5-32
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(87) Motion Sensor Detection Level (K5)
This function is utilized to determine the amount of human activity depending on the reaction rate as in
the following table.
When “HIGH” (01) is set, the threshold of the amount of human activity is smaller than the standard.
As the result, the detection level of human sensor becomes higher.
When “LOW” (02) is set, the threshold of the amount of human activity is larger than the standard.
As a result, the detection level of human sensor becomes lower.
Setting
Conditions
Amount of
Human Activity
00 (Factory Setting)
01
02
Standard
High Sensitive
Low Sensitive
Extra Large
80% < Reaction Rate
60% < Reaction Rate
80% < Reaction Rate
Large
30% <
Reaction Rate ˂ 80%
20% <
Reaction Rate ˂60%
40% <
Reaction Rate ˂ 80%
Small
3% < Reaction Rate < 30%
3% < Reaction Rate < 20%
3% < Reaction Rate < 40%
No Available
Reaction Rate < 3%
Reaction Rate < 3%
Reaction Rate < 20%
(88) Operation Setting during Thermistor of Wired Controller or Remote Sensor (K6)
This function is utilized to change the function "Thermistor of Wired Controller / Remote Sensor (C8)"
according to operation mode.
Setting Condition
Operation Mode
00
ALL
01
COOL / DRY
02
HEAT
03
same as "00"
NOTE:
All modes are available during automatic Cool/Heat operation mode.
(89) Radiation Temperature Correction (K7)
This function is utilized to correct the radiation temperature detected higher/lower than actual radiation
temperature depending on the environment.
Setting Condition
Operation Mode
00 (Standard)
0
o
F (0
o
C)
01 (Upward)
+3
o
F (+2
o
C)
02 (Downward)
-3
o
F (-2
o
C)
(90) Control of Dew Condensation Prevention (K8)
Condensation may occur around air outlet during COOL / DRY operation with horizontal air flow and
downward air flow for long time period.
This function is utilized to prevent condensation by moving the louver swing angle to the third step
automatically for 30 minutes every 1 hour.
(91) Not Prepared (K9)
(92) Not Prepared (KA)
Содержание CICM008B21S
Страница 2: ......
Страница 10: ...viii SM 18003 ...
Страница 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Страница 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Страница 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Страница 22: ......
Страница 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Страница 74: ...MAINTENANCE 4 2 SM 18003 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit ...
Страница 99: ...SM 18003 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 138: ......
Страница 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Страница 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Страница 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Страница 151: ......
Страница 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...