Operating instructions

8.5 Controller parameters

For Disinfection, pH value, bonded chlorine and conductivity inputs the 
following settings may be programmed:

Con-

troller

Xp value

Tn value

pH value

P

1 - 500 %

-

PI

1 - 500 %

1 - 200 min

PD

1 - 500 %

1 - 1200 s

PID

1 - 500 %

1 - 200 min

1 - 1200 s

The following control parameters are set by the manufacturer before 
shipment:

Controller

Xp

Tn

Tv

Disinfection controller

35 %

15 min

OFF

Controller pH value

10 %

15 min

OFF

8.6 Control direction

The control direction can be set for each controller. 

 

Possible options:
•  increase value   

(display "up" arrow)

•  decrease value   

(display "down" arrow)

•  2-side regulation  (only free chlorine and pH value)
The connection terminals are also marked with an arrow.

8.7 Basic load dosing

Basic load dosing can be configured outside of the control range. This 
dosing takes place even if the PID automatic controller output is 0%. 
If a basic load is configured, this value is shown in blue on the display 
screen in the Y display. The Y display for automatic control is shown in 
green. In the status display, this condition is indicated by a "+" after the 
Y display. Note that this basic load is always effective and that a certain 
percentage of the actuator is always open irrespective of the control 
even though the controller does not require dosing. The basic load can 
be adjusted separately for each output up to a maximum of 20% of the 
control range.

8.8 Manual mode

Controllers can be manually adjusted.
If a controller is manually operated, this will be indicated by a large "M" 
behind the "Y" in the status displays and the Y display on the screen will 
be shown blue. Manual operation is also indicated in the bottom row.
In the manual setting menu the control output can be adjusted directly 
to any value between 0% and 100% and saved.

ATTENTION!

Manual operation is not reset automatically.

9 Alarms

9.1 Measurement alarms

For each measuring input a minimum and a maximum alarm can be 
set. In the case of a value falling above or below this value, the alarm is 
shown and an alarm relay as common alarm triggers. The alarm settings 
of the relay and the controller for this measuring input can be analysed 
separately. The time delay of the alarm is adjustable (delay).

9.2 Safety cutout  (Y alarm)

TOPAX is equipped with a safety disconnect. If, due to an unforeseeable 
event, a sensor fault etc. the controller output power exceeds 95% for 
a programmable period, an alarm is displayed for this controller and the 
controller output is set to 0%. This function is activated by default. The 
time is adjustable.
An adjusted basic load is also switched off in the event of a safety cutout.
All alarms are displayed in clear text form on the screen. The alarm 
relay is activated and the measured value, which caused the alarm, is 
shown in red.

ATTENTION!

The alarms are represented in red on the display. 
After clearing, acknowledge the alarms by pressing 
the OK key twice.

(see also chapter “15 Troubleshooting and diagnostics” on page 38).

Содержание TOPAX DE

Страница 1: ...TOPAX DE Two Channel Controller EN 01 Operating instructions Read this operating manual before using the equipment To be retained for future reference...

Страница 2: ...tion amperometric measurement cells 20 5 2 pH value measurement input 21 5 3 Measurement output Redox potential 23 5 4 Temperature measurement input 23 6 Explanation of digital signal inputs 24 6 1 St...

Страница 3: ...behalf of the operating company The operating company must also ensure that the operating manual has been under stood 1 4 Electrical device safety instructions Basic safety precautions should always b...

Страница 4: ...nd obtaining spare parts TOPAX may be converted or changed only by qualified technical person nel If the configuration of the TOPAX is wrongly made by assembly or ser vice personnel errors and dangers...

Страница 5: ...als Total chlorine measuring input Encapsulated electrode Measuring range adjustable from 0 1 00 mg l 0 2 00 mg l or 0 10 mg l Disturbance variable input option ally available 0 20 mA or 4 20 mA Distu...

Страница 6: ...mm 8 7 mm Relay output alarm M16 X 1 5 NYM O 3x 1 5 mm 9 1 mm connection to PC computer cable Cat 5 M12 X 1 5 Type 2X2XAWG24 1 5 7 mm Connection of current outputs remote communication cable M12 X 1 5...

Страница 7: ...ts are removed at the same time the front housing will no longer be attached to the bottom section ATTENTION The equipment must only be opened when it is dis connected from the power supply 4 2 Dimens...

Страница 8: ...he software configuration automatically assigns these outputs to the respective terminals in a sequential order depending on the configura tion of the TOPAX 1 Disinfection controller 2 Controller pH v...

Страница 9: ...ate the RS 485 resistances on the last TOPAX in the network 4 4 6 TopView software For remote viewing on a PC the manufacturer offers the full version of the TopView display program and a freeware ver...

Страница 10: ...must be clean and dry The permissible bending radius of the cable must be respected The quality of the holding wires must correspond to the defaults from the data sheet of the sensor IMPORTANT If pos...

Страница 11: ...surement output 0 4 20 mA Redox 6 7 Measurement output 0 4 20 mA Temperature or programmed as controller output 8 9 Measurement output 0 4 20 mA combined chlorine or programmed as controller output 10...

Страница 12: ...r polarity of clips 59 and 61 at wish 60 Driver 61 4 7 3 Input module 3x Terminal Function Cable colour 71 Reference electrode with integrated cable Disinfection potentiostatic measuring cell Referenc...

Страница 13: ...71 72 73 7 pH Single Rod Measuring Cell PE110 pH 52 53 8 Redox Single Rod Measuring Cell ME110 ORP 54 55 9 Reference Electrode for Potentiostat SS Electrode for Potentiostat 1 4571 Gold Electrode for...

Страница 14: ...rrent output Current output 20mA analogue accessories Menu configuration 0 6 3 DANGER Open the housing of the TOPAX controller with disconnected power supply only Secure the power supply to prevent it...

Страница 15: ...54 55 61 51B 52B 71 72 73 74 75 76 77 78 39 40 41 43 44 45 46 42 35 95 96 A B A B pH value dosing pump PC interface Temperature pH value Redox 90 264 V AC Input module 5 fold CPRT ATE 5 fold Power sup...

Страница 16: ...12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 36 37 38 PE N L 33 34 92 93 94 87 88 89 90 91 86 81 82 83 84 85 56 57 58 59 60 51A 52A 53 54 55 61 51B 52B 71 72 73 74 75 76 77 78 39 40...

Страница 17: ...1 First set up and programming guidelines After correct installation switch on the power supply The TOPAX is programmed by the manufacturer based on customers specs before shipment and is supplied alo...

Страница 18: ...highlighted in grey To go back to the previous menu press the key back or 4 11 10 Menu 0 5 Completing the configuration The TOPAX moves immediately on to the configuration at the latest after menu 0 4...

Страница 19: ...hemical and physical correlations which are necessary to understand the behaviour of the measurement inputs The measurement inputs are processed for Disinfection pH value Redox potential Temperature A...

Страница 20: ...d using a two point calibration see section 12 1 5 Menu 1 2 Calibration on page 30 The physical measurement A measured on the measuring cell is shown on the display during calibration Reference value...

Страница 21: ...4 20 mA Whenever your TOPAX fea tures a lower value than 3 5 mA an alert message is displayed total chlorine sensor failure the alarm relay is switched 5 2 pH value measurement input 5 2 1 Technical d...

Страница 22: ...ble and the plug connectors If the zero point and transconductance values of the single rod measuring cell exceed the tolerances the system notifies the operator with a warning mes sage The measuring...

Страница 23: ...ixed buffer solution value The deviation should not exceed 10 approximately The plausibility of the transconductance measurement is monitored throughout the process After a reaction time approx 1 minu...

Страница 24: ...tal inputs are activated the level switches must be connected to the terminals respectively If no level switch is at tached the inputs are to be deactivated 7 Explanation of measuring values outputs 7...

Страница 25: ...ed current 0 4 20 mA or control outputs with pulse frequency The latter can be controlled as electronic optocoupler or relay outputs 8 Controller explanation 8 1 Definitions Term Definition actual val...

Страница 26: ...nd Ph close to the setpoints within tight limits e g for bathing the control ler must be adjusted to the controlled system This is achieved via the control parameters Xp for the proportional area Tn f...

Страница 27: ...f 20 of the control range 8 8 Manual mode Controllers can be manually adjusted If a controller is manually operated this will be indicated by a large M behind the Y in the status displays and the Y di...

Страница 28: ...nually adjusted to the actuator independently of the settings in the service menu recorder It is possible to configure the 0 20 mA controller output and a 4 20 mA recorder output It must be noticed th...

Страница 29: ...ecorder night mode service 2 mg l pH C 26 3 7 04 0 39 Fig 20 Menu 2 Extension of the main menu 12 1 3 Overview of the sub menus You can access all other sub menus through the main menu menu 1 and the...

Страница 30: ...electrode Menu 1 2 1 3 Encapsulated electrode Menu 1 2 1 pH value pH single rod measuring cell without specifications about slope rate Menu 1 2 2 pH single rod measuring cell with specifications abou...

Страница 31: ...1 4 2 Switching status of all outputs 1 4 3 Physical values and calibrated resistivity values of all inputs 1 4 4 used software version serial number hardware identification data input identification...

Страница 32: ...Xp value 2 1 2 3 2 Parameter Tn ON or OFF time 2 1 2 3 3 Parameter Tv ON or OFF time 2 1 2 4 Basic load ON or OFF time 2 1 2 5 Manual mode value ON OFF Select one of the two control units The device g...

Страница 33: ...digit of the limit value is highlighted in grey and can be ad justed Use the arrow keys to set up the value switch over between the individual positions alter numerical values Confirm the entry by pr...

Страница 34: ...s To select the menus press the arrow keys and Confirm the selection with OK 12 1 14 Menu 0 4 0 Configuration The configuration of TOPAX can be changed saved and loaded Existing configuration files ar...

Страница 35: ...rd Main menu menu 2 service password and service password In these menus you can block the various levels by using a password a 4 digit numerical code All information menus remain available The passwo...

Страница 36: ...a system name on the display Switching on off additional information on the standard display Setting the brightness of the display 12 1 29 Menu 5 18 Language Main menu menu 2 service language User lan...

Страница 37: ...OFF 14 Memory card The memory card transfers and stores language data and logfiles The data which is saved on the card can be transferred to a PC by means of a reading device To remove the memory card...

Страница 38: ...xceeded Activated configurable Min alarm Measurement below set level Activated configurable Y alarm Safety cutout see item 9 2 Activated configurable 15 3 Remedy Display Reason Remedy System start Sys...

Страница 39: ...t Disinfection Types of output Terminal connection clips Servomotor with potentiometer Motor Potentiometer with position feedback Servo motor without potentiometer Pulse frequency Optocoupler Pulse fr...

Страница 40: ...27 28 OK closed OK opened Not active 17 Device revision This operating manual applies to the following devices Device and model Revision status Software Version TOPAX 1 2013 1 25 onwards Language file...

Страница 41: ...t person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions of the device Point of use system designation Access...

Страница 42: ...ualquier modificaci n en la presente mercanc a sin nuestra previa autorizaci n esta declaraci n pierde su validez NL EU overeenstemmingsverklaring Ondergetekende Lutz Jesco GmbH Am Bostelberge 19 3090...

Страница 43: ...ata 5 H Hardware status 35 Housing 7 I Inputs module 8 Installation 7 K Key layout 17 L Language 36 Level dosing pump 24 Level inputs 24 Logbook 28 M Manual mode 27 Measurement input Disinfection 20 m...

Страница 44: ...com Internet www lutz jescoasia com sterreich Lutz Jesco GmbH Aredstra e 7 2 2544 Leobersdorf Austria Tel 43 2256 62180 Fax 43 2256 6218062 E Mail info lutz jesco at Internet www lutz jesco at Middle...

Отзывы: