SM-18003
5-17
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.2.1 Function Selection Item
5.4.2 Function Setting
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
1
b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
○
00
01
02
03
04
Standard (Set Temp. +7
o
F (+4
o
C))
Removal (Set Temp.)
Set Temp. +3
o
F (+2
o
C) (*1)
Set Temp. +5
o
F (+3
o
C)
Set Temp. +2
o
F (+1
o
C)
2
b2
Circulator Function during
Heating Thermo-OFF
○
00
01
Not Available
Available
3
b3
Not Prepared
-
-
Not Used (Use as 00 conditions)
4
b4
Change of Filter Cleaning Time
-
00
01
02
03
04
Standard 1,200 hrs (Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5
b5
Fixing of Operation Mode
×
00
01
Standard
Fixed
6
b6
Fixing of Setting Temperature
×
00
01
Standard
Fixed
7
b7
Fixing of Operation as
Exclusive Cooling Unit
×
00
01
Standard
Fixed
8
b8
Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9
b9
Fixing of Fan Speed
×
00
01
Standard
Fixed
10
bA
Not Prepared
-
-
Not Used
11
bb
Cooling Temperature Compensation
due to Uneven Heat Load
×
00
01
02
Standard (No Compensation)
Set Temp. –2
o
F (–1
o
C)
Set Temp. –3
o
F (–2
o
C)
12
bC
Not Prepared
-
-
Not Used (Use as 00 conditions)
13
bd
Not Prepared
-
-
Not Used (Use as 00 conditions)
14
bE
Not Prepared
-
-
Not Used (Use as 00 conditions)
15
C1
Not Prepared
-
-
Not Used (Use as 00 conditions)
16
C2
Not Prepared
-
-
Not Used
17
C3
Not Prepared
-
-
Not Used
18
C4
Not Prepared
-
-
Not Used
19
C5
Hi Speed
(Except for Hi Speed during Heating
Thermo-OFF)
○
00
01
02
Not Available
Hi Speed 1
Hi Speed 2
20
C6 Hi Speed during Heating Thermo-
OFF
○
00
01
Not Available
Available
21
C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of
Compressor
○
00
01
Standard
Cancellation
22
C8 Thermistor of Wired Controller (*6)
○
00
01
02
00
01
02
< If Wired Controller Thermistor is Selected ˃
Not Available
Control by Thermistor of Wired Controller
Control by Average Value of Indoor Suction
Thermistor and Thermistor of Wired Controller
< If Remote Sensor is Selected ˃
Control by Average Value of Indoor Suction
Thermistor and Remote Sensor
Control by Remote Sensor
Same as "00"
23
C9
Not Prepared
-
-
Not Used
24
CA
Not Prepared
-
-
Not Used
25
Cb Selection of Forced Stoppage Logic
×
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
Содержание CICM008B21S
Страница 2: ......
Страница 10: ...viii SM 18003 ...
Страница 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Страница 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Страница 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Страница 22: ......
Страница 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Страница 74: ...MAINTENANCE 4 2 SM 18003 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit ...
Страница 99: ...SM 18003 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 138: ......
Страница 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Страница 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Страница 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Страница 151: ......
Страница 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...