background image

General troubleshooting

Table 11: Troubleshooting

Problem

Possible cause and correction

Verification

Controller is OFF.

Transformer has tripped:

Power is at Primary of

Transformer, 0V at Secondary.

Breaker/Fuse has tripped:

Power is at Primary of

Transformer, 24V at Secondary, 0V

at Fuse/Breaker.

Cause:

1. Transformer is shorted.

2. 24 VAC powered sensor is not

wired with the same polarity as the

controller.

3. SA Bus device is not wired with the

same polarity as the controller.

Correction:

1. Ensure polarity of ~24 V COM / UI-C /

+ 15VC/SA BUS COM on the controller,

auxiliary devices, and I/O is the same.

2. Ensure BO-1, BO-2, and BO-3

terminals of binary outputs are not

connected to ~24 VAC COM, and verify

that BO-C terminals are not connected

to ~24 VAC HOT (these terminals are

internally sourced).

3. Verify the short circuit has been

resolved with an ohm-meter.

4. Reset the breaker/fuse or replace the

transformer.

Note: 

When replacing the

transformer, it is recommended to

replace with a model that utilizes a

resettable circuit breaker. A circuit

breaker makes solving wiring

problems easier.

1. Disconnect the Secondary of the 24

VAC transformer.

2. Use an ohm-meter to measure

between ~24 V HOT and COM; there

must be no short circuit.

Note: 

Some installations require

the secondary of the transformer

to be Earth Grounded. If this is

the case, verify that the Earth

Ground connection is valid and not

shared between multiple pieces of

equipment.

Configurable output - analog mode is

invalid

:

0–10 V output is set to 10–100%, but 0 V is at

output terminals.

Output is in protection mode

, a state the

analog portion of the configurable output

goes into when it detects a wiring problem.

The analog output is set to 0% regardless

of the command whenever a wiring fault is

detected.

Cause:

There is a power polarity mismatch between

the connected device and the configurable

output.

Correction:

Ensure polarities of ~24 V COM/CO-C match

and that the connected end device uses the

same polarity.

1. Measure the output and verify that it

matches the command.

2. Disconnect the connected device

and verify the commanded value is

present.

Configurable output - analog mode is

invalid

:

0–10V output has an undesirable offset of up

to 1 V.

The Common Reference is incorrect.

Cause:

The CO-C terminal is not connected.

Correction:

Connect the CO-C terminal of the

configurable output to the common of the

connected end device.

1. Measure the output and verify that it

matches the command.

2. Disconnect the connected device

and verify the commanded value is

present.

M4-CVM VAV Box Controllers Installation Guide

18

Содержание CVM03050

Страница 1: ...e and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N...

Страница 2: ...al block or N2 protocol as required 13 EOL End of Line Switch See Setting the End of Line EOL switch 14 SA Bus Port RJ 12 6 Pin Modular Jack See Modular ports 15 FC Bus Port RJ 12 6 Pin Modular Jack S...

Страница 3: ...you must provide hard stops at both full closed and full open damper positions If you install the CVM controller at the full open position the controller provides the open stop for 45 and 60 boxes The...

Страница 4: ...ons Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detai...

Страница 5: ...A bus Note Stranded 4 wire 2 twisted pair shielded cable One twisted pair is the and leads The second pair is COM and POWER Note Do not use the modular SA Bus port and the terminal block SA Bus simult...

Страница 6: ...avant d avoir v rifi toutes les connexions du c blage Le c blage inad quat de cette borne peut causer un court circuit sur l alimentation lectrique de 24 V c Un court circuit peut causer le d clenche...

Страница 7: ...ings and requirements To determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI n terminals Provides 35 mA total current Sa...

Страница 8: ...INARY Outputs BO C Binary Output 24 VAC Triac Internal Power Connects BO n to 24 BO C when activated Internal Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty...

Страница 9: ...and the load current in mA when wiring inputs and outputs Note Figure 9 applies to low voltage 30 V inputs and outputs only Figure 9 Maximum wire length for low voltage 30 V Inputs and Outputs by curr...

Страница 10: ...Common SA BUS 1 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and POW...

Страница 11: ...on for the applicable termination diagrams Table 8 Termination details Type of Field Device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI...

Страница 12: ...xternal Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch...

Страница 13: ...AC supply from the controller 2 Set the address switches to the desired N2 address For details about setting a device address see Setting the device address 3 Reconnect the 24 VAC supply to the contro...

Страница 14: ...ommunication 1 254 Note Addresses 0 and 255 are reserved and not for use on equipment controllers The device address is a decimal address set using three rotary switches located at the top of the cont...

Страница 15: ...the CVM03050 controller use the following procedure 1 With the desired application loaded in the controller commission the VAV Box Refer to the Controller Tool Help LIT 12011147 2 Perform airflow bal...

Страница 16: ...Elec Reheat Series Fan W C Adj Single Duct SCR Electric Reheat Proportional Heating Valve Single Speed Series Fan Warm Cool Adjust SCR Elec Reheat Parallel Fan W C Adj Single Duct SCR Electric Reheat...

Страница 17: ...ration SA Bus devices offline such as netsensors Rapid blink SA Bus communications issue Off Steady No faults On Steady Device fault or no application loaded FC BUS Green Blink 2 Hz Blink 2 Hz Data tr...

Страница 18: ...COM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not s...

Страница 19: ...ontroller Display NS ATV7003 0 Handheld VAV Balancing Tool NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions AS CBLT...

Страница 20: ...cks 30 terminal blocks in total MS FIT100 0 The Field Inspection Tool FIT is a portable handheld device with a user interface that is used to test and troubleshoot the BACnet protocol MS TP RS 485 com...

Страница 21: ...er and equipment controllers 4 wire SA Bus between equipment controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from equipment controller to bus...

Страница 22: ...e of its products Repair information If the CVM03050 equipment controller fails to operate within its specifications replace the unit For a replacement unit contact the nearest Johnson Controls repres...

Отзывы: