 III) INSTALLATION

 Unpacking the Water Heater

WARNING

Excessive Weight Hazard

Use two or more people to move and install 
water heater. Failure to do so can result in 
back or other injury.

Important:

 Do not remove any permanent instructions, 

labels or the rating plate from the outside of the water heater 
or on the inside of panels.

1.  Move the water heater to the location of installation 

before removing the exterior packaging.

2.  Remove exterior packaging and place installation com-

ponents aside.

3.  Inspect all parts for damage prior to installation and 

start-up.

4.  Completely read and understand all instructions before 

attempting to assemble and install this product.

If you observe damage to the water heater or any of its com-
ponents, DO NOT ASSEMBLE OR INSTALL IT OR MAKE 
ANY ATTEMPT TO FIX THE DAMAGED PART(S). Contact 
the place of purchase for further instructions.
5.  After installation, dispose of packaging material in the 

proper manner.

 Location Requirements

IMPORTANT:

This water heater must be installed strictly in accordance 
with the instructions enclosed, and local electrical, fuel 
and building codes. It is possible that connections to 
the water heater, or the water heater itself, may develop 
leaks. IT IS THEREFORE IMPERATIVE that the water 
heater be installed so that any leakage of the tank or 
related water piping is directed to an adequate drain in 
such a manner that it cannot damage the building, fur-
niture, floor covering, adjacent areas, lower floors of the 
structure or other property subject to water damage. This 
is particularly important if the water heater is installed in 
a multi-story building, on finished flooring or carpeted 
surfaces. THE MANUFACTURER WILL NOT ASSUME 
ANY LIABILITY for damage caused by water leaking from 
the water heater, pressure relief valve, or related fittings. 
Select a location as centralized within the piping system 
as possible. In any location selected, it is recommended 
that a suitable drain pan be installed under the water 
heater. This pan must limit the water level to a MAXIMUM 
depth of 45mm (1 3/4 in.) and have a diameter that is a 
minimum of 50mm (2 in.) greater than the diameter of the 
water heater. Suitable piping shall connect the drain pan 
to a properly operating floor drain. When used with a fuel-
fired heater, this drain pan must not restrict combustion 
air flow.

Note:

 Before installing this water heater, consideration and 

planning must be given to the following details:
• Location 

and 

Clearances.

• 

Access for gas supply; See “Gas Supply”.

• 

How and where to obtain combustion and ventilation air 
supply; See “Air Requirements”.

• 

Routing and support of the vent piping.

• 

Position of water supply and placement of water piping 
for hot and cold water; See “Water Supply”.

• 

Floor drain and service.

 In Earthquake Zones

Note:

 The water heater must be braced, anchored, or 

strapped to avoid moving during an earthquake. Contact 
local utilities for code requirements in your area.

Note:

 REVIEW SAFETY WARNINGS FOUND IN THE 

FRONT OF THIS MANUAL BEFORE PROCEEDING

 Clearances and Accessibility

Specific clearance locations are shown in Figure 3. A mini-
mum of 600mm (24 in.) of front clearance shall be provided 
for inspection and service. We recommend that 0.9m (36 
in.) above be maintained for serviceability.

Locate the water heater such that all controls are easily 
accessible, and the rating plate is visible.

Clearance to combustibles varies by model.  Refer to rating 
plate to confirm clearances.
Heaters with a volume of 19 gallons through 50 gallons and 
60 gallon (standard input) must have the following minimum 
clearances to combustibles:
  Front 

102mm (4 in.)

  Sides and Rear  25mm (1 in.)
  Top 

203mm (8 in.)

  Flue 

152mm (6 in.)

JW6058 and G6058 (high input) series heaters must have 
the following minimum clearances to combustibles:
  Front 

127mm (5 in.)

  Sides and Rear  25mm (1 in.)
  Top 

203mm (8 in.)

  Flue 

152mm (6 in.)

45mm

(1 3/4 in.) 

MAX

AT LEAST 50mm (2 in.) 

GREATER THAN THE 

DIAMETER OF THE 

WATER HEATER.

PIPE TO 

ADEQUATE 

DRAIN

Figure 1

  Typical Drain Pan Installation

 

– 5 – 

Содержание G6058 Series

Страница 1: ...TY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agenc...

Страница 2: ...ting Instructions 13 Lighting the Pilot If the Status Light Does Not Blink If the Pilot Does Not Light If the Pilot Lights but the Status Light Does Not Blink Lighting Instructions 14 V OPERATION 15 B...

Страница 3: ...ct vented water heater which takes its combustion air either from the installation area or from air ducted to the unit from the outside In addition to the installation instructions found in this man u...

Страница 4: ...BUSTION AND VENTILATION AIR IS NOT RESTRICTED DANGER Carbon Monoxide Warning Follow all vent system requirements by the local authorities having jurisdiction over your installation Failure to do so ca...

Страница 5: ...ny location selected it is recommended that a suitable drain pan be installed under the water heater This pan must limit the water level to a MAXIMUM depth of 45mm 1 3 4 in and have a diameter that is...

Страница 6: ...xhaust fans ventilation systems clothes dryers fireplaces etc can affect the proper operation of the water heater Special attention must be given to conditions these devices may create Flow reversal o...

Страница 7: ...t leak test liquid Bubbles will indicate leaks Never use a match or open flame to test for gas leaks A fire or explosion could result If leaks exist repair as required and retest DO NOT light the burn...

Страница 8: ...ssary skills required to prop erly install this venting system you should not proceed but enlist the help of a qualified service technician Drafthood Installation SLOPE UP 21mm PER METRE 1 4 in PER ft...

Страница 9: ...mentally handicapped If any one using the hot water fits into one of these groups or if there is a provincial state or local code requiring a certain temperature water at the hot water faucet then you...

Страница 10: ...the data plate of the water heater The Discharge Line Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Must not be capped blocke...

Страница 11: ...bar on the temperature dial will increase the risk of scald injury Hot water can produce third degree burns in 6 seconds at 60 C 140 F in 30 seconds at 54 C 130 F in 5 minutes at 49 C 120 F 1 Have the...

Страница 12: ...5 seconds 65 149 1 second 2 seconds 68 154 instantaneous 1 seconds U S Government Memorandum C P S C Peter L Armstrong Sept 15 1978 VAC GAS CONTROL TEMPERATURE KNOB STATUS LIGHT IGNITER 120 F MARK 130...

Страница 13: ...ght the Igniter may not be sparking or the unit may not be getting gas or for a new installation there may still be air in the gas line Each time you click the igniter button you should be able to see...

Страница 14: ...e gas control temperature knob and repeat steps 2 through 5 waiting 10 minutes before attempting to relight the pilot If the status light does not start blinking after three lighting attempts turn the...

Страница 15: ...ed in the first 20 minutes from start up due to heavy condensation In this situation if the unit is relit it will fol low its normal heating cycle without further incidents After installation always a...

Страница 16: ...inlet valve and nearby hot faucet until the water is no longer hot 5 Open the water heater drain valve and allow all the water to drain from the tank Flush the tank with water as needed to remove sed...

Страница 17: ...ian Figure 15 T P Relief Valve Test TEMPERATURE AND PRESSURE RELIEF VALVE MANUAL RELIEF VALVE DISCHARGE LINE TO DRAIN Resetting and Replacing the Safety TCO Switch NG models Figure 16 TCO Switch TCO R...

Страница 18: ...control valve thermostat 6 To remove the gas control valve thermostat thread a 100mm 4 in section of gas pipe into the inlet and use it to turn the gas control valve thermostat counter clockwise Do no...

Страница 19: ...tion If such a solution is not available use a mixture of hand dish washing soap and water one part soap to 15 parts water or childrens soap bubble solution Bubbles form ing indicate a leak Correct an...

Страница 20: ...ERMOPILE ASSEMBLY SCREW RETAINER CLIP WHITE WIRE MANIFOLD COMPONENT BLOCK MANIFOLD DOOR BURNER AND OTHER FITTINGS NOT SHOW FOR CLARITY IGNITER WIRE Figure 22 Manifold Door Assembly 6 Read this step ca...

Страница 21: ...ance Do not use piping that has been treated with chromates broiler seal or other chemicals and do not add chemicals to the water heating piping Do not introduce toxic chemicals such as those used for...

Страница 22: ...trol Temperature Knob was not held in for sufficient time 6 Low gas pressure 7 No gas 8 Dirt in gas lines 9 Cold drafts 10 Thermostat ECO switch open 1 Replace igniter pilot assembly 2 See Lighting In...

Страница 23: ...ter heater Check flue way flue baffle and burner 2 Clean locate source and correct 3 Provide fresh air ventilation SMOKING AND CARBON FORMATION SOOTING 1 Insufficient secondary air 2 Low gas pressure...

Страница 24: ...Wait 10 minutes for the Thermopile to cool then attempt to relight Pilot by following the lighting instructions on the water heater s label Until the Thermopile reaches its normal operating temperatu...

Страница 25: ...e minute Remove the outer door Look through the sight glass for a pilot flame If a pilot flame is observed with the gas control valve thermostat knob set to the OFF position the pilot valve is stuck o...

Страница 26: ...D DOOR GASKET 25 BURNER Figure 27 Manifold Door Assembly Vesta 25 14 17 18 19 20 22 23 24 21 15 1 NIPPLE HOT OUTLET 2 NIPPLE COLD INLET 3 DRAFTHOOD 4 TEMPERATURE PRESSURE RELIEF VALVE 6 ANODE 7 DIP TU...

Страница 27: ...e water heater s Model Number SKU Serial Number date of purchase and date of installation c THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THIS EXPRESS WARRANTY IS WHER...

Страница 28: ...cy beyond the control of the Manufacturer or s The water heater is installed in a closed system without adequate provision for thermal expansion 3 Except when speci cally prohibited by the applicable...

Отзывы: