100.210-IOM (FEB 2015)
Page 21
VYPER
™
VARIABLE SPEED DRIVE
INSTALLATION
Figure 10 - Pressure Drop vs. Flow rate
HEAT ExCHANGER PRESSURE DROP 912/752 & 700/572 Models
Figure 9 - minimum Flow rates - glyCol
In.order.to.adequately.size.piping.and.booster.pump.require-
ments,. the. pressure. drop. of. the. coolant. across. the. heat.
exchanger.must.be.known..Figure.10.provides.installation.
designers.with.pressure.drop.reference.for.different.mixtures.
of.propylene.glycol.and.water..