background image

VENTILATED

Low level grille

184cm

2

 (28in

2

)

FROM INSIDE
BUILDING

High level grille

92cm

2

 (14in

2

)

VENTILATED

Low level grille

92cm

2

 (14in

2

)

FROM OUTSIDE
BUILDING

High level grille

46cm

2

 (7in

2

)

Table  1: Minimum Effective Areas

4.

 DUCT SYSTEM

(See British Design Manual - Gas fired Warm Air Heating)

4.1

RETURN AIR

4.1.1 All return air shall be POSITIVELY ducted from outside the compartment to the top of the unit via a return air duct,

and mechanically secured. It is recommended that the return air duct be not routed directly from the main living
area, but from a convenient central area serving the remainder of the dwelling.

4.1.2 The return air system should be constructed of fire-resistant material. The flue shall not be run through an area

serving as a return air path. It is extremely important that the correct size of return air grilles and ducting is used.
The return air duct size should not be less than the equivalent of 200mm x 200mm (8" x 8"). If flexible duct is used
the duct diameter should not be less than 254mm (10") dia. The return air grille should have a free area of not less
than 650cm

2

 (100in

2

).

4.1.3 An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to

which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m

2

/

kW (1in

2

/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’s.

4.1.4

The return air duct should allow for ease of removal for access to the flue.

4.1.5

All duct work in the room or internal space in which the heater is installed shall be mechanically secured, and
sealed with ducting tape.

4.2

WARM DELIVERED AIR

4.2.1

All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short
extended duct runs are taken below floor level these should be similarly insulated, and in addition wrapped with a
sound vapour proof barrier, and protected from crushing.

4.2.2

The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to

suit the needs of its specific heating requirements and building layout. The type of duct system, (i.e. radial/
extended plenum/stepped) should be installed using the least number of fittings to minimize airflow resistance.
The base duct, which equalizes the air pressure to supply ducts, shall be constructed to support the weight of the
heater, which shall be secured to the plenum with screws on at least two sides, and sealed using self-adhesive
foam strip, ducting tape or sealing compound. All ducting and blanking plates shall be mechanically secured and
sealed.

5.

INSTALLATION REQUIREMENTS

5.1  

FLUES 

(see British Standards BS 5440 Pt.1 Flues)

5.1.1

All joints shall be soundly sealed.

5.1.2

The flue should be kept as short and warm as possible, but must have a minimum equivalent height of 1m..

5.1.3

Sufficient support brackets shall be installed to bear the weight of the total flue system.

5.1.4

The spigot connection of the heater draught diverter will internally accept the spigot end of a non-asbestos flue
to BS 567 or twin wall metal flue to BS 715 of nominal 100mm (4in) diameter.

5.1.5

A split collar should be fitted to provide for flue maintenance or inspection.

5.1.6

The flue shall be in accordance with the Building Regulations and British Gas Materials and  Installations
specification (3rd edition) with regard to clearance and shielding from combustible materials.

5.1.7

All materials shall be in accordance with Building Regulations requirements.

5.1.8

The flue should run as vertically as possible. Horizontal runs should be avoided if at all possible and any
directional change should be as gentle as possible. If there is any doubt about the flue configuration, the
equivalent flue height should be determined (see 5.1.10).

5.1.9

If the appliance to be fitted is a replacement, the old appliance should be checked for signs of spillage prior to
commencement of the installation and appropriate action taken, (i.e. check flue system and renew as necessary).

3

ZZ1031/4

ZZ1031/4

16

Fig. 5, JB25P Mk 5 CIRCUIT DIAGRAM

Содержание JB25P MK 5

Страница 1: ...Publication No ZZ 1031 4 August 2004 These instructions are to be left with the User or adjacent to the Gas Appliance 1 Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently If you have a problem in obtaining a spare part please contact Johnson and Starley Spares Department at the address below JOHNSON STARLEYLTD Telephone 01604 762881 Rhosili Road Brackmil...

Страница 2: ...pplicable only to dwellings of more than two storeys Combustible floors must be insulated from the heater 2 5 In slot fit installations for caravan installations see instructions packed with Slot Fit Kit TS30 or TSA30 the slot fit compartment must comply with the appropriate section of BS 5864 Side and rear clearances should be no less than 6mm 1 4 in 2 6 In freestanding installations see instruct...

Страница 3: ...ted from crushing 4 2 2 The duct system should be carefully designed as given in the guidelines in the British System Design Manual to suit the needs of its specific heating requirements and building layout The type of duct system i e radial extended plenum stepped should be installed using the least number of fittings to minimize airflow resistance The base duct which equalizes the air pressure t...

Страница 4: ... an existing flue system can be used Note Ventilation of the compartment room or internal space in which the appliance is to be installed must be checked for compliance with the requirements of BS 5440 Part 2 Ref Section 3 of these instructions and upgraded as necessary 5 1 11 Calculation method forflue sizing BS 5440 Part 1 AppendixA a This appendix provides a procedure for estimating whether a g...

Страница 5: ...ty polarity and resistance to earth checks should be carried out with a multimeter On completion of any maintenance fault finding task that has required the breaking and remaking of electrical connections then checks of continuity polarity and resistance to earth must be repeated 9 2 WARNINGS 9 2 1 When purging or checking gas supplies ensure that the ventilation to the room or cupboard is adequat...

Страница 6: ... Remove the appliance upper and lower doors 8 11 3 Disconnect the Summer circulation switch 8 11 4 Release the switch securing bezel and the remove switch 8 11 5 Refitting or replacement is in reverse order 8 12 FAN DELAY CONTROL AND LIMIT SWITCH REMOVAL 8 12 1 Ensure that the electrical supply is isolated 8 12 2 Remove the appliance lower and upper doors 8 12 3 Release the 2 x 4mm screws securing...

Страница 7: ...the Pilot Burner remains alight If the Pilot Burner extinguishes wait three minutes and repeat steps 6 3 4 and 6 3 5 until the Pilot Burner remains alight 6 3 6 Ensure that the pilot flame envelops the Thermocouple tip adjusting the Multifunctional Control Pilot Adjuster as required refer Fig 4 6 3 7 Set the Heater Electricity supply ON 6 3 8 Set the Time Control to required Heating On periods 6 3...

Страница 8: ... using a torch or similar examine the heat exchanger externally for signs of cracks or holes particularly around welded joints 8 1 9 Using a torch or similar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst again viewing through the Fan Aperture 8 1 10 Re...

Страница 9: ...ROLS CHECK 6 6 1 Ignite the Pilot burner 6 6 2 Set the TIME CONTROL to ON 6 6 3 Set the Room Thermostat slowly clockwise until the Main Burner ignites 6 6 4 Ensure that the fan starts to operate after a short period 6 6 5 When the temperature reaches the control setting check that the Main Burner extinguishes followed by the fan switching off after a short period 6 6 6 When the temperature falls b...

Страница 10: ...ROLS CHECK 6 6 1 Ignite the Pilot burner 6 6 2 Set the TIME CONTROL to ON 6 6 3 Set the Room Thermostat slowly clockwise until the Main Burner ignites 6 6 4 Ensure that the fan starts to operate after a short period 6 6 5 When the temperature reaches the control setting check that the Main Burner extinguishes followed by the fan switching off after a short period 6 6 6 When the temperature falls b...

Страница 11: ... using a torch or similar examine the heat exchanger externally for signs of cracks or holes particularly around welded joints 8 1 9 Using a torch or similar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst again viewing through the Fan Aperture 8 1 10 Re...

Страница 12: ...the Pilot Burner remains alight If the Pilot Burner extinguishes wait three minutes and repeat steps 6 3 4 and 6 3 5 until the Pilot Burner remains alight 6 3 6 Ensure that the pilot flame envelops the Thermocouple tip adjusting the Multifunctional Control Pilot Adjuster as required refer Fig 4 6 3 7 Set the Heater Electricity supply ON 6 3 8 Set the Time Control to required Heating On periods 6 3...

Страница 13: ... Remove the appliance upper and lower doors 8 11 3 Disconnect the Summer circulation switch 8 11 4 Release the switch securing bezel and the remove switch 8 11 5 Refitting or replacement is in reverse order 8 12 FAN DELAY CONTROL AND LIMIT SWITCH REMOVAL 8 12 1 Ensure that the electrical supply is isolated 8 12 2 Remove the appliance lower and upper doors 8 12 3 Release the 2 x 4mm screws securing...

Страница 14: ...ty polarity and resistance to earth checks should be carried out with a multimeter On completion of any maintenance fault finding task that has required the breaking and remaking of electrical connections then checks of continuity polarity and resistance to earth must be repeated 9 2 WARNINGS 9 2 1 When purging or checking gas supplies ensure that the ventilation to the room or cupboard is adequat...

Страница 15: ... an existing flue system can be used Note Ventilation of the compartment room or internal space in which the appliance is to be installed must be checked for compliance with the requirements of BS 5440 Part 2 Ref Section 3 of these instructions and upgraded as necessary 5 1 11 Calculation method forflue sizing BS 5440 Part 1 AppendixA a This appendix provides a procedure for estimating whether a g...

Страница 16: ...ted from crushing 4 2 2 The duct system should be carefully designed as given in the guidelines in the British System Design Manual to suit the needs of its specific heating requirements and building layout The type of duct system i e radial extended plenum stepped should be installed using the least number of fittings to minimize airflow resistance The base duct which equalizes the air pressure t...

Страница 17: ...pplicable only to dwellings of more than two storeys Combustible floors must be insulated from the heater 2 5 In slot fit installations for caravan installations see instructions packed with Slot Fit Kit TS30 or TSA30 the slot fit compartment must comply with the appropriate section of BS 5864 Side and rear clearances should be no less than 6mm 1 4 in 2 6 In freestanding installations see instruct...

Страница 18: ...18 ZZ1031 4 Fig 7 PRINCIPAL DIMENSIONS mm ...

Страница 19: ...Publication No ZZ 1031 4 August 2004 These instructions are to be left with the User or adjacent to the Gas Appliance 1 Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently If you have a problem in obtaining a spare part please contact Johnson and Starley Spares Department at the address below JOHNSON STARLEYLTD Telephone 01604 762881 Rhosili Road Brackmil...

Отзывы: