For wet pipe system installations of 1 

in. NPT Series DS-2 Dry-Type Sprin-

klers connected to CPVC piping, use 

only the following TYCO CPVC fittings:
•  1 in. x 1 in. NPT Female Adapter (P/N 

80145)

•  1 in. x 1 in. x 1 in. NPT Sprinkler Head 

Adapter Tee (P/N 80249)

For dry pipe system installations, 

use only the side outlet of maximum  

2 1/2 in. reducing tee when locat-

ing Series DS-2 Dry-Type Sprinklers 

directly below the branch line. Oth-

erwise, use the configuration shown 

in Figure 9 to assure complete water 

drainage from above Series DS-2 Dry-

Type Sprinklers and the branchline. 

Failure to do so may result in pipe 

freezing and water damage.

NOTICE

Do not install Series DS-2 Dry-Type 

Sprinklers into any other type fitting.

Failure to use the appropriate fitting 

may result in one of the following:
•  failure of the sprinkler to operate 

properly due to formation of ice over 

the Inlet Plug or binding of the Inlet 

Plug

•  insufficient engagement of the 

Inlet pipe-threads with consequent 

leakage

Drainage

In accordance with the minimum 

requirements of the NATIONAL FIRE 

PROTECTION ASSOCIATION for dry 

pipe sprinkler systems, branch, cross, 

and feed-main piping connected to Dry 

Sprinklers and subject to freezing tem-

peratures must be pitched for proper 

drainage.

Exposure Length

When using dry sprinklers in wet pipe 

sprinkler systems to protect areas 

subject to freezing temperatures, use 

Table C to determine a sprinkler’s 

appropriate exposed barrel length to 

prevent water from freezing in the con-

necting pipes due to conduction. The 

exposed barrel length measurement 

must be taken from the face of the 

sprinkler fitting to the surface of the 

structure or insulation that is exposed 

to the heated area. See Figure 9 for an 

example.
For protected area temperatures 

between those given above, the 

minimum recommended length from 

the face of the fitting to the outside of 

the protected area may be determined 

by interpolating between the indicated 

values.

You can also install Series DS-2 Dry-

Type Sprinklers in the 1 in. NPT outlet 

of a GRINNELL Figure 730 Mechanical 

Tee. However, the use of the Figure 730 

Tee for this arrangement is limited to 

wet pipe systems.
The configuration shown in Figure 8 is 

only applicable for wet pipe systems 

where the sprinkler fitting and water-

filled pipe above the sprinkler fitting are 

not subject to freezing and where the 

length of the Dry-Type Sprinkler has the 

minimum exposure length depicted in 

Figure 9. See the Exposure Length 

section.

Sprinkler Fittings

Install 1 in. NPT Series DS-2 Dry-Type 

Sprinklers in the 1 in. NPT outlet or run 

of the following fittings:
•  malleable or ductile iron threaded 

tee fittings that meet the dimensional 

requirements of ANSI B16.3 (Class 

150)

•  cast iron threaded tee fittings that 

meet the dimensional requirements 

of ANSI B16.4 (Class 125)

Do not install Series DS-2 Dry-Type 

Sprinklers into elbow fittings. The Inlet 

of the sprinkler can contact the interior 

of the elbow.
The unused outlet of the threaded tee is 

plugged as shown in Figure 10.

SIDE

OUTLET

PLUGGED

TO WET

SYSTEM

FITTING

(SEE DESIGN

CRITERIA

SECTION)

SPRINKLER

DSB-2

BOOT

HEATED

AREA

AREA

SUBJECT

TO

FREEZING

RUN

OUTLET

PLUGGED

TO DRY

SYSTEM

DSB-2

BOOT

FITTING

(SEE DESIGN

CRITERIA

SECTION)

SPRINKLER

HEATED

AREA

(SEE DESIGN

CRITERIA

SECTION)

FACE OF

SPRINKLER

FITTING

LENGTH

EXPOSURE

DSB-2

BOOT

INSULATED

FREEZER

STRUCTURE

(ENDS ON

OPPOSING

SIDES OF

STRAP TIES

BOOT)

ADHESIVE

SHOWN

WITH FLUSH

ESCUTCHEON

DS-2

2-3/4" DIA.

(69,9 mm)

CLEARANCE

HOLE

DSB-2 BOOT

FIGURE 8 

SPRINKLER FITTING 

HEATED AREA

FIGURE 10 

SPRINKLER FITTING 

UNHEATED AREA

FIGURE 9 

EXPOSURE LENGTH

FIGURE 11 

MODEL DSB-2 DRY SPRINKLER 

BOOT WITH SERIES DS-2 

DRY-TYPE PENDENT SPRINKLER

Содержание DS-2 Series

Страница 1: ...Carbon Steel General Description TYCO Series DS 2 Dry Type Sprinklers 11 2K Pendent Extended Coverage Light and Ordinary Hazard ECLH ECOH are decorative glass bulb auto matic sprinklers typically used where pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures for exam ple sprinkler drops from unheated portions of buildings sprinklers and or a portion of the...

Страница 2: ... Figure 3 SPRINKLER FINISH Natural Brass Chromed Plated Polyester Natural Brass Chrome Plated Polyester 135 F 57 C Orange 1 2 3 1 2 3 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Notes 1 UL Listed maximum order length of 48 in 2 C UL Listed maximum order length of 48 in 3 Approved by the City of New York under MEA 173 02 E 286 F 141 C temperature rating applies to installatio...

Страница 3: ...20 F 29 C 14 355 6 150 3 75 30 F 34 C 16 405 8 200 4 100 40 F 40 C 18 455 8 200 4 100 50 F 46 C 20 510 10 255 6 150 60 F 51 C 20 510 10 255 6 150 Notes 1 For protected area temperatures that occur between values listed above use the next cooler temperature 2 These lengths are inclusive of wind velocities up to 30 mph 18 6 kph Response Rating Coverage Area 4 ft x ft m x m Minimum Flow 1 Light Hazar...

Страница 4: ...gure 3 plus 1 4 in 6 3 mm Extended Order Length from Figure 4 plus 3 1 4 in 82 6 mm Without Escutcheon Order Length from Figure 5 minus 2 1 4 in 57 2 mm 2 1 4 1 8 57 2 3 2 mm ORDER LENGTHS 3 to 48 76 2 to 1219 2 mm IN 1 4 6 4 mm INCREMENTS ESCUTCHEON WILL PERMIT 1 4 6 4 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm SPRINKLER FITTING REFER TO DESIGN CRI...

Страница 5: ...5 8 15 9 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING FOR ORDER LENGTHS 3 1 4 82 6 mm 4 7 8 1 8 123 8 3 2 mm or FOR ORDER LENGTHS 3 1 4 82 6 mm 5 5 8 1 8 142 9 3 2 mm 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm ORDER LENGTHS 1 to 45 1 4 25 4 to 1149 4 mm IN 1 4 6 4 mm INCREMENTS SPRINKLER FITTING REFER TO DESIGN CRITERIA SECTION DO NOT FIGURE 4 SERIES DS 2 DRY TYPE PENDENT SPRINKLER ECLH ECOH W...

Страница 6: ...or protected area temperatures between those given above the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values You can also install Series DS 2 Dry Type Sprinklers in the 1 in NPT outlet of a GRINNELL Figure 730 Mechanical Tee However the use of the Figure 730 Tee for this arrangement is limi...

Страница 7: ...s easier when a non hardening sealant was used and torque guidelines were followed After removal inspect the sprinkler for damage Step 3 After installing the ceiling and applying a ceiling finish slide on the outer piece of the Escutcheon until it comes in contact with the ceiling Do not lift the ceiling panel out of its normal position When using the Deep Escutcheon hold the outer piece in contac...

Страница 8: ... applicable Part Number from Table E Sprinkler Wrench Specify W Type 17 Sprinkler Wrench P N 56 010 4 118 Sprinkler Boot Specify Model DSB 2 Dry Sprinkler Boot P N 63 000 0 002 This P N includes one 1 Boot two 2 Strap Ties and 1 3 oz of Adhesive a sufficient quantity for installing one boot Notes 1 Escutcheon Finish applies to sprinklers with escutcheons 2 286 F 141 C temperature rating applies to...

Отзывы: