background image

TFP540

Page 8 of 8

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; 

TEFLON is a registered trademark of DuPont

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indi-

cate the full product name, including 
description and Part Number (P/N).

Dry-Type Sprinkler

When ordering Series DS-2 Dry-Type 

Sprinklers, 11.2K Pendent, Extended 

Coverage, Light and Ordinary Hazard, 

specify the following information:
•  SIN TY5238

•  Order Length:   

Dry-Type Sprinklers are furnished 

based upon Order Length as mea-

sured from the face of the ceiling to 

the face of the sprinkler fitting, see 

Figures 2 to 5. After the measure-

ment is taken, round it to the nearest 

1/4 in. increment.

•  Inlet Connections: 

 

1 In. NPT 

 

(Standard) 

•  ISO 7-R 1 

 

(For information on ISO Inlet Thread 

Connections, contact your Johnson 

Controls Sales Representative.)

•  Temperature Rating
•  Sprinkler Finish
•  Escutcheon Type and Finish, as 

applicable

•  Part Number from Table E

Sprinkler Wrench

Specify W-Type 17 Sprinkler Wrench, 

P/N 56-010-4-118

Sprinkler Boot

Specify Model DSB-2 Dry Sprinkler 

Boot, P/N 63-000-0-002
This P/N includes one (1) Boot, two 

(2) Strap Ties, and 1/3 oz of Adhesive 

(a sufficient quantity for installing one 

boot).

Notes:

1.  Escutcheon Finish applies to sprinklers with escutcheons.
2.  286°F (141°C) temperature rating applies to non-recessed sprin-

kler assemblies.

3.  Dry-Type Sprinklers are furnished based upon “Order Length” 

as measured per Figures 2 to 5, as applicable, and for each indi-
vidual sprinkler where it is to be installed. After the measurement 
is taken, round it to the nearest 1/4 in. increment.

*  

Use Prefix “I” for ISO 7-R 1 Connection  

     (for example, I-61-431-1-372).

 P/N

*

  61  –   XXX  –   X  –   XXX

ORDER 

LENGTH

(3)

055

5.50 in.

082

8.25 in.

180

18.00 in.

187

18.75 in.

372

37.25 in.

480

48.00 in.

SPRINKLER 

FINISH

ESCUTCHEON 

FINISH(1)

0

CHROME 

PLATED

SIGNAL WHITE 

(RAL9003) 

POLYESTER

1

NATURAL 

BRASS

SIGNAL WHITE 

(RAL9003) 

POLYESTER

4

SIGNAL WHITE 

(RAL9003) 

POLYESTER

SIGNAL WHITE 

(RAL9003) 

POLYESTER

5

NATURAL 

BRASS

BRASS 

PLATED

9

CHROME 

PLATED

CHROME 

PLATED

TEMPERATURE 

RATING

(2)

0

135°F (57°C)

1

155°F (68°C)

2

175°F (79°C)

3

200°F (93°C)

4

286°F (141°C)

SIN

40

Pendent with 

Flush Escutcheon

TY5238 

(Figure 2)

41

Pendent with 

Recessed Escutcheon

TY5238 

(Figure 3)

42

Pendent with 

Extended Escutcheon

TY5238 

(Figure 4)

43

Pendent without 

Escutcheon

TY5238 

(Figure 5)

TABLE E 

SERIES DS-2 EXTENDED COVERAGE DRY-TYPE SPRINKLERS 

PART NUMBER SELECTION

Содержание DS-2 Series

Страница 1: ...Carbon Steel General Description TYCO Series DS 2 Dry Type Sprinklers 11 2K Pendent Extended Coverage Light and Ordinary Hazard ECLH ECOH are decorative glass bulb auto matic sprinklers typically used where pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures for exam ple sprinkler drops from unheated portions of buildings sprinklers and or a portion of the...

Страница 2: ... Figure 3 SPRINKLER FINISH Natural Brass Chromed Plated Polyester Natural Brass Chrome Plated Polyester 135 F 57 C Orange 1 2 3 1 2 3 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Notes 1 UL Listed maximum order length of 48 in 2 C UL Listed maximum order length of 48 in 3 Approved by the City of New York under MEA 173 02 E 286 F 141 C temperature rating applies to installatio...

Страница 3: ...20 F 29 C 14 355 6 150 3 75 30 F 34 C 16 405 8 200 4 100 40 F 40 C 18 455 8 200 4 100 50 F 46 C 20 510 10 255 6 150 60 F 51 C 20 510 10 255 6 150 Notes 1 For protected area temperatures that occur between values listed above use the next cooler temperature 2 These lengths are inclusive of wind velocities up to 30 mph 18 6 kph Response Rating Coverage Area 4 ft x ft m x m Minimum Flow 1 Light Hazar...

Страница 4: ...gure 3 plus 1 4 in 6 3 mm Extended Order Length from Figure 4 plus 3 1 4 in 82 6 mm Without Escutcheon Order Length from Figure 5 minus 2 1 4 in 57 2 mm 2 1 4 1 8 57 2 3 2 mm ORDER LENGTHS 3 to 48 76 2 to 1219 2 mm IN 1 4 6 4 mm INCREMENTS ESCUTCHEON WILL PERMIT 1 4 6 4 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm SPRINKLER FITTING REFER TO DESIGN CRI...

Страница 5: ...5 8 15 9 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING FOR ORDER LENGTHS 3 1 4 82 6 mm 4 7 8 1 8 123 8 3 2 mm or FOR ORDER LENGTHS 3 1 4 82 6 mm 5 5 8 1 8 142 9 3 2 mm 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm ORDER LENGTHS 1 to 45 1 4 25 4 to 1149 4 mm IN 1 4 6 4 mm INCREMENTS SPRINKLER FITTING REFER TO DESIGN CRITERIA SECTION DO NOT FIGURE 4 SERIES DS 2 DRY TYPE PENDENT SPRINKLER ECLH ECOH W...

Страница 6: ...or protected area temperatures between those given above the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values You can also install Series DS 2 Dry Type Sprinklers in the 1 in NPT outlet of a GRINNELL Figure 730 Mechanical Tee However the use of the Figure 730 Tee for this arrangement is limi...

Страница 7: ...s easier when a non hardening sealant was used and torque guidelines were followed After removal inspect the sprinkler for damage Step 3 After installing the ceiling and applying a ceiling finish slide on the outer piece of the Escutcheon until it comes in contact with the ceiling Do not lift the ceiling panel out of its normal position When using the Deep Escutcheon hold the outer piece in contac...

Страница 8: ... applicable Part Number from Table E Sprinkler Wrench Specify W Type 17 Sprinkler Wrench P N 56 010 4 118 Sprinkler Boot Specify Model DSB 2 Dry Sprinkler Boot P N 63 000 0 002 This P N includes one 1 Boot two 2 Strap Ties and 1 3 oz of Adhesive a sufficient quantity for installing one boot Notes 1 Escutcheon Finish applies to sprinklers with escutcheons 2 286 F 141 C temperature rating applies to...