background image

TFP540

Page 7 of 8

Clearance Space

In accordance with NFPA 13, when 

connecting an area subject to freez-

ing and an area containing a wet pipe 

sprinkler system, the clearance space 

around the sprinkler barrel of Dry-Type 

Sprinklers must be sealed. Due to 

temperature differences between two 

areas, the potential for the formation of 

condensation in the sprinkler and sub-

sequent ice build-up is increased. If 

this condensation is not controlled, ice 

build-up can occur that might damage 

the dry-type sprinkler and/or prevent 

proper operation in a fire situation.
Use of the Model DSB-2 Dry Sprin-

kler Boot, described in Technical Data 

Sheet TFP591 and shown in Figure 11, 

can provide the recommended seal.

Installation

TYCO Series DS-2 Dry-Type Sprin-

klers, 11.2K Pendent, Extended Cover-

age, Light and Ordinary Hazard must 

be installed in accordance with this 

section.

General Instructions

Series DS-2 Dry-Type Sprinklers must 

only be installed in fittings that meet 

the requirements of the Design Cri-

teria section. See the Design Criteria 

section for other important require-

ments regarding piping design and 

sealing of the clearance space around 

the Sprinkler Casing. With reference 

to Figure 7, do not grasp the sprinkler 

by the deflector. Failure to follow this 

instruction may impair performance of 

the device.
Do not install any bulb-type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in. 

(1,6 mm) for the 135°F (57°C) rating to 

1/8 in. (3,2 mm) for the 360°F (182°C) 

rating.
A leak-tight 1 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 20 to  

30 lb-ft (26,8 to 40,2 N·m). Higher 

levels of torque may distort the sprin-

kler Inlet with consequent leakage or 

impairment of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment in an Escutch-

eon Plate by under or over-tightening 

the Sprinkler. Re-adjust the position of 

the sprinkler fitting to suit.

Note:

 Install pendent sprinklers only in 

the pendent position. The deflector of a 

pendent sprinkler must be parallel to the 

ceiling.

Step 1.

 With a non-hardening pipe-

thread sealant such as TEFLON applied 

to the Inlet threads, hand-tighten the 

sprinkler into the sprinkler fitting. Do 

not grasp the sprinkler by the deflec-

tor, see Figure 7.

Step 2.

 Wrench-tighten the sprinkler 

using either:
•  a pipe wrench on the Inlet Band or 

the Casing, see Figure 1

•  a W-Type 17 Sprinkler Wrench on 

the wrench flat (see Figure 6); apply 

the wrench recess of the W-Type 17 

Sprinkler Wrench to the wrench flat

Note:

 If sprinkler removal becomes 

necessary, remove the sprinkler using the 

same wrenching method noted above. 

Sprinkler removal is easier when a non-

hardening sealant was used and torque 

guidelines were followed. After removal, 

inspect the sprinkler for damage.

Step 3.

 After installing the ceiling and 

applying a ceiling finish, slide on the 

outer piece of the Escutcheon until 

it comes in contact with the ceiling. 

Do not lift the ceiling panel out of its 

normal position.
When using the Deep Escutcheon, 

hold the outer piece in contact with the 

mounting surface (ceiling or wall). Then 

rotate the inner piece approximately 1/4 

turn with respect to the outer piece, 

to hold the Deep Escutcheon firmly 

together.

Care and 

Maintenance

TYCO Series DS-2 Dry-Type Sprinklers, 

11.2K Pendent, Extended Coverage, 

Light and Ordinary Hazard must be 

maintained and serviced in accordance 

with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

systems from the proper authorities 

and notify all personnel who may be 

affected by this action.
Absence of the outer piece of an 

escutcheon, which is used to cover a 

clearance hole, may delay the time to 

sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb 

Seat (see Figure 1) to indicate if the Dry 

Sprinkler is remaining dry. Evidence of 

leakage from the Vent Hole indicates 

potential leakage past the Inlet seal 

and the need to remove the sprinkler 

to determine the cause of leakage, 

for example, an improper installation 

or an ice plug. Close the fire protec-

tion system control valve and drain the 

system before removing the sprinkler.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb, see the Installation 

Section.
The owner is responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

compliance with this document, as well 

as with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION, such as NFPA 25, in addition 

to the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Содержание DS-2 Series

Страница 1: ...Carbon Steel General Description TYCO Series DS 2 Dry Type Sprinklers 11 2K Pendent Extended Coverage Light and Ordinary Hazard ECLH ECOH are decorative glass bulb auto matic sprinklers typically used where pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures for exam ple sprinkler drops from unheated portions of buildings sprinklers and or a portion of the...

Страница 2: ... Figure 3 SPRINKLER FINISH Natural Brass Chromed Plated Polyester Natural Brass Chrome Plated Polyester 135 F 57 C Orange 1 2 3 1 2 3 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Notes 1 UL Listed maximum order length of 48 in 2 C UL Listed maximum order length of 48 in 3 Approved by the City of New York under MEA 173 02 E 286 F 141 C temperature rating applies to installatio...

Страница 3: ...20 F 29 C 14 355 6 150 3 75 30 F 34 C 16 405 8 200 4 100 40 F 40 C 18 455 8 200 4 100 50 F 46 C 20 510 10 255 6 150 60 F 51 C 20 510 10 255 6 150 Notes 1 For protected area temperatures that occur between values listed above use the next cooler temperature 2 These lengths are inclusive of wind velocities up to 30 mph 18 6 kph Response Rating Coverage Area 4 ft x ft m x m Minimum Flow 1 Light Hazar...

Страница 4: ...gure 3 plus 1 4 in 6 3 mm Extended Order Length from Figure 4 plus 3 1 4 in 82 6 mm Without Escutcheon Order Length from Figure 5 minus 2 1 4 in 57 2 mm 2 1 4 1 8 57 2 3 2 mm ORDER LENGTHS 3 to 48 76 2 to 1219 2 mm IN 1 4 6 4 mm INCREMENTS ESCUTCHEON WILL PERMIT 1 4 6 4 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm SPRINKLER FITTING REFER TO DESIGN CRI...

Страница 5: ...5 8 15 9 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING FOR ORDER LENGTHS 3 1 4 82 6 mm 4 7 8 1 8 123 8 3 2 mm or FOR ORDER LENGTHS 3 1 4 82 6 mm 5 5 8 1 8 142 9 3 2 mm 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm ORDER LENGTHS 1 to 45 1 4 25 4 to 1149 4 mm IN 1 4 6 4 mm INCREMENTS SPRINKLER FITTING REFER TO DESIGN CRITERIA SECTION DO NOT FIGURE 4 SERIES DS 2 DRY TYPE PENDENT SPRINKLER ECLH ECOH W...

Страница 6: ...or protected area temperatures between those given above the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values You can also install Series DS 2 Dry Type Sprinklers in the 1 in NPT outlet of a GRINNELL Figure 730 Mechanical Tee However the use of the Figure 730 Tee for this arrangement is limi...

Страница 7: ...s easier when a non hardening sealant was used and torque guidelines were followed After removal inspect the sprinkler for damage Step 3 After installing the ceiling and applying a ceiling finish slide on the outer piece of the Escutcheon until it comes in contact with the ceiling Do not lift the ceiling panel out of its normal position When using the Deep Escutcheon hold the outer piece in contac...

Страница 8: ... applicable Part Number from Table E Sprinkler Wrench Specify W Type 17 Sprinkler Wrench P N 56 010 4 118 Sprinkler Boot Specify Model DSB 2 Dry Sprinkler Boot P N 63 000 0 002 This P N includes one 1 Boot two 2 Strap Ties and 1 3 oz of Adhesive a sufficient quantity for installing one boot Notes 1 Escutcheon Finish applies to sprinklers with escutcheons 2 286 F 141 C temperature rating applies to...

Отзывы: