5.4.2.2 Description of Function Selection Item
(1) Cancellation of Heating Temperature Compensation due to Uneven Heat Load (b1)
This function is utilized when the setting temperature of the wired controller and the inlet air
temperature of the indoor unit are required to be equal.
This is useful when the inlet air thermistor is relocated to the outside of the indoor unit.
(2) Circulator Function during Heating Thermo-OFF (b2)
In the standard factory setting, the air flow volume changes to “LOW” automatically to prevent a cold
draft during heating Thermo-OFF.
Therefore, the air flow might not be distributed uniformly in the room depending on the installation
location of the air conditioner or room structure. In such case, it is recommended to utilize this
function.
The function keeps the air flow volume during Thermo-OFF at the same level as during Thermo-ON.
The air flow in the room is kept at the same level as during Thermo-ON and so the room temperature
will be uniformly-distributed. If using the air conditioner with auto swing function, the auto swing
function will be activated even during heating Thermo-OFF.
NOTE:
The temperature sensibility and demands for air flow distribution differ depending on the person. It is
therefore recommended to discuss these matters with customers thoroughly and then to install t
he unit
accordingly.
(3) Not Prepared (b3)
(4) Change of Filter Cleaning Time (b4)
The period before filter sign indication is set according to indoor unit model before shipment.
The filter sign (“FLTR” on wired controller) is indicated according to the filter cleaning time (Factory
Setting). However, this filter cleaning time can be changed depending on the condition of the filter as
shown in the table below.
Period for
Filter Sign Indication
Approx.
1,200 hrs.
Approx.
100 hrs.
Approx.
1,200 hrs.
Approx.
2,500 hrs.
No Indication
Liquid Crystal Display
on Wired Controller
00
(Factory Setting)
01
02
03
04
NOTE:
While “Control by External Input” is valid, the filter sign will be “No Indication” if the external input is
disconnected.
(5) Fixing of Operation Mode (b5)
This function is utilized when the operation mode is not required to be changed.
When this function is valid, the set operation mode cannot be changed by the wired controller.
(6) Fixing of Setting Temperature (b6)
This function is utilized when setting temperature is not required to be changed.
When this function is valid, the setting temperature cannot be changed by the wired controller.
Setting Temperature for Room Temperature Control during Heating
Setting Condition
Actual Control Temperature
00 (Standard)
Wired Controller Setting Temperature (Indicated Value) +7
o
F (+4
o
C)
01
Wired Controller Setting Temperature (Indicated Value)
02
Wired Controller Setting Temperature (Indicated Value) +3
o
F (+2
o
C)
03
Wired Controller Setting Temperature (Indicated Value) +5
o
F (+3
o
C)
04
Wired Controller Setting Temperature (Indicated Value) +2
o
F (+1
o
C)
NOTE:
The maximum setting temperature after correction is as follows.
Inverter Multi Unit: 94
o
F (34
o
C)
Содержание CICM008B21S
Страница 2: ......
Страница 10: ...viii SM 18003 ...
Страница 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Страница 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Страница 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Страница 22: ......
Страница 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Страница 74: ...MAINTENANCE 4 2 SM 18003 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit ...
Страница 99: ...SM 18003 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 138: ......
Страница 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Страница 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Страница 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Страница 151: ......
Страница 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...