Figure 7: 24 VAC supply power terminal block wiring

Table 4: Supply power terminal block wiring

Description

1

Supply power terminal block

2

Supply power terminal header

3

Wires from Johnson Controls 24 VAC, class 2 power

transformer

4

COM (Brown wire)

5

24 VAC (Orange wire)

Note: 

The supply power wire colors may be different

on transformers from other manufacturers. Refer to

the transformer manufacturer’s instructions and the

project installation drawings for wiring details.

Important: 

Connect 24 VAC supply power to

the CVM and all other network devices so that

transformer phasing is uniform across the network

devices. Powering network devices with uniform

24 VAC supply power phasing reduces noise,

interference, and ground loop problems. The CVM

does not require an earth ground connection.

However, when grounding the secondary of the 24

VAC transformer is required, only one connection

to ground must be made near the transformer. See

Figure 8.

Figure 8: Transformer grounding

 CAUTION

Risk of Property Damage:

Do not apply power to the system before checking all

wiring connections. Improper wiring of this terminal

may cause a short circuit across the 24 VAC power

supply. A short circuit may result in a tripped circuit

breaker or blown fuse. If using a transformer with a

built-in fuse, the transformer may need to be replaced.

 ATTENTION

Risque de dommages matériels:

Ne mettez pas l’appareil sous tension avant d’avoir

vérifié toutes les connexions du câblage. Le câblage

inadéquat de cette borne peut causer un court-

circuit sur l’alimentation électrique de 24 V c. Un

court-circuit peut causer le déclenchement du

disjoncteur ou le grillage d’un fusible. Si vous utilisez

un transformateur avec un fusible intégré, vous

pourriez devoir remplacer le transformateur.

To wire the CVM03050 controller, complete the following

steps:

1.  Terminate wiring according to the appropriate figure

in 

Termination diagrams

.

2.  Wire network sensors and other devices to the SA

Bus.

3.  Wire the FC Bus in a daisy chain.
4.  Ensure that the CVM03050 is assigned a device

address. Set the device address using the rotary

switches at the top of the controller. See 

Setting the

device address

.

5.  Connect the CVM controller to 24 VAC, Class 2 power.

Note: 

If you are using the CVM03050 controller with

the Wireless Field Bus System, refer to the 

WNC1800/

ZFR182x Pro Series Wireless Field Bus System Bulletin

(LIT-12012320)

 or the 

ZFR1800 Series Wireless Field Bus

System Bulletin (LIT-12011336)

.

Terminal wiring guidelines, functions,

ratings, and requirements

This section provides further guidelines on input and

output wiring, maximum cable length versus load current,

and SA Bus and supply power wiring.
For information about removing a terminal block from the

controller, see 

Removing a terminal block

.

Input and Output wiring guidelines

Table 5 provides information and guidelines about the

functions, ratings, and requirements for the controller

input and output terminals, and Table 5 also references

M4-CVM VAV Box Controllers Installation Guide

6

Содержание CVM03050

Страница 1: ...e and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N...

Страница 2: ...al block or N2 protocol as required 13 EOL End of Line Switch See Setting the End of Line EOL switch 14 SA Bus Port RJ 12 6 Pin Modular Jack See Modular ports 15 FC Bus Port RJ 12 6 Pin Modular Jack S...

Страница 3: ...you must provide hard stops at both full closed and full open damper positions If you install the CVM controller at the full open position the controller provides the open stop for 45 and 60 boxes The...

Страница 4: ...ons Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detai...

Страница 5: ...A bus Note Stranded 4 wire 2 twisted pair shielded cable One twisted pair is the and leads The second pair is COM and POWER Note Do not use the modular SA Bus port and the terminal block SA Bus simult...

Страница 6: ...avant d avoir v rifi toutes les connexions du c blage Le c blage inad quat de cette borne peut causer un court circuit sur l alimentation lectrique de 24 V c Un court circuit peut causer le d clenche...

Страница 7: ...ings and requirements To determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI n terminals Provides 35 mA total current Sa...

Страница 8: ...INARY Outputs BO C Binary Output 24 VAC Triac Internal Power Connects BO n to 24 BO C when activated Internal Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty...

Страница 9: ...and the load current in mA when wiring inputs and outputs Note Figure 9 applies to low voltage 30 V inputs and outputs only Figure 9 Maximum wire length for low voltage 30 V Inputs and Outputs by curr...

Страница 10: ...Common SA BUS 1 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and POW...

Страница 11: ...on for the applicable termination diagrams Table 8 Termination details Type of Field Device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI...

Страница 12: ...xternal Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch...

Страница 13: ...AC supply from the controller 2 Set the address switches to the desired N2 address For details about setting a device address see Setting the device address 3 Reconnect the 24 VAC supply to the contro...

Страница 14: ...ommunication 1 254 Note Addresses 0 and 255 are reserved and not for use on equipment controllers The device address is a decimal address set using three rotary switches located at the top of the cont...

Страница 15: ...the CVM03050 controller use the following procedure 1 With the desired application loaded in the controller commission the VAV Box Refer to the Controller Tool Help LIT 12011147 2 Perform airflow bal...

Страница 16: ...Elec Reheat Series Fan W C Adj Single Duct SCR Electric Reheat Proportional Heating Valve Single Speed Series Fan Warm Cool Adjust SCR Elec Reheat Parallel Fan W C Adj Single Duct SCR Electric Reheat...

Страница 17: ...ration SA Bus devices offline such as netsensors Rapid blink SA Bus communications issue Off Steady No faults On Steady Device fault or no application loaded FC BUS Green Blink 2 Hz Blink 2 Hz Data tr...

Страница 18: ...COM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not s...

Страница 19: ...ontroller Display NS ATV7003 0 Handheld VAV Balancing Tool NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions AS CBLT...

Страница 20: ...cks 30 terminal blocks in total MS FIT100 0 The Field Inspection Tool FIT is a portable handheld device with a user interface that is used to test and troubleshoot the BACnet protocol MS TP RS 485 com...

Страница 21: ...er and equipment controllers 4 wire SA Bus between equipment controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from equipment controller to bus...

Страница 22: ...e of its products Repair information If the CVM03050 equipment controller fails to operate within its specifications replace the unit For a replacement unit contact the nearest Johnson Controls repres...

Отзывы: