4. Using an SA Bus connection, download a controller

application file configured for BACnet MS/TP to the

controller.

Configuring wireless communications

About this task:

To configure a controller for use with the ZFR Pro Series

Wireless Field Bus system, complete the following steps:

1. Disconnect the 24 VAC supply from the controller.
2. Wire the input/output terminals and SA bus.

Note: 

In wireless network applications, do

not connect any wires to the FC bus terminal

block. (Connect the SA/FC terminal block on an

expansion module to an SA bus only.)

3.

Important:

 Before the CVM controller is powered

on, connect the ZFR Pro Wireless Field Bus Router

to the FC bus port (RJ-12 modular jack) on the front

of the controller.

4. Ensure that the controller's rotary switches are

set to the correct device address. For details about

setting a device address, see 

Setting the device

address

.

5. Reconnect the 24 VAC supply to the controller.

Result:

For more information about the ZFR Pro Wireless Field

Bus system, refer to the 

WRG1830/ZFR183x Pro Series

Wireless Field Bus System Technical Bulletin (LIT-12013553)

.

Setting the device address

Metasys equipment controllers are master devices on MS/

TP (FC or SA) buses. Before you operate controllers on a

bus, you 

must

 set a valid and unique device address for

each controller on the bus.
The following table describes the valid rotary switch

device addresses for communications bus applications.

FC bus communication

mode

Valid device address range

Wired MS/TP

communication

4-127

Note: 

Addresses 0-3 are

reserved and not for use on

equipment controllers.

Zigbee wireless

communication

4-127

Note: 

Addresses 0-3 are

reserved and not for use on

equipment controllers.

N2 communication

1-254

Note: 

Addresses 0 and 255 are

reserved and not for use on

equipment controllers.

The device address is a decimal address set using three

rotary switches located at the top of the controller. The

numbers are ordered from left to right, most significant

bit (MSB) to least significant bit (LSB) when the controller

is oriented as shown in Figure 1. In the following figure,

the switches are set to 1 2 3, designating this controller's

device address as 123.

Figure 10: Device address rotary switch block

The device address must match the device address

defined in the Controller Configuration Tool (CCT) under

Define Hardware > Network Settings

.

To set the device addresses on controllers, complete the

following steps:

1.  Set a unique and sequential device address for each

of the devices connected on the FC or SA, starting

with device address 4.

2.  To ensure the best bus performance, set sequential

device addresses with no gaps in the device address

range (4, 5, 6, 7, 8, 9, and so on). The devices do not

need to be physically connected on the bus in their

numerical device address order.

3.  Write each controller's device address on the white

label below the Device Address Rotary Switch Block

on the controller's cover.

For more information about controller device addresses

and how to set them on MS/TP buses, refer to the 

MS/TP

Communications Bus Technical Bulletin (LIT-12011034)

.

Removing a terminal block

About this task:

To remove a terminal block from the circuit board,

complete the following steps:

Note: 

You need a flat blade screwdriver to remove

the terminal block.

1. To prevent any possibility of damage from an

accidental short, 

remove power from the

controller

.

2. Underneath the terminal block, in the small gap

between the bottom of the terminal block and

the circuit board, insert the flat blade of the

screwdriver.

Figure 11: Terminal block

M4-CVM VAV Box Controllers Installation Guide

14

Содержание CVM03050

Страница 1: ...e and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N...

Страница 2: ...al block or N2 protocol as required 13 EOL End of Line Switch See Setting the End of Line EOL switch 14 SA Bus Port RJ 12 6 Pin Modular Jack See Modular ports 15 FC Bus Port RJ 12 6 Pin Modular Jack S...

Страница 3: ...you must provide hard stops at both full closed and full open damper positions If you install the CVM controller at the full open position the controller provides the open stop for 45 and 60 boxes The...

Страница 4: ...ons Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detai...

Страница 5: ...A bus Note Stranded 4 wire 2 twisted pair shielded cable One twisted pair is the and leads The second pair is COM and POWER Note Do not use the modular SA Bus port and the terminal block SA Bus simult...

Страница 6: ...avant d avoir v rifi toutes les connexions du c blage Le c blage inad quat de cette borne peut causer un court circuit sur l alimentation lectrique de 24 V c Un court circuit peut causer le d clenche...

Страница 7: ...ings and requirements To determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI n terminals Provides 35 mA total current Sa...

Страница 8: ...INARY Outputs BO C Binary Output 24 VAC Triac Internal Power Connects BO n to 24 BO C when activated Internal Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty...

Страница 9: ...and the load current in mA when wiring inputs and outputs Note Figure 9 applies to low voltage 30 V inputs and outputs only Figure 9 Maximum wire length for low voltage 30 V Inputs and Outputs by curr...

Страница 10: ...Common SA BUS 1 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and POW...

Страница 11: ...on for the applicable termination diagrams Table 8 Termination details Type of Field Device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI...

Страница 12: ...xternal Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch...

Страница 13: ...AC supply from the controller 2 Set the address switches to the desired N2 address For details about setting a device address see Setting the device address 3 Reconnect the 24 VAC supply to the contro...

Страница 14: ...ommunication 1 254 Note Addresses 0 and 255 are reserved and not for use on equipment controllers The device address is a decimal address set using three rotary switches located at the top of the cont...

Страница 15: ...the CVM03050 controller use the following procedure 1 With the desired application loaded in the controller commission the VAV Box Refer to the Controller Tool Help LIT 12011147 2 Perform airflow bal...

Страница 16: ...Elec Reheat Series Fan W C Adj Single Duct SCR Electric Reheat Proportional Heating Valve Single Speed Series Fan Warm Cool Adjust SCR Elec Reheat Parallel Fan W C Adj Single Duct SCR Electric Reheat...

Страница 17: ...ration SA Bus devices offline such as netsensors Rapid blink SA Bus communications issue Off Steady No faults On Steady Device fault or no application loaded FC BUS Green Blink 2 Hz Blink 2 Hz Data tr...

Страница 18: ...COM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not s...

Страница 19: ...ontroller Display NS ATV7003 0 Handheld VAV Balancing Tool NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions AS CBLT...

Страница 20: ...cks 30 terminal blocks in total MS FIT100 0 The Field Inspection Tool FIT is a portable handheld device with a user interface that is used to test and troubleshoot the BACnet protocol MS TP RS 485 com...

Страница 21: ...er and equipment controllers 4 wire SA Bus between equipment controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from equipment controller to bus...

Страница 22: ...e of its products Repair information If the CVM03050 equipment controller fails to operate within its specifications replace the unit For a replacement unit contact the nearest Johnson Controls repres...

Отзывы: