.
160°F.and.this.will.inhibit.the.Slide.Valve.from.loading..
Force Unload - VSD Phase C Baseplate Temperature
Occurs.when.the.Phase.C.baseplate.temperature.reaches.
165°F.and.this.will.unload.the.Slide.Valve...
FAULT CODE DESCRIPTIONS
Fault 1 : VSD Board Power Supply
Message
Quantum:..“Fault.1”
Quantum.LX:.“VSD.Board.Power.Supply.Fault”
This.fault.is.set.on.every.power-up..The.fault.is.immediately.
cleared.and.logged.in.the.fault.history.to.record.the.occur-
rence.of.the.power.loss.
Fault 3: VSD Interface Board Motor Current > 15%
Message
Quantum:.“Fault.3”
Quantum.LX:.“VSD.Interface.Board.Motor.Current.>.15%”
This.fault.occurs.whenever.the.Vyper
™
.is.not.running.and.
a.motor.current.of.greater.than.15.%.FLA.is.detected.for.at.
least.ten.seconds.
Fault 4: VSD Interface Board Run Signal
Message
Quantum:.“Fault.4”
Quantum.LX:.“VSD.Interface.Board.Run.Signal.Fault”
This.fault.occurs.if.the.Run.Signal.from.the.Quantum.Control.
Panel.is.high,.but.the.speed.command.being.sent.over.the.
RS-485.communications.link.is.zero..This.fault.may.also.occur.
if.the.Run.Signal.is.low,.but.the.speed.command.is.not.zero...
Both. conditions. must. be. present. for. five. seconds. before.
the.fault.is.set,.and.are.only.applicable.in.automatic.mode.
Fault 5: Interface Board Panel Communications Loss
Message
Quantum:.“Fault.5”
Quantum.LX:.“VSD.\.Board.to.Panel.Comms.Loss”
This.fault.occurs.when.the.VSD.board.loses.communications.
from. the. Quantum
™
LX. Control. Panel,. meaning. it. has. not.
received.any.data.for.a.period.of.fifteen.seconds..This.fault.
is.only.applicable.in.automatic.mode.
Fault 7: Vyper Initialization
Message
Quantum:.“Fault.7”
Quantum.LX:.“VSD.Initialization.Fault”
At. power-up,. all. the. boards. go. through. a. process. called.
initialization.. At. this. time,. memory. locations. are. cleared,.
jumper. positions. are. checked,. and. serial. communications.
links.are.established..There.are.many.causes.for.an.unsuc-
cessful.initialization..The.following.check.list.should.aid.in.
determining.why.the.initialization.has.not.been.completed:
•. The.Control.Center.and.the.Vyper
™
.must.be.energized.at.
the.same.time..The.practice.of.pulling.the.fuse.in.the.con-
trol.center.to.make.wiring.changes.will.create.a.problem..
Power-up.must.be.done.by.closing.the.main.disconnect.
on.the.Vyper
™
.cabinet.with.all.fuses.in.place..Be.sure.you.
do.not.have.an.open.fuse,.causing.loss.of.power.to.the.
Vyper
™
.Logic.board.which.can.cause.this.fault.
FRICK VYPER
™
FAULT CODE LIST
Quantum
™
Lx
Fault Code
Quantum
™
Lx Fault Message
1
VSD.Interface.Board.Power.Supply.Fault
3
VSD.Interface.Board.Motor.Current.>.15%
4
VSD.Interface.Board.Run.Signal.Fault
5
VSD.Interface.Board.to.Panel.Comms.Loss
7
VSD.Initialization.Fault
8
VSD.Stop.Contacts.Fault
9
harmonic.Filter.Logic.Board.Or.Comms.Fault
10
harmonic.Filter.high.Total.Demand.Distortion
11
VSD.high.Phase.B.Inverter.Baseplate.Temp
12
VSD.high.Phase.C.Inverter.Baseplate.Temp
13
VSD.Low.Phase.B.Inverter.Baseplate.Temp
14
VSD.Low.Phase.C.Inverter.Baseplate.Temp
17
VSD.high.Phase.A.Instantaneous.Current
18
VSD.high.Phase.B.Instantaneous.Current
19
VSD.high.Phase.C.Instantaneous.Current
21
VSD.Phase.A.Gate.Driver.Fault
22
VSD.Phase.B.Gate.Driver.Fault
23
VSD.Phase.C.Gate.Driver.Fault
24
VSD.Single.Phase.Input.Power.Fault
27
VSD.105%.Motor.Current.Overload.Fault
28
VSD.high.DC.Bus.Voltage.Fault
29
VSD.Logic.Board.Power.Supply.Fault
33
VSD.Low.DC.Bus.Voltage.Fault
34
VSD.DC.Bus.Voltage.Imbalance.Fault
35
VSD.high.Internal.Ambient.Temp.Fault
36
VSD.high.Phase.A.Inverter.Baseplate.Temp
37
VSD.Logic.Board.Processor.Fault
38
VSD.Run.Signal.Fault
39
VSD.high.Converter.heatsink.Temp.Fault
40
VSD.Invalid.Current.Scale.Selection
41
VSD.Low.Phase.A.Inverter.Baseplate.Temp
42
VSD.Serial.Communication.Fault
43
VSD.Precharge.Lockout.Fault
44
VSD.Low.Converter.heatsink.Temp.Fault
45
VSD.Current.Imbalance.Fault
46
VSD.Precharge.-..DC.Bus.Voltage.Imbalance.
47
VSD.Precharge.-.Low.DC.Bus.Voltage.2
48
VSD.Precharge.-.Low.DC.Bus.Voltage.1
50
harmonic.Filter.high.DC.Bus.Voltage.Fault
51
harmonic.Filter.high.Phase.C.Current.Fault
52
harmonic.Filter.high.Phase.B.Current.Fault
53
harmonic.Filter.high.Phase.A.Current.Fault
54
harmonic.Filter.Phase.Locked.Loop.Fault
56
harmonic.Filter.Logic.Board.Power.Supply
65
harmonic.Filter.Precharge.-.high.DC.Bus.Voltage
66
harmonic.Filter.Precharge.-.Low.DC.Bus.Voltage
67
harmonic.Filter.DC.Current.Transformer.1
68
harmonic.Filter.DC.Current.Transformer.2
69
harmonic.Filter.high.Baseplate.Temp.Fault
71
harmonic.Filter.Low.DC.Bus.Voltage
75
harmonic.Filter.DC.Bus.Voltage.Imbalance
76
harmonic.Filter.110%.Input.Current.Overload
77
harmonic.Filter.Run.Signal.Fault
81
VSD.Interface.Board.NovRAM.Failure
83
harmonic.Filter.Serial.Communication
84
harmonic.Filter.Input.Frequency.Out.of.Range
TABlE 20 - FAUlT CoDE lIST
•. The.EPROMs.must.be.correct.for.each.board,.and.they.
must.be.correctly.installed..There.are.a.total.of.seven.(7).
EPROMs.in.each.Vyper
™
.system..These.EPROMs.are.cre-
ated.as.a.set,.and.cannot.be.intermixed..All.pins.must.be.
properly.inserted.into.the.EPROM.sockets..
•. Serial.data.must.be.established..(See:.Serial.Communi-
cation. Fault”. error. code).. If. communications. between.
the.Vyper
™
.Logic,.Filter.Logic,.and.Interface.Boards.and.
Quantum
™
.panel.does.not.take.place.during.initialization,.
Fault.5.message.will.appear.before.any.other.message.can.
Содержание Frick 572
Страница 16: ...100 210 IOM FEB 2015 Page 16 VYPER VARIABLE SPEED DRIVE INSTALLATION OPERATION MAINTENANCE Notes ...