100.210-IOM (FEB 2015)
Page 64
VYPER
™
VARIABLE SPEED DRIVE
MAINTENANCE
VYPER
™
ALARMS / SHUTDOWNS
OVERVIEW
In.addition.to.the.Alarms.and.Shutdowns.that.the.Quantum
™
LX.
software. generates. for. the. basic. compressor. package,.
there.are.warnings.and.shutdowns.that.are.associated.with.
the. Vyper
™
. drive. operation.. These. can. be. initiated. by. the.
Quantum
™
LX.panel.or.the.Vyper
™
.drive..The.following.pages.
describe.these.warnings.and.shutdowns.by.title.and.descrip-
tion.as.well.as.the.cause.and.items.to.check.
When.a.Shutdown.occurs,.the.display.backlight.will.flash.on.
and.off.to.alert.an.operator.of.the.shutdown..This.visual.alarm.
will.help.get.the.attention.of.the.operator.in.a.noisy.engine.
room.environment.where.audible.alarms.may.not.be.heard..
Pressing.any.key.on.the.keypad.will.clear.the.flashing.backlight.
alarm..The.FRICK.VYPER
™
.FAULT.CODES.table.shows.the.full.
listing.of.fault.codes..A.detailed.description.and.troubleshoot-
ing.recommendations.follow..
The.following.warnings.and.or.shutdowns.are.initiated.by.
the. Quantum
™
LX. panel.. These. safeties. are. set. for.
When
Running:
High Motor Stator Temp. –
.If.the.motor.stator.temperature.
rises.above.a.critical.point,.one.or.more.embedded.thermistors.
will.open,.removing.the.digital.input.to.the.Dig..Aux..#1.mod-
ule,.wire.#28.(typical)..There.is.one.thermistor.per.winding.
If.the.motor.is.equipped.with.stator.RTDs.(one.per.winding).
the.same.result.will.occur.only.that.the.signal.is.now.an.ana-
log.signal.and.is.set.up.as.one.of.the.PhD.monitoring.chan-
nels..The.warning.and.shutdown.values.can.be.seen.on.the.
PhD.setpoints.screen.of.the.Quantum
™
LX.panel.and.should.
be.set.based.on.the.limits.of.the.motor’s.insulation.class..
Blower Motor Aux. –
.If.the.motor.is.equipped.with.auxiliary.
blowers.mounted.to.the.top.of.the.main.drive.motor,.then.a.
confirmed.run.signal.is.required..This.signal.is.in.the.form.of.
a.digital.signal.from.the.Aux..Contacts.of.the.blower.motor.
starter/s.and.is.received.by.Dig..Aux..#2,.wire.#29.(typical).
High Vyper Coolant Temp. –
.The.Vyper.Coolant.Temp..is.
monitored. by. the. Quantum
™
LX. Panel. from. a. temperature.
probe.mounted.at.the.coolant.reservoir.on.analog.auxiliary.
#9.(Ch..13.analog.brd.#2)..If.the.Vyper
™
.Coolant.exceeds.the.
high.Temp.Warning.or.Shutdown.values.for.the.delays,.this.
warning.or.shutdown.will.occur..These.values.can.be.seen.
on.page.2.of.the.Analog.Auxiliaries.setpoints.screens..Default.
settings.are.130°F.for.the.warning,.135°F.for.the.shutdown.
Low Vyper Coolant Temp. –
.The.Vyper.Coolant.Temp..is.
monitored. by. the. Quantum
™
LX. Panel. from. a. temperature.
probe.mounted.at.the.coolant.reservoir.on.analog.auxiliary.
#9.(Ch..13.analog.brd.#2)..If.the.Vyper.Coolant.exceeds.the.
Low.Temp.Warning.or.Shutdown.values.for.the.delays,.this.
warning.or.shutdown.will.occur..These.values.can.be.seen.
on.page.2.of.the.Analog.Auxiliaries.setpoints.screens..Default.
settings.are.85°F.for.the.warning,.80°F.for.the.shutdown.
NOTICE
If the compressor has been down for an extended period
and the ambient temperature is less than the Low Vyper
Coolant Temp. warning or shutdown values, it may be
necessary to lower these settings temporarily in order
to get the drive running.
WARNING
This setpoint can never be set lower than 5°F above
ambient dry bulb temperature. If not sure of dry bulb
temperature, DO NOT GUESS.
Once.the.drive.is.running.with.the.coolant.temperature.back.
above.the.default.setting.for.this.safety,.go.back.and.change.
them.to.85°F.for.the.warning.and.80°F.for.the.shutdown.
The. warnings. and. shutdowns. on. the. following. pages. are.
initiated. by. the. Vyper
™
. drive. and. communicated. to. the.
Quantum
™
LX.panel.for.display.and.clearing.purposes.
QUANTUM
™
Lx LOAD INHIBIT,
FORCE UNLOAD MESSAGES
Load Inhibit - VSD Ambient Temperature
Occurs.when.the.Vyper.cabinet.temperature.reaches.130°F.
and.this.will.inhibit.the.Slide.Valve.from.loading...
Force Unload - VSD Ambient Temperature
Occurs.when.the.Vyper.cabinet.temperature.reaches.135°F.
and.this.will.unload.the.Slide.Valve...
Load Inhibit - VSD Converter Heatsink Temp
Occurs.when.the.converter.heatsink.temperature.reaches.
155°F.and.this.will.inhibit.the.Slide.Valve.from.loading...
Force Unload - VSD Converter Heatsink Temp
Occurs.when.the.converter.heatsink.temperature.reaches.
160°F.and.this.will.unload.the.Slide.Valve...
Load Inhibit - Harmonic Filter Baseplate Temperature
Occurs. when. the. harmonic. filter. baseplate. temperature.
reaches.175°F.and.this.will.inhibit.the.Slide.Valve.from.loading.
Occurs. when. the. harmonic. filter. baseplate. temperature.
reaches.160°F.and.this.will.inhibit.the.Slide.Valve.from.loading..
Force Unload - Harmonic Filter Baseplate Temperature
Occurs. when. the. harmonic. filter. baseplate. temperature.
reaches.180°F.and.this.will.unload.the.Slide.Valve...
Occurs. when. the. harmonic. filter. baseplate. temperature.
reaches.165°F.and.this.will.unload.the.Slide.Valve....
Load Inhibit - VSD Baseplate Temperature
Occurs.when.the.baseplate.temperature.reaches.160°F.and.
this.will.inhibit.the.Slide.Valve.from.loading..
Force Unload - VSD Baseplate Temperature
Occurs.when.the.baseplate.temperature.reaches.165°F.and.
this.will.unload.the.Slide.Valve..
Load Inhibit - VSD Phase A Baseplate Temperature
Occurs.when.the.Phase.A.baseplate.temperature.reaches.
160°F.and.this.will.inhibit.the.Slide.Valve.from.loading..
Force Unload - VSD Phase A Baseplate Temperature
Occurs.when.the.Phase.A.baseplate.temperature.reaches.
165°F.and.this.will.unload.the.Slide.Valve..
Load Inhibit - VSD Phase B Baseplate Temperature
Occurs.when.the.Phase.B.baseplate.temperature.reaches.
160°F.and.this.will.inhibit.the.Slide.Valve.from.loading..
Force Unload - VSD Phase B Baseplate Temperature
Occurs.when.the.Phase.B.baseplate.temperature.reaches.
165°F.and.this.will.unload.the.Slide.Valve..
Содержание Frick 572
Страница 16: ...100 210 IOM FEB 2015 Page 16 VYPER VARIABLE SPEED DRIVE INSTALLATION OPERATION MAINTENANCE Notes ...
Страница 18: ...100 210 IOM FEB 2015 Page 18 VYPER VARIABLE SPEED DRIVE INSTALLATION Figure 7 Vyper Cabinet and Stand ...
Страница 40: ...100 210 IOM FEB 2015 Page 40 VYPER VARIABLE SPEED DRIVE INSTALLATION OPERATION MAINTENANCE Notes ...
Страница 60: ...100 210 IOM FEB 2015 Page 60 VYPER VARIABLE SPEED DRIVE INSTALLATION OPERATION MAINTENANCE Notes ...