SM-18003
5-33
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(94) Not Prepared (L2)
(95) Louver Setting during Energy-Saving Forced Thermo-OFF (L3)
(96) Fan Speed during Energy-Saving Forced Thermo-OFF (L4)
This function is utilized to increase the fan speed to prevent the deterioration of comfort due to force
thermo-OFF for energy saving during cooling operation.
Setting Condition
Air Volume During Force Thermo-OFF
Air Flow Volume
HIGH2
HIGH
MED
LOW
00 (Standard)
HIGH2
HIGH
MED
LOW
01 (Hi Speed)
HIGH2
HIGH2
HIGH
MED
Setting Condition
Energy-Saving Force Thermo-OFF
00 (Receive Air: LOW) Louver stay in downward air flow position during Auto Swing Mode
01 (Receive Air: MED) Louver stay in downward air flow position longer than "00" during Auto Swing Mode
02 (Receive Air: HIGH) Louver is fixed at the 7th step of downward air flow
03 (Not Available)
Cancel the louver operation
(93) Motion Sensor Installation Position (L1)
This function is utilized to select the installation position of the cover for corner with motion sensor and
radiation temperature sensor by wired controller.
Setting Condition
Installation Position
00
A (Factory-Setting)
01
B
02
- (Not Available)
03
D
Ref.
Pipe
Mark of
Mark of
Mark of
Mark of
Mark of
The motion sensor cannot
install to the location of the mark of “C” .
B
C
A
The mark of “A” is
the factory setting position
for motion sensor.
D
Electrical Box
Decorative Panel without
Four Corner Covers
(97) Louver Swing Operation during Energy-Saving Forced Thermo-OFF (L5)
This function is set at "01", the function "L3" setting will be available.
(98) Not Prepared (L6)
(99) Not Prepared (L7)
(100) Not Prepared (L8)
(101) Not Prepared (L9)
(102) Not Prepared (LA)
(103) Not Prepared (Lb)
(104) Setting Temperature (P1)
This function is utilized to provide setting temperature for every 1
o
F (0.5
o
C) at "00" and every 2
o
F (1
o
C)
at "01".
Control differential of thermistor also uses the temperature for every 1
o
F (0.5
o
C) at "00" and every 2
o
F
(1
o
C) at "01".
(105) Not Prepared (P2)
(106) Thermistor Selection (P3)
This function is utilized to select the thermistor with function (107).
Setting Condition
Thermistor (Sensor)
00
Inlet Air Thermistor
01
Outlet Air Thermistor
02
Thermistor of Remote Control
03
Remote Sensor
Содержание CICM008B21S
Страница 2: ......
Страница 10: ...viii SM 18003 ...
Страница 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Страница 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Страница 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Страница 22: ......
Страница 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Страница 74: ...MAINTENANCE 4 2 SM 18003 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit ...
Страница 99: ...SM 18003 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 138: ......
Страница 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Страница 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Страница 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Страница 151: ......
Страница 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...