14 | BA-40400-02-V14
Two-Channel Controller TOPAX DE
4.9 Output configuration
No.
Article name
Output
Configuration
Signal type
Terminal
1
C7700 20mA
Current output
Current output (20mA)
analogue
See
TOP
AX menu configura
tion 0.6.3
2
C7700 3-p-s
Relay (3 step)
3 point step with poti
digital
3
EASYZON D/Da
Current output
Current output (20mA)
analogue
4
MAGDOS DE, DX, LT, LDp, LD, LK, LP
Opto coupler output
Impulsefrequency (opto)
digital
5
MAGDOS LA, LP, DX
Current output
Current output (20mA)
analogue
6
MAGDOS LB bis 2018
Relay (with power relay*)
On/off
digital
7
MAGDOS LDp, LD, LK, LP, LB ab 2018
Relay
On/off
digital
8
MEMDOS DX, LA, LP
Current output
Current output (20mA)
analogue
9
MEMDOS DX, LP
Opto coupler output
Impulsefrequency (opto)
digital
10
MEMDOS E, LB
Relay (with motor protection*)
On/off
digital
11
MEMDOS SMART LB, LD, LK, LP
Relaisausgang
On/off
digital
12
MEMDOS SMART LD, LK, LP
Opto coupler output
Impulsefrequency (opto)
digital
13
MEMDOS SMART LP
Current output
Current output (20mA)
analogue
14
MIDIDOS E
Relay (with motor protection*)
On/off
digital
15
MINIDOS A
Relay (with motor protection*)
On/off
digital
16
Peristaltic pump
Relay (with motor protection*)
Impulselength (relais)
digital
17
Technoline SC
Relay
Impulselength (relais), min. 300s
digital
18
Technoline SC
Relay
On/off
digital
19
Technomat PS
Relay
Impulselength (relais), min. 300s
digital
20
Technomat PS
Relay
On/off
digital
21
Technostar 2000 AT
Current output
Current output (20mA)
analogue
22
Technostar ST-30
Current output
Current output (20mA)
analogue
* accessories
Menu configuration 0.6.3
DANGER!
Open the housing of the TOPAX controller with disconnected power supply only! Secure the power supply to prevent it from
being switched on again.
The assignment of the output terminals depends on the connected devices and their configuration. The required terminals are shown in the menu 0.6.3.
The following steps will take you in that menu.
Precondition for action:
• The TOPAX controller has been successfully installed in accordance with section “4.5 Electrical installation” on page 9.
• The TOPAX controller is disconnected from the power supply.
• The housing of the TOPAX controller is closed.
Perform the following steps:
1. Establish the power supply of the TOPAX controller.
2. Wait until the device is booted.
3. Now press the following keys to get to the configuration menu:
• „OK“,
• „menu 2“,
• „service“,
• „OK“,
• „edit“.
4. Now you are able to change the configuration of the different input and output terminals. Choose the configuration of the output terminals appropiate
to the table above and confirm each entry with „next“ until you reached menu 0.5.
5. Press „save“ and confirm with „OK“. Now you can see the new configuration and the required terminals.
6. Press „next“ until you reached menu 0.6.3. Now you see the output terminals you have to connect your devices with. Note the numbers of the required
terminals.
7. Press „next“ and confirm with „OK“.
8. Disconnect the power supply of the TOPAX controller, open the housing and connect your devices to the required terminals.
9. Check the correct control of your devices and make corrections if necessary.
The TOPAX controller can now control the connected devices.