The 60 gallon heater is equipped with a Heat Reflector 
Shield (see Figure 2). This Shield reflects heat from the 
High-input heaters to prevent damage to combustible floors. 
The Shield is held in place by three (3) tabs that rest on the 
inside of the legs of the water heater. Ensure the Shield is 
positioned horizontally (parallel to the bottom of the heater) 
and in the designated position of 38mm (1.5 in.) below the 
flame-arrestor.

Figure 2

  Heat Shield Installation (60 gallon only)

HEAT SHIELD

FLAME 

ARRESTOR

DRAIN 
VALVE

LEG

BOTTOM 

PAN

WARNING

Do not install directly on carpet. Instead, place the 
water heater on a metal or wood panel extending a 
minimum of 75mm (3 in.) from all sides. In alcoves 
or closets, cover the carpet completely. Ensure this 
panel is capable of supporting the weight of this 
heater when filled with water.
FAILURE TO PROPERLY INSTALL THIS HEATER MAY 
RESULT IN A FIRE HAZARD.

The water heater shall be located in an area not subject 
to freezing temperatures. Water heaters located in uncon-
ditioned spaces (e.g., attics, basements, etc.) may require 
insulation of the water and drain piping to protect against 
freezing. Proper ventilation needs to be provided for water 
heaters installed in unconditioned spaces (e.g., attics, base-
ments, etc.) in order to avoid an event where air tempera-
ture exceeds 42°C (108°F). The drain and controls must be 
easily accessible for operation and service. Maintain proper 
clearances as specified on the data plate.
Ensure that the water heater is level. This heater may be 
installed in a closet or alcove and is certified for operation 
on a combustible floor.

Figure 3

  Minimum Clearance Locations

AIR INTAKE

VENT

FRONT 600mm 
(24 in.) MIN. 
FOR SERVICE

BACK 25mm (1 in.)

SIDES 
25mm 
(1 in.)

SIDES AND 
BACK 25mm 
(1 in.)

TOP TO CEILING 
200mm (8 in.)

Do not locate the water heater near an air-moving device. 
The operation of air-moving devices such as exhaust fans, 
ventilation systems, clothes dryers, fireplaces, etc., can 
affect the proper operation of the water heater. Special 
attention must be given to conditions these devices may 
create. Flow reversal of flue gases may cause an increase 
of carbon monoxide inside of the dwelling.
If the water heater is located in an area that is subject to 
an excessive amount of lint, dirt or oil, it may be necessary 
to clean the flame arrestor periodically (see “Maintenance” 
section).

Important:

 It is always recommended that a suitable drain 

pan (field supplied) be installed under the water heater to 
protect the area from water damage resulting from normal 
condensation, a leaking tank or piping connections. Refer to 
Figure 1. Under no circumstances is the manufacturer to be 
held responsible for any water damage in connection with 
this water heater.

 Gas Supply

Install the gas piping as shown in Figure 4. Use only new 
pipe and fittings with clean-cut threads. Sealing compounds 
used on the pipe threads shall be approved for use with 
natural and propane gas.
Use gas piping of adequate sizing to ensure gas input. 
Gas piping material must be approved for use with natu-
ral gas and propane fuels. All piping must comply with all 
local codes and with the latest edition of

 “Natural Gas 

and Propane Installation Code” CSA-B149.

1 in Canada, 

“National Fuel Gas Code” ANSI Z223.1 (NFPA 54)

 in the 

U.S.A. The final connection to the water heater is made 
using 1/2” NPT.
Before connecting to the gas service, check that a properly 
sized gas meter and regulator are available to service the 
water heater. If other appliances are using the same meter 
and regulator, ensure that the capacity of the meter and 
regulator matches that of the combined input of all appli-
ances connected to it.
DO NOT tamper with the gas control/thermostat, igniter, 
thermocouple, or temperature and pressure relief valve. 
Tampering voids all warranties. Only a qualified service 
technician should service these components.

Figure 4

  Recommended Gas Piping

GROUND-

JOINT UNION

MANUAL 

GAS 

SHUT-OFF

GAS CONTROL/THERMOSTAT

75mm (3 in.)

 

– 6 – 

Содержание G6058 Series

Страница 1: ...TY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agenc...

Страница 2: ...ting Instructions 13 Lighting the Pilot If the Status Light Does Not Blink If the Pilot Does Not Light If the Pilot Lights but the Status Light Does Not Blink Lighting Instructions 14 V OPERATION 15 B...

Страница 3: ...ct vented water heater which takes its combustion air either from the installation area or from air ducted to the unit from the outside In addition to the installation instructions found in this man u...

Страница 4: ...BUSTION AND VENTILATION AIR IS NOT RESTRICTED DANGER Carbon Monoxide Warning Follow all vent system requirements by the local authorities having jurisdiction over your installation Failure to do so ca...

Страница 5: ...ny location selected it is recommended that a suitable drain pan be installed under the water heater This pan must limit the water level to a MAXIMUM depth of 45mm 1 3 4 in and have a diameter that is...

Страница 6: ...xhaust fans ventilation systems clothes dryers fireplaces etc can affect the proper operation of the water heater Special attention must be given to conditions these devices may create Flow reversal o...

Страница 7: ...t leak test liquid Bubbles will indicate leaks Never use a match or open flame to test for gas leaks A fire or explosion could result If leaks exist repair as required and retest DO NOT light the burn...

Страница 8: ...ssary skills required to prop erly install this venting system you should not proceed but enlist the help of a qualified service technician Drafthood Installation SLOPE UP 21mm PER METRE 1 4 in PER ft...

Страница 9: ...mentally handicapped If any one using the hot water fits into one of these groups or if there is a provincial state or local code requiring a certain temperature water at the hot water faucet then you...

Страница 10: ...the data plate of the water heater The Discharge Line Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Must not be capped blocke...

Страница 11: ...bar on the temperature dial will increase the risk of scald injury Hot water can produce third degree burns in 6 seconds at 60 C 140 F in 30 seconds at 54 C 130 F in 5 minutes at 49 C 120 F 1 Have the...

Страница 12: ...5 seconds 65 149 1 second 2 seconds 68 154 instantaneous 1 seconds U S Government Memorandum C P S C Peter L Armstrong Sept 15 1978 VAC GAS CONTROL TEMPERATURE KNOB STATUS LIGHT IGNITER 120 F MARK 130...

Страница 13: ...ght the Igniter may not be sparking or the unit may not be getting gas or for a new installation there may still be air in the gas line Each time you click the igniter button you should be able to see...

Страница 14: ...e gas control temperature knob and repeat steps 2 through 5 waiting 10 minutes before attempting to relight the pilot If the status light does not start blinking after three lighting attempts turn the...

Страница 15: ...ed in the first 20 minutes from start up due to heavy condensation In this situation if the unit is relit it will fol low its normal heating cycle without further incidents After installation always a...

Страница 16: ...inlet valve and nearby hot faucet until the water is no longer hot 5 Open the water heater drain valve and allow all the water to drain from the tank Flush the tank with water as needed to remove sed...

Страница 17: ...ian Figure 15 T P Relief Valve Test TEMPERATURE AND PRESSURE RELIEF VALVE MANUAL RELIEF VALVE DISCHARGE LINE TO DRAIN Resetting and Replacing the Safety TCO Switch NG models Figure 16 TCO Switch TCO R...

Страница 18: ...control valve thermostat 6 To remove the gas control valve thermostat thread a 100mm 4 in section of gas pipe into the inlet and use it to turn the gas control valve thermostat counter clockwise Do no...

Страница 19: ...tion If such a solution is not available use a mixture of hand dish washing soap and water one part soap to 15 parts water or childrens soap bubble solution Bubbles form ing indicate a leak Correct an...

Страница 20: ...ERMOPILE ASSEMBLY SCREW RETAINER CLIP WHITE WIRE MANIFOLD COMPONENT BLOCK MANIFOLD DOOR BURNER AND OTHER FITTINGS NOT SHOW FOR CLARITY IGNITER WIRE Figure 22 Manifold Door Assembly 6 Read this step ca...

Страница 21: ...ance Do not use piping that has been treated with chromates broiler seal or other chemicals and do not add chemicals to the water heating piping Do not introduce toxic chemicals such as those used for...

Страница 22: ...trol Temperature Knob was not held in for sufficient time 6 Low gas pressure 7 No gas 8 Dirt in gas lines 9 Cold drafts 10 Thermostat ECO switch open 1 Replace igniter pilot assembly 2 See Lighting In...

Страница 23: ...ter heater Check flue way flue baffle and burner 2 Clean locate source and correct 3 Provide fresh air ventilation SMOKING AND CARBON FORMATION SOOTING 1 Insufficient secondary air 2 Low gas pressure...

Страница 24: ...Wait 10 minutes for the Thermopile to cool then attempt to relight Pilot by following the lighting instructions on the water heater s label Until the Thermopile reaches its normal operating temperatu...

Страница 25: ...e minute Remove the outer door Look through the sight glass for a pilot flame If a pilot flame is observed with the gas control valve thermostat knob set to the OFF position the pilot valve is stuck o...

Страница 26: ...D DOOR GASKET 25 BURNER Figure 27 Manifold Door Assembly Vesta 25 14 17 18 19 20 22 23 24 21 15 1 NIPPLE HOT OUTLET 2 NIPPLE COLD INLET 3 DRAFTHOOD 4 TEMPERATURE PRESSURE RELIEF VALVE 6 ANODE 7 DIP TU...

Страница 27: ...e water heater s Model Number SKU Serial Number date of purchase and date of installation c THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THIS EXPRESS WARRANTY IS WHER...

Страница 28: ...cy beyond the control of the Manufacturer or s The water heater is installed in a closed system without adequate provision for thermal expansion 3 Except when speci cally prohibited by the applicable...

Отзывы: