100.210-IOM (FEB 2015)
Page 30
VYPER
™
VARIABLE SPEED DRIVE
INSTALLATION
VYPER
™
POWER AND CONTROL ENTRY LOCATIONS
Figure 18 - Vyper
™
Cabinet Power and Control Entry locations
Vyper.drives.provide.a.removable.plate.on.the.top.left.of.the.
cabinet.that.designates.the.point.of.entry.for.the.incoming.
power..This.is.the.only.acceptable.point.of.entry.for.power.
into. a. Vyper. drive.. This. plate. must. be. removed. for. the.
proper.sized.holes.to.be.punched.and.then.reinstalled..For.
remote.mounted.cabinets,.the.power.exits.through.the.top.
of.a.separate.motor.connection.box..The.holes.on.this.box.
can.be.punched.in.place.since.there.is.no.chance.for.metal.
filings.to.fall.into.the.electronics.of.the.drive..
Under.no.circumstances.is.it.acceptable.to.bring.power.into.
or.take.power.out.of.a.Vyper.at.any.other.point.
It.is.possible.to.come.up.through.the.floor,.alongside.of.the.
Vyper,.then.turn.in.and.down.into.the.drive..All.NEC.codes.
relative.to.conductor.size.and.bend.radius.must.be.followed.