P-Rated
Rated power value of motor, unit is W. The
setting principle is that the rated power is equal
to the rated power value indicated on the pump
nameplate.
F-Rated
Rated frequency value of motor, unit is W. The
setting principle is that the rated power is equal
to the rated frequency value indicated on the
pump nameplate.
RPM-Rated
Rated speed value, in RPM. The setting
principle is that the rated speed is equal to the
rated speed indicated on the pump nameplate.
PF-Rated
Rated power factor, unit is. The setting
principle is that the rated power factor is equal
to the rated power factor indicated on the pump
nameplate.
Imotor
Motor overload current protection value, refer
to the water pump motor nameplate to set this
parameter, it is recommended to be equal to
1.2 times the motor rated current value.
StopFreq
Stop frequency value in Hz. The setting
principle is that the shutdown frequency is
approximately equal to the lowest output
frequency of the inverter when the PV pump
system is able to pump water.
M-Mode
Select this option to control the forward or
reverse of the motor. This parameter can be set
if the pump water is abnormal during the first