Design
Criteria
UL and C-UL Listing
Requirements
TYCO Series DS-2 Dry-Type Sprin-
klers, 11.2K Pendent, Extended Cov-
erage, Light and Ordinary Hazard
are intended for use in fire sprinkler
systems designed in accordance
with the extended coverage installa-
tion rules recognized by the applica-
ble Listing agency (for example, UL
Listing is based on NFPA 13 require-
ments). See Table B for coverage and
flow rate criteria.
Temperature
Rating
Bulb
Color Code
TY5238
with Flush Escutcheon
(Figure 2)
with Extended Escutcheon
(Figure 4)
without Escutcheon
(Figure 5)
TY5238
with Recessed Escutcheon
(Figure 3)
SPRINKLER FINISH
Natural
Brass
Chromed
Plated
Polyester**
Natural
Brass
Chrome
Plated
Polyester**
135°F (57°C)
Orange
1, 2, 3
1, 2, 3
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
286°F (141°C)*
Blue
Notes:
1. UL Listed (maximum order length of 48 in.)
2. C-UL Listed (maximum order length of 48 in.)
3. Approved by the City of New York under MEA 173-02-E
* 286 °F (141 °C) temperature rating applies to installations in Ordniary Hazard Occupancies only.
** Frame and deflector only
COMPRESSION
SCREW
FRAME
INSERT
PLUG WITH
GASKETED SPRING
PLATE SEAL
WATER TUBE
SPRING
CASING
BULB
SEAT
DEFLECTOR
BULB
GUIDE
TUBE
PLUG
SPRING
PIN
INLET
YOKE
VENT HOLE
INLET BAND
FIGURE 1
SERIES DS-2 ECLH/ECOH DRY-TYPE PENDENT SPRINKLER
ASSEMBLY
TABLE A
SERIES DS-2 ECLH/ECOH DRY-TYPE PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS