1. GENERAL DESCRIPTION
1.
BRIEF DESCRIPTION
1
Air Filter
2
Air circulating fan
3
Fuse(s)
4
Time control
5
Data plate
6
Limit switch
7
Multifunctional control
8
Pilot burner
9
Burner and Control Assembly
10
Gas connection
11
Airflow sensor (Modairflow
models)
12
Fan Delay Control
(non-Modairflow)
13
Electrical Assembly
14
Piezo unit
15
Spillage monitoring device (TTB)
(at rear)
16
Electronics module
(MODAIRFLOW)
Fig. 1
1.1
HI-SPEC J65 is an open-flued, fan assisted downflow, ducted warm air heater, which may be supplied with MODAIR-
FLOW control and in conjunction with an ELJAN 6 water circulator. A non-MODAIRFLOW version is available as an
option. A Spillage Monitoring Device (TTB) is fitted which senses the temperature in the draught diverter, and shuts down
the appliance when this temperature rises due to the presence of flue gases.
1.2
The Air heater output can be adjusted between 16.1kW (58.0MJ/h, 55,000Btu/h) and 19.1kW (68.6MJ/h, 65,000Btu/h).
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is
3.32kW (11.5MJ/h, 11,340Btu/h).
THIS APPLIANCE CONFORMS TO BS EN 55014
Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for Gas Appliances)
BS 5440 Pt. 2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws
HI-SPEC J65 WARM AIR HEATERS
MODAIRFLOW and non-MODAIRFLOW Control
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. No 42 451 14
Publication No. ZZ 941/8
October 2006
These instructions are to be left with the User or adjacent to the Gas Meter
1
8
11 12
5
14
9
7
6
10
3
4
16
13
15
2
1
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.
JOHNSON & STARLEY LTD.
Telephone: (01604) 762881
Rhosili Road,
Brackmills,
Fax:
(01604) 767408
Northampton NN4 7LZ
1.
BRIEF DESCRIPTION
1
Air Filter
2
Air circulating fan
3
Fuse(s)
4
Time control
5
Data plate
6
Limit switch
7
Multifunctional control
8
Pilot burner
9
Burner and Control Assembly
10
Gas connection
11
Airflow sensor (Modairflow
models)
12
Fan Delay Control
(non-Modairflow)
13
Electrical Assembly
14
Piezo unit
15
Spillage monitoring device (TTB)
(at rear)
16
Electronics module
(MODAIRFLOW)
Fig. 1
1.1
HI-SPEC J65 is an open-flued, fan assisted downflow, ducted warm air heater, which may be supplied with MODAIR-
FLOW control and in conjunction with an ELJAN 6 water circulator. A non-MODAIRFLOW version is available as an
option. A Spillage Monitoring Device (TTB) is fitted which senses the temperature in the draught diverter, and shuts down
the appliance when this temperature rises due to the presence of flue gases.
1.2
The Air heater output can be adjusted between 16.1kW (58.0MJ/h, 55,000Btu/h) and 19.1kW (68.6MJ/h, 65,000Btu/h).
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is
3.32kW (11.5MJ/h, 11,340Btu/h).
THIS APPLIANCE CONFORMS TO BS EN 55014
Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for Gas Appliances)
BS 5440 Pt. 2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws
HI-SPEC J65 WARM AIR HEATERS
MODAIRFLOW and non-MODAIRFLOW Control
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. No 42 451 14
Publication No. ZZ 941/8
October 2006
These instructions are to be left with the User or adjacent to the Gas Meter
1
8
11 12
5
14
9
7
6
10
3
4
16
13
15
2
1
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.
JOHNSON & STARLEY LTD.
Telephone: (01604) 762881
Rhosili Road,
Brackmills,
Fax:
(01604) 767408
Northampton NN4 7LZ
1.
BRIEF DESCRIPTION
1
Air Filter
2
Air circulating fan
3
Fuse(s)
4
Time control
5
Data plate
6
Limit switch
7
Multifunctional control
8
Pilot burner
9
Burner and Control Assembly
10
Gas connection
11
Airflow sensor (Modairflow
models)
12
Fan Delay Control
(non-Modairflow)
13
Electrical Assembly
14
Piezo unit
15
Spillage monitoring device (TTB)
(at rear)
16
Electronics module
(MODAIRFLOW)
Fig. 1
1.1
HI-SPEC J65 is an open-flued, fan assisted downflow, ducted warm air heater, which may be supplied with MODAIR-
FLOW control and in conjunction with an ELJAN 6 water circulator. A non-MODAIRFLOW version is available as an
option. A Spillage Monitoring Device (TTB) is fitted which senses the temperature in the draught diverter, and shuts down
the appliance when this temperature rises due to the presence of flue gases.
1.2
The Air heater output can be adjusted between 16.1kW (58.0MJ/h, 55,000Btu/h) and 19.1kW (68.6MJ/h, 65,000Btu/h).
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is
3.32kW (11.5MJ/h, 11,340Btu/h).
THIS APPLIANCE CONFORMS TO BS EN 55014
Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for Gas Appliances)
BS 5440 Pt. 2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws
HI-SPEC J65 WARM AIR HEATERS
MODAIRFLOW and non-MODAIRFLOW Control
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. No 42 451 14
Publication No. ZZ 941/8
October 2006
These instructions are to be left with the User or adjacent to the Gas Meter
1
8
11 12
5
14
9
7
6
10
3
4
16
13
15
2
1
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.
JOHNSON & STARLEY LTD.
Telephone: (01604) 762881
Rhosili Road,
Brackmills,
Fax:
(01604) 767408
Northampton NN4 7LZ
1.
BRIEF DESCRIPTION
1
Air Filter
2
Air circulating fan
3
Fuse(s)
4
Time control
5
Data plate
6
Limit switch
7
Multifunctional control
8
Pilot burner
9
Burner and Control Assembly
10
Gas connection
11
Airflow sensor (Modairflow
models)
12
Fan Delay Control
(non-Modairflow)
13
Electrical Assembly
14
Piezo unit
15
Spillage monitoring device (TTB)
(at rear)
16
Electronics module
(MODAIRFLOW)
Fig. 1
1.1
HI-SPEC J65 is an open-flued, fan assisted downflow, ducted warm air heater, which may be supplied with MODAIR-
FLOW control and in conjunction with an ELJAN 6 water circulator. A non-MODAIRFLOW version is available as an
option. A Spillage Monitoring Device (TTB) is fitted which senses the temperature in the draught diverter, and shuts down
the appliance when this temperature rises due to the presence of flue gases.
1.2
The Air heater output can be adjusted between 16.1kW (58.0MJ/h, 55,000Btu/h) and 19.1kW (68.6MJ/h, 65,000Btu/h).
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is
3.32kW (11.5MJ/h, 11,340Btu/h).
THIS APPLIANCE CONFORMS TO BS EN 55014
Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for Gas Appliances)
BS 5440 Pt. 2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws
HI-SPEC J65 WARM AIR HEATERS
MODAIRFLOW and non-MODAIRFLOW Control
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. No 42 451 14
Publication No. ZZ 941/8
October 2006
These instructions are to be left with the User or adjacent to the Gas Meter
1
8
11 12
5
14
9
7
6
10
3
4
16
13
15
2
1
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.
JOHNSON & STARLEY LTD.
Telephone: (01604) 762881
Rhosili Road,
Brackmills,
Fax:
(01604) 767408
Northampton NN4 7LZ
Содержание 42-451-14
Страница 24: ...www johnsonandstarley co uk 24 11 WIRING DIAGRAMS Fig 5a MODAIRFLOW CIRCUIT DIAGRAM...
Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 Fig 5b Non MODAIRFLOW CIRCUIT DIAGRAM...
Страница 26: ...www johnsonandstarley co uk 26 12 FUNCTIONAL DIAGRAMS Fig 6a Non MODAIRFLOW FUNCTIONAL DIAGRAM...
Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 Fig 6b MODAIRFLOW FUNCTIONAL DIAGRAM...
Страница 28: ...www johnsonandstarley co uk 28 13 DIMENSIONS Fig 7 HI SPEC J65 DIMENSIONS...
Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 14 NOTES...
Страница 31: ...31 Sales Spares Replacement Help Line 01604 762881 16 EXPLODED DIAGRAM Fig 8 HI SPEC J65 EXPLODED DIAGRAM...