Technical specifications

Table 14: CVM03050 Controllers technical specifications

Description

Power Requirement

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2

(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption

10 VA typical, 14 VA maximum

Note: 

The VA rating does not include any power supplied to the peripheral devices

connected to three Outputs (BOs) or Configurable Outputs (COs), which can

consume up to 12 VA for each BO or CO, for a possible total consumption of an

additional 60 VA (maximum). There are 3 BO's and 2 CO's that can each draw 12VA

for a total of 60VA additional power.

Note: 

The USB feature is not currently supported.

Power Source

+15 VDC power source terminals provide 35 mA total current. Quantity 1 located in

Universal IN terminals - for active (3-wire) input devices

Ambient Conditions

Operating:

 0°C to 50°C (32°F to 122°F) 10% to 90% RH noncondensing

Storage:

 -40°C to 70°C (-40°F to 158°F) 5% to 95% RH noncondensing

Network Engines

All network engine model types

Communications Protocol

BACnet MS/TP; N2. Wireless also supported (at FC Bus and for Sensors) with additional

hardware.

Device Addressing for BACnet MS/TP

Decimal address set via three rotary switches; valid controller device addresses 4-127

Device Addressing for N2

Decimal address set via three rotary switches: valid controller device addresses 1-254

Communications Bus

Note: 

For more information, refer to

the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

BACnet MS/TP (default), N2
3-wire FC Bus between the supervisory controller and equipment controllers
4-wire SA Bus between equipment controller, network sensors and other sensor/actuator

devices, includes a lead to source 15 VDC supply power (from equipment controller) to

bus devices

Processor

RX64M 32-bit Renesas microcontroller

Memory

16MB Flash Memory and 8MB SDRAM

Real-Time Clock Backup Power Supply

Super capacitor maintains power to the onboard real-time clock for a minimum of 72

hours when supply power to the controller is disconnected.

Input and Output Capabilities

3 - Universal Inputs

: Defined as 0–10 VDC, 0–600k ohms, or Binary Dry Contact

2 - Configurable Outputs:

 Defined as 0-10 VDC or 24 VAC Triac BO

3 - Binary Outputs

: Defined as 24 VAC Triac (external power source only)

Universal Input (UI) Resolution/

Configurable Output (CO) Accuracy

UI Analog Input Mode:

 15-bit resolution on UIs

CO Analog Output Mode:

 0–10 VDC ± 200 mV

Air Pressure Differential Sensor

Range: -2 in. to 2 in. H2O

Performance Characteristics:

Typical Accuracy at ambient operating conditions: +/- 0.5 % in. H2O
Typical accuracy at zero (null) pressure is +/- 0.0006 in. H2O

Actuator Rating

4 N·m (35 lb·in) minimum shaft length = 44 mm (1-3/4 in.) (if provided)

Terminations

Inputs/Outputs

: Pluggable Screw Terminal

FC Bus, SA Bus, and Supply Power

: 4-Wire and 2-Wire Pluggable Screw Terminal Blocks

FC and SA Bus Modular Ports

: RJ-12 6-Pin Modular Jacks

Mounting

Mounts to damper shaft using single set screw and to duct with single mounting screw

Housing

Enclosure material:

 ABS and polycarbonate UL94 5VB; Self-extinguishing

Protection Class: IP20 (IEC529)

Dimensions
(Height x Width x Depth)

165 mm x 125 mm x 73 mm (6.5 in. x 4.92 in. x 2.9 in.)

Center of Output Hub to Center of Captive Spacer: 

135 mm (5-5/16 in.)

Weight

0.69 kg (1.52 lb)

M4-CVM VAV Box Controllers Installation Guide

21

Содержание CVM03050

Страница 1: ...e and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N...

Страница 2: ...al block or N2 protocol as required 13 EOL End of Line Switch See Setting the End of Line EOL switch 14 SA Bus Port RJ 12 6 Pin Modular Jack See Modular ports 15 FC Bus Port RJ 12 6 Pin Modular Jack S...

Страница 3: ...you must provide hard stops at both full closed and full open damper positions If you install the CVM controller at the full open position the controller provides the open stop for 45 and 60 boxes The...

Страница 4: ...ons Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detai...

Страница 5: ...A bus Note Stranded 4 wire 2 twisted pair shielded cable One twisted pair is the and leads The second pair is COM and POWER Note Do not use the modular SA Bus port and the terminal block SA Bus simult...

Страница 6: ...avant d avoir v rifi toutes les connexions du c blage Le c blage inad quat de cette borne peut causer un court circuit sur l alimentation lectrique de 24 V c Un court circuit peut causer le d clenche...

Страница 7: ...ings and requirements To determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI n terminals Provides 35 mA total current Sa...

Страница 8: ...INARY Outputs BO C Binary Output 24 VAC Triac Internal Power Connects BO n to 24 BO C when activated Internal Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty...

Страница 9: ...and the load current in mA when wiring inputs and outputs Note Figure 9 applies to low voltage 30 V inputs and outputs only Figure 9 Maximum wire length for low voltage 30 V Inputs and Outputs by curr...

Страница 10: ...Common SA BUS 1 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and POW...

Страница 11: ...on for the applicable termination diagrams Table 8 Termination details Type of Field Device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI...

Страница 12: ...xternal Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch...

Страница 13: ...AC supply from the controller 2 Set the address switches to the desired N2 address For details about setting a device address see Setting the device address 3 Reconnect the 24 VAC supply to the contro...

Страница 14: ...ommunication 1 254 Note Addresses 0 and 255 are reserved and not for use on equipment controllers The device address is a decimal address set using three rotary switches located at the top of the cont...

Страница 15: ...the CVM03050 controller use the following procedure 1 With the desired application loaded in the controller commission the VAV Box Refer to the Controller Tool Help LIT 12011147 2 Perform airflow bal...

Страница 16: ...Elec Reheat Series Fan W C Adj Single Duct SCR Electric Reheat Proportional Heating Valve Single Speed Series Fan Warm Cool Adjust SCR Elec Reheat Parallel Fan W C Adj Single Duct SCR Electric Reheat...

Страница 17: ...ration SA Bus devices offline such as netsensors Rapid blink SA Bus communications issue Off Steady No faults On Steady Device fault or no application loaded FC BUS Green Blink 2 Hz Blink 2 Hz Data tr...

Страница 18: ...COM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not s...

Страница 19: ...ontroller Display NS ATV7003 0 Handheld VAV Balancing Tool NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions AS CBLT...

Страница 20: ...cks 30 terminal blocks in total MS FIT100 0 The Field Inspection Tool FIT is a portable handheld device with a user interface that is used to test and troubleshoot the BACnet protocol MS TP RS 485 com...

Страница 21: ...er and equipment controllers 4 wire SA Bus between equipment controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from equipment controller to bus...

Страница 22: ...e of its products Repair information If the CVM03050 equipment controller fails to operate within its specifications replace the unit For a replacement unit contact the nearest Johnson Controls repres...

Отзывы: