background image

GAMMA VERSUS MANUAL 

 

2

 

COD. 1257066                                                                                         Gamma VERSUS Manual v1.13 

 

 

1.

 

1.

 

INTRODUCTION

 

....................................................................................................................................

 

4

 

2.

 

INSTALLATIONS

 

TYPES

 

..............................................................................................................................

 

5

 

2.1

 

Swing

door

 

.......................................................................................................................................

 

5

 

2.2

 

Gate

 

.................................................................................................................................................

 

5

 

2.3

 

Sectional

 

door

 

..................................................................................................................................

 

6

 

2.4

 

Folding

door

 

....................................................................................................................................

 

6

 

2.5

 

Rolling

door

 

.....................................................................................................................................

 

7

 

2.6

 

Fast

door

 

..........................................................................................................................................

 

7

 

2.7

 

Two

 

leaves

 

sliding

 

door

 

...................................................................................................................

 

8

 

2.8

 

Two

 

leaves

 

swing

door

 

....................................................................................................................

 

8

 

3.

 

ASSEMBLY

 

AND

 

INSTALLATION

 

................................................................................................................

 

9

 

3.1

 

Installation

 

with

 

support

 

.................................................................................................................

 

9

 

3.2

 

Installation

 

without

 

support

 

............................................................................................................

 

9

 

3.3

 

Reverse

 

installation

 

.......................................................................................................................

 

10

 

4.

 

PARAMETERS

 

..........................................................................................................................................

 

11

 

4.1

 

ON/OFF

 

Option

 

parameters

 

..........................................................................................................

 

11

 

4.2

 

Numeric

 

parameters

 

......................................................................................................................

 

14

 

4.3

 

Switch

 

parameters

 

.........................................................................................................................

 

18

 

4.4

 

Input

 

parameters

 

...........................................................................................................................

 

19

 

4.5

 

Output

 

parameters

 

........................................................................................................................

 

22

 

4.6

 

Status

 

parameters

 

.........................................................................................................................

 

23

 

5.

 

LIGHT

 

INDICATORS

 

.................................................................................................................................

 

24

 

5.1

 

Indication

 

of

 

errors

 

/

 

warnings

 

.............................................................................................................

 

24

 

6.

 

DISPLAY

 

MESSAGES

 

................................................................................................................................

 

25

 

6.1

 

Serious

 

errors

 

.................................................................................................................................

 

25

 

6.2

 

Minor

 

errors

 

...................................................................................................................................

 

26

 

6.3

 

Warnings

 

........................................................................................................................................

 

26

 

7.

 

VERSUS

 

FUNCTIONS

 

...............................................................................................................................

 

28

 

7.1

 

Autoprogramming

 

function

 

...........................................................................................................

 

28

 

7.2

 

Hall

 

or

 

time

 

mode

 

function

 

............................................................................................................

 

29

 

7.3

 

Pedestrian

 

function

 

.......................................................................................................................

 

30

 

7.4

 

Speed

 

regulation

 

and

 

slow

 

speed

 

mode

 

in

 

AC

 

motors

 

function

 

...................................................

 

31

 

7.5

 

AC

 

motor

 

internal

 

limit

 

switches

 

and

 

blocking

 

detection

 

function

 

...............................................

 

33

 

7.6

 

Autoclosing

 

function

 

......................................................................................................................

 

35

 

7.7

 

Close

 

by

 

security

 

contact

 

function.................................................................................................

 

36

 

7.8

 

Deadman

 

function

 

.........................................................................................................................

 

37

 

7.9

 

No

 

stop

 

on

 

opening

 

function

 

.........................................................................................................

 

38

 

7.10

 

Radioband

 

function

 

.......................................................................................................................

 

39

 

7.11

 

Radiosens

 

function

 

........................................................................................................................

 

41

 

7.12

 

Electro

 

lock

 

and

 

reverse

 

strike

 

at

 

open

 

functions

 

.........................................................................

 

44

 

7.13

 

Backjump

 

function

 

.........................................................................................................................

 

46

 

7.14

 

Security

 

contact

 

autotest

 

function

 

................................................................................................

 

47

 

7.15

 

Security

 

edge

 

autotest

 

function

 

....................................................................................................

 

49

 

7.16

 

Closing

 

security

 

wired

 

edge

 

or

 

Radioband

 

inhibition

 

function

 

.....................................................

 

51

 

7.17

 

Closing

 

security

 

contact

 

inhibition

 

function

 

..................................................................................

 

52

 

7.18

 

Automatic

 

8K2/optical

 

security

 

edge

 

detection

 

function

 

.............................................................

 

53

 

7.19

 

Flash

 

and

 

pre

flash

 

function

 

..........................................................................................................

 

55

 

7.20

 

Anti

intrusive

 

function

 

...................................................................................................................

 

56

 

7.21

 

Alarm

 

function

 

...............................................................................................................................

 

57

 

7.22

 

Panic

 

function

 

................................................................................................................................

 

58

 

7.23

 

Hydraulic

 

mode

 

function

 

...............................................................................................................

 

59

 

7.24

 

Recharge

 

maneuver

 

function

 

........................................................................................................

 

61

 

7.25

 

Password

 

blocking

 

function

 

...........................................................................................................

 

62

 

Содержание GAMMA VERSUS Series

Страница 1: ...COD 1257066 Gamma VERSUS Manual v1 13 The contents of this manual is property of JCM TECHNOLOGIES S A GAMMA VERSUS MANUAL ...

Страница 2: ...28 7 2 Hall or time mode function 29 7 3 Pedestrian function 30 7 4 Speed regulation and slow speed mode in AC motors function 31 7 5 AC motor internal limit switches and blocking detection function 33 7 6 Autoclosing function 35 7 7 Close by security contact function 36 7 8 Deadman function 37 7 9 No stop on opening function 38 7 10 Radioband function 39 7 11 Radiosens function 41 7 12 Electro lo...

Страница 3: ...rnal limit switches detection 73 8 7 Manual Programming with slow speed function activated 74 8 8 Pedestrian Programming 76 8 9 Manual programming with slow speed function activated with two motors 77 9 PROGRAMMING CODES IN THE RECEIVER 80 9 1 Manual Programming MOTION transmitters 80 9 2 Programming by radio 81 9 3 Reset 81 10 ACCESSORIES 82 10 1 VERSUS PROG portable programmer 82 10 2 V POT card...

Страница 4: ...Versatile control units Under the concept Do It Yourself the control unit can be customized as the real needs of the client All the options and functions of the board can be configurated and modified from JCM Software previously agreed and be modified via radio by proximity o through cable directly on the board at the client offices or in the installation Moreover the design of the box allows inst...

Страница 5: ...GAMMA VERSUS MANUAL 5 COD 1257066 Gamma VERSUS Manual v1 13 2 INSTALLATIONS TYPES 2 1 Swing door 2 2 Gate ...

Страница 6: ...GAMMA VERSUS MANUAL 6 COD 1257066 Gamma VERSUS Manual v1 13 2 3 Sectional door 2 4 Folding door ...

Страница 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door ...

Страница 8: ...GAMMA VERSUS MANUAL 8 COD 1257066 Gamma VERSUS Manual v1 13 2 7 Two leaves sliding door 2 8 Two leaves swing door ...

Страница 9: ... in the wall and screw the support with 4cm diameter wall screws Hang the box on the support and screw the lower side 3 2 Installation without support Unscrew the 4 screws from the control unit to be released from the support Open the door to the left Present the box on the wall and mark the two holes with a pencil Remove the box and make holes in the wall Screw the box to the wall with screws at ...

Страница 10: ...do this you only need to screw the box upside down or mount the support upside down if included For the front keypad functions to be rotated so that the arrows indicating up opens and the arrow indicating down closes turn upside down the card VERSUS DPLAY and VERSUS POT plugged into the motherboard If you do not have any of them the front keypad acts the opposite of what logically expected ...

Страница 11: ...on opening and therefore will act accordingly In most cases it will open until this is found adding pulses or time if required 1 ON 0A FC CL installed 0 OFF Indicates whether during programming the panel has found and memorised a limit switch on closure and therefore will act accordingly In most cases it will close until this is found adding pulses or time if required 1 ON 0B Open mechanical stop ...

Страница 12: ...een programmed during the manoeuvre The security contact inhibition during the closing movement may not comply with regulations 1 ON 19 Substr Bjump PROG 0 OFF This refers to the special function of subtracting the number of pulses used in closure Back Jump from the total number of pulses of the movement In other words if the closure Back Jump is enabled the panel will search for the closure refer...

Страница 13: ...etect OptoEdge IN1 0 OFF Indicates that the IN1 input is configured as optical edge input 1 ON 30 Autodetect OptoEdge IN2 0 OFF Indicates that the IN2 input is configured as optical edge input 1 ON 31 Autodetect OptoEdge IN3 0 OFF Indicates that the IN3 input is configured as optical edge input 1 ON 91 Pre FLASH option 0 OFF Enables the pre flash function at the beginning of the manoeuvre 1 ON 92 ...

Страница 14: ...larm output by a fire alarm plus a closing security activated In OFF the output is activated when there is only a fire alarm activated D7 Automatic opening by fire alarm 0 OFF 1 ON Enable the automatic opening by fire alarm activation In OFF performs an automatic closing by the same fire alarm activation DC Autodetect OptoEdge IN8 0 OFF 1 ON Indicates that the IN8 input is configured as optical ed...

Страница 15: ...re to this point 37 Open Ped stop point 1000 Stop point for the door during pedestrian opening movements 38 Close Ped stop point 1000 Stop point for the door during pedestrian closure movements 39 Open Ped slow start pt 1000 Opening movement point where the slow speed is started in order to be able to slow down the door on pedestrian opening 3A Close Ped slow start pt 1000 Closing movement point w...

Страница 16: ... time 10 Activation time of the garage light 4C Flash frequency 10 Flash period time 4D Pre flash time 10 Pre flash time 4E Max sequence time 10 Maximum maneuver time 4F Press time to deadman 10 Needed pushing time of the Open or Close Pushbutton to enter to deadman mode 50 Panic signal period 10 Activation time of the panic signal 51 Integrator value TH1 1000 Integrator threshold 1 value internal...

Страница 17: ... the programmer will indicate the time from the beginning of the opening to this point CE Slow speed pos close M2 1000 Initial position of slow speed in motor M2 closing In case of operating by pulses it is the number of pulses form the floor door closed In case of operating by time the programmer will indicate the time from the beginning of the opening to this point CF Offset in opening between M...

Страница 18: ... the RSENS mode 10 RBAND CONFIG Enables the RBAND mode 11 TIME HALL CONFIG Configures 1 ON Time function 2 OFF HALL function 12 SEC CL TEST Enables the closing security contact autotest 13 SEC OP TEST Enables the opening security contact autotest 14 PRE FLASH Enables the pre flash function 15 CLOSING BY SEC CL Enables the closing security contact 16 COURTESY LIGHT FLASH Configures 1 ON garage ligh...

Страница 19: ...s not got a defined function 1 S EDGE CL Closing safety edge input 8k2 2 S EDGE OP Opening safety edge input 8k2 5 FC OP M1 M1 motor opening limit switch input NC 6 FC OP M2 M2 motor opening limit switch input NC 7 FC CL M1 M1 motor closing limit switch input NC 8 FC CL M2 M2 motor closing limit switch input NC 9 SEC OP Opening security contact input NC 10 SEC CL Closing security contact input NC ...

Страница 20: ...nput 41 OPTO EDGE OP Opening optical safety edge input 42 PRESSURE SWITCH Configuration input as pressure switch 43 AUTOEDGE CL Closing automatic 8K2 OPTO safety edge input 44 AUTOEDGE OP Opening automatic 8K2 OPTO safety edge input 45 COURTESY LIGHT ON Courtesy light activation input 46 OPEN SLOW SPEED REF Configuration input as opening slow speed entering reference 47 CLOSE SLOW SPEED REF Config...

Страница 21: ... 13 6C OPEN pushbutton IN 6D CLOSE pushbutton IN 6E PROG pushbutton IN 6F HALL A IN 70 OPTO EDGE IN 71 DCS CH1 IN 72 DCS CH2 IN 73 Low Voltage IN 74 Motion C1 IN 75 Motion C2 IN 76 Motion C3 IN 77 Motion C4 IN C9 OPEN 2 pushbutton IN CA CLOSE 2 pushbutton IN ...

Страница 22: ...Active output when error detection 13 PEDESTRIAN SEQUENCE Active output during pedestrian mode 14 PANIC SIGNAL Active output when panic signal detection 15 GREEN LIGHT Green traffic light control output 16 RED LIGHT Red traffic light control output 17 INSIDE GREEN LIGHT Green inside traffic light control output traffic control mode 18 INSIDE RED LIGHT Red inside traffic light control output traffi...

Страница 23: ... as tamper signal B0 4 6 Status parameters The status parameters indicate the state of the maneuver last errors or control panel versions These parameters are only read parameters and they cannot be modified Num Parameters Factor DPLAY Description 7D Door pos in HALL mode 1000 Shows the door position when HALL mode 7E Door pos in time mode 1000 Shows the door position when time mode 7F Control pan...

Страница 24: ...f the STOP ERROR LED indicator a series of slow and fast flashing are performed An slow flash 1 second ON indicator 0 5 seconds OFF indicator A quick flash 0 3 seconds ON 0 5 seconds OFF The error or warning value can be up to 2 digits To display the value the control panel performs a slow number of flashes to indicate the first digit and a number of quick flashes to show the second digit For exam...

Страница 25: ...nstalled RSENS NC WHEN PROG Control panel programmed without RSENS connected Connect the RSEC card and program the control panel again RSENS NOT FOUND Control panel programmed with RSENS connected and now it is not connected Program the control panel again without RSEC or connect the RSEC again that was programmed to the control panel previously RSENS PROG ERROR RSENS programming error are R and T...

Страница 26: ...tch should be installed to improve the installation with the RSENS system RSENS LOW BATTERY RSENS low battery Verify the batteries of the RSENS transmitter TAMPER Input tamper input has been activated indicating manipulation of the control panel Information failure only for technical service 6 3 Warnings Informative messages from the control panel Error Description Solution FC CL M1 NOT FOUND Clos...

Страница 27: ...ted Verify that the security edge activation was produces by an obstacle ERROR RADIO DESCRYPT Receiving not programmed transmitters from another customer or installer Verify that in the installation there are no emitters of another client installer activated with our control panel ERROR RADIO RTDS The radio signal received is very low Verify the installation and the radio signal S OPTOEDGE CL ON C...

Страница 28: ...ing function is enabled when the maneuver is programmed a single user action is needed After this user action the control panel automatically executes the opening and closing maneuvers During these maneuvers the control panel searches and stores the opened closed point references Finally the control panel exits the programming mode automatically Notes The autoprogramming function can not be enable...

Страница 29: ...ill use Time or Hall signal as a position reference Notes The main maneuver parameters that define its duration are the P33 and P34 configuration parameters in addition to PCB and PCC in M22 model for second motor The opened and closed positions are the starting points and they always take the 0 value P33 parameter configures the opening stop point opening maneuver duration and the P34 parameter c...

Страница 30: ... autoprogramming function is enabled The only difference is that the pushbutton needed to program the pedestrian maneuver is the PEDESTRIAN pushbutton Operating After programming the pedestrian maneuver if a PESESTRIAN pushbutton is pressed the pedestrian maneuver is executed and the door opens the portion of the programmed aperture Notes The pedestrian maneuver parameters that define its duration...

Страница 31: ...e any value from 10 to 100 The smaller the value the slower the normal speed This configuration parameter can be configured by means of VERSUS PROG programming tool To enable slow speed mode it is necessary to set to ON the associated P04 parameter by means of a VERSUS PROG programming tool It is also possible to enable or disable this function by setting the slow speed mode ON OFF function to an ...

Страница 32: ... the slow speed starting closing point PCD and PCE parameters set the slow speed starting opening or closing point for motor 2 To define these points it is necessary to press the START or PEDESTRIAN pushbutton during the programming sequence except if autoprogramming function is enabled For example when programming the opening maneuver the first press starts the maneuver in normal speed and the se...

Страница 33: ...or internal limit switches and blocking detection it is necessary to set to ON the associated P1E parameter by means of a VERSUS PROG programming tool There is also possible to enable disable this function by means of assigning this function to a one of the selector switches P54 to P5C parameters There are also 4 status parameters read only parameters that give information about this function The ...

Страница 34: ... the door in order to search the close internal limit switch After detecting it it automatically starts opening the door until it detects the open internal limit switch and stops Then it will start counting the autoclosing time if not autoprogramming function is enabled With another press the door will close until close internal limit switch is detected again Finally the control panel will exit th...

Страница 35: ...ts value can be checked or modified by using the P41 configuration parameter This parameter can take values from 0 seconds to several minutes The units used for this parameter are seconds Operating If the autoclose function is enabled when the maneuver reaches the opened position it starts a timer When the timer value is equal to the autoclose timeout value the control panel starts closing automat...

Страница 36: ... P49 configuration parameter allows modifying the pause timer that is started after the door reaches the opened position and the security contact is activated This parameter can take values from 0 seconds to several minutes The units used for this parameter are seconds Operating If the close by security contact function is enabled when the security contact is activated during the opening maneuver ...

Страница 37: ... enter to deadman mode if a security is active P5E to P77 parameters allow assigning an input value to every available control panel input Open deadman and Close deadman input values can be assigned to these inputs By using these inputs control panel enters directly to deadman mode Operating There are four ways to enter to the deadman mode 1 Deadman mode enabled by P07 configuration parameter Ever...

Страница 38: ...switch is detected during deadman mode the movement will stop Model All Associated parameters ID Description Type P03 No stop on opening ON OFF Description The no stop on opening function avoids stopping the opening maneuver if an alternative or close pushbutton is pressed Configuration To enable the no stop on opening function it is needed to set to ON the P03 configuration parameter by means of ...

Страница 39: ... on the EXPANSION connector Moreover before proceeding with the control panel programming process it is needed to program the Radioband transmitter to the RSEC R receiver see Radioband transmitter and RSEC R receiver user instructions to learn how to perform this programming process Parameters To enable the Radioband function it is needed to set to ON the P28 configuration parameter by means of a ...

Страница 40: ...ation Radioband security activation is detected control panel executes the security inversion maneuver and displays the Wr10 or Wr11 warning in order to inform user that activation has occurred Wr10 is due to a closing security edge activation and the Wr11 is due to opening security edge activation If Radioband system is used in closing maneuver it is also possible to inhibit the Radioband activat...

Страница 41: ...System set up In order to use Radiosens system on VERSUS control panels an RSEC R receiver must be connected to the control panel on the EXPANSION connector Moreover before proceeding with the control panel programming process it is needed to program the RSENS transmitter to the RSEC R receiver see RSENS transmitter and RSEC R receiver user instructions to learn how to perform this programming pro...

Страница 42: ...ring the first 10 maneuver portions of the closing maneuver Besides being able to set the end zone of inhibition by parameter P53 it is possible to set it without the VERSUS PROG programming tool during programming of the maneuver If the Radiosens system is used when the maneuver is programmed 2 opening closing sequences are performed The first sequence is performed by the user to program the trav...

Страница 43: ...ged and it is needed to pass the new parameter values to the RSENS transmitter Because of this is necessary to synchronize the RSENS transmitter to the RSEC R receiver by programming again the transmitter to the receiver After setting up the hardware configured the parameters and programmed the maneuver sequence the Radiosens system is ready Therefore the programmed RSENS transmitter will be taken...

Страница 44: ...osens system is used Opening inversion maneuvers are not allowed when Radiosens system is used Every closing maneuver must start from the OPENED point and it has to be executed the whole closing maneuver Control panel sequence must be programmed again in case of any mechanical alteration or modification installation maintenance knock on the door etc Even though a mechanical modification or alterat...

Страница 45: ...olock function To enable this function use the PBD configuration parameter There is also possible to control this function by means of assigning this function to one of the selector switches P54 to P5C parameters Operating After electro lock function is enabled the control panel executes the electro lock sequence every time an opening maneuver is started The electro lock time is divided in two par...

Страница 46: ...euver reference points Configuration To enable the backjump function it is needed to set the P0F configuration parameter to ON in case of opening backjump or set the P10 configuration parameter to ON in case of closing backjump by means of a VERSUS PROG programming tool Backjump opening and closing timers are configured by means of the P3C and P3D configuration parameters These parameters can take...

Страница 47: ... autotest function on VERSUS control panels the security contact must be supplied by control panel voltage output Depending on the control panel model this output can be 12Vdc or configurable 12 24Vdc The security contact output it must be connected to the corresponding control panel input Parameters The output that supplies the security contact must be configured as a Autotest signal if the secur...

Страница 48: ...quence steps In the first step the control panel removes the power supply of the security contact by using the configured test output In the second step the control panel checks that the test input has no signal This means that the security contact has released its output In the third step the power supply of the security contact is recovered Finally in the fourth step it checks that the test inpu...

Страница 49: ...ystem set up In order to use security contact autotest function on VERSUS control panels the wired security edge must be supplied by control panel voltage output Depending on the control panel model this output can be 12Vdc or configurable 12 24Vdc Regarding the wired security edge output it must be connected to a control panel Parameters The output that supplies the security edge must be configur...

Страница 50: ...rts These are the autotest sequence steps In the first step the control panel removes the power supply of the security wired edge by using the configured test output In the second step the control panel checks that the test input has no signal This means that the security wired edge has released its output In the third step is recovers the power supply of the security wired edge Finally in the fou...

Страница 51: ...ion parameter This parameter is a position parameter and the units that are used depend on the time or Hall mode configuration If the control panel is working on the time mode seconds are used as units and the inhibition zone can take values from 0 to 180 seconds On the other hand if control panel is working on the Hall mode pulses are used as units and the inhibition zone can take values from 0 t...

Страница 52: ...sequence must be programmed in order to detect the security contact activation activated by the door and this activation defines the security contact position If the security contact is activated during the programming of the closing maneuver P18 configuration status parameter is set to ON The inhibition zone is defined by the sum of the following two parameters The programmed security contact pos...

Страница 53: ...a new control panel programming sequence Model All Associated parameters ID Description Type P5E P60 IN X INPUT P29 P31 PDC PDD Autodetect OptoEdge INX ON OFF Associated errors ID Description Type Wr10 Security edge closing active Warning Wr11 Security edge opening active Warning Wr37 S Optical edge opening active Warning Wr38 S Optical edge closing active Warning Description The security edge aut...

Страница 54: ...he closing maneuver This configuration is done by using P5E to P60 configuration parameters by means of a VERSUS PROG programming tool After the edge is connected and the input is configured the 8K2 or optical mode detection is performed during the normal control panel programming sequence After programming this sequence detection result can be checked by using the P29 to P31 status parameters If ...

Страница 55: ... configuration parameter has to be set to ON If pre flash function needs to be controlled by user without VERSUS PROG programming tools Pre flash ON OFF function can be assigned to any switch To configure the switch values P54 to P5C configuration parameters can be used Pre flash time value can be configured by using the P4D configuration parameter This parameter can take values from 0 to 60 secon...

Страница 56: ...outputs The configured Intrusive outputs will be activated in case of non desired entrance detection Therefore these outputs can be used to activate any kind of alarm system The output is normally opened and it changes to normally closed when it is activated It keeps active until the door is completely closed To use the anti intrusive function a closing security contact input is compulsory as the ...

Страница 57: ...when it is activated It keeps active until the alarm condition is resolved To use the alarm function a closing mechanical limit switch input is compulsory as the mechanical limit switch is used as security sensor Therefore it is needed to configure any of the available inputs as mechanical limit switch input In order to use the closing mechanical limit switch it has to be detected on the control p...

Страница 58: ...used to configure the TL CARD V extra outputs The configured Panic outputs will be activated pulse output in case of transmitter long activation is detected Therefore these outputs can be used to activate any kind of alarm system The output is normally opened and it changes to normally closed when it is activated It keeps active for a short period of time pulse To configure the time that is needed...

Страница 59: ...uring programming sequence process When control panel maneuvers are programmed if user reaches the top and bottom door limits and the hydraulic motor presses for an extratime that is configured by P2D parameter in these points OPEN and CLOSE references are detected Therefore in normal operation these references will be taken into account To check if these references have been detected P1F and P20 ...

Страница 60: ...nel red LED it also flashes to inform the user that it is inhibited in order to detect the OPENED or CLOSED reference Once reached the reference and to ensure proper closing or opening of the door the door continue closing opening for the extra time parameter set by P2D If pressure switch test is enabled and there is no signal activation during the inhibition zone test fails and Er19 error is disp...

Страница 61: ...ing If recharge maneuver is enabled the control panel starts a 1 hour timer every time the door enters to CLOSED or OPENED position After this timer finishes the control panel executes a 3 seconds opening maneuver in case of OPENED position or a 3 seconds closing maneuver in case of CLOSED position This maneuver is executed in order to correctly keep the door closed or opened After these 3 seconds...

Страница 62: ...rd blocking function is enabled configured password value is requested if user wants to modify control panel configuration The password value is requested by VERSUS PROG programming tools when user tries to modify configuration parameters If password is correctly introduced control panel is unblocked and user can change its configuration After 2 minutes of no user activity control panel is blocked...

Страница 63: ...art Open Open inside Start pedestrian or Open pedestrian To perform this the configuration parameters P5E to P60 are used By PB2 configuration parameter can be chosen the traffic control mode Depending on how the mode is configured the traffic lights are activated or deactivated in certain states of the door in a different way Operating JCM traffic control mode value 0 In this mode all traffic lig...

Страница 64: ...arning can be checked by means of the P9B status configuration parameter Operating By default control panel reports a limited list of errors These errors are those that are critical or those that inform about a security malfunction If user wants to expand the error information in order to see normal errors or warnings error and warning function has to be enabled If no VERSUS PROG programming tool ...

Страница 65: ...a magnetic loop vehicle detection connected to this input Configuration To enable this function it is needed to assign the activation to one of the switches by means of the P54 P5C configuration parameters Once the function assigned to the switch it can be activated setting at ON the switch Operating If the function is enabled if you receive an order to open when the door is closed the door will n...

Страница 66: ... must assign the role of maintenance warning to one of the outputs of the control panel This assignment is done by configuration parameters P78 P7C if using a control panel output or by output configuration parameters PA1 PB0 when using a TL CARD V output The maximum number of operations is fixed by setting numerical parameter P32 Operating If the maintenance warning function is activated the cont...

Страница 67: ...one if OFF closing is done There are 2 types of outputs fire information flash and activation The first performs the normal function of flash but in the case that the fire signal is active remains in flash until the signal turns off The second simply follows the input fire signal and it is activated during automatic opening closing To open the door with the fire signal active it is necessary to co...

Страница 68: ...0 TAMPER activations counter NUMERIC Description TAMPER function allows the installer to configure an output of the control panel in order to inform on the box tampering This output can be used to control an alarm warning siren etc You can also control the number of manipulations by a counter that can be accessed and reset by VERSUS PROG Configuration To enable this function you must assign a TAMP...

Страница 69: ...oning Before performing a program the door should be fully in closed position 8 2 Door positioning in Dead man mode Press the PROG button to enter Programming mode The PROG Led will turn on Through the buttons OPEN and CLOSE if there are available you can position the door to the totally closed position ...

Страница 70: ...rammed transmitter to program the maneuver 5 The door opens 6 Press START pushbutton to stop the door at the desired positon 7 The door stops 8 The door closes automatically 9 Press START pushbutton to stop the door at the desired positon 10 The door stops 11 The PROG Led turns off 12 The programming is finished The control panel is programmed with the following fixed parameters slow speed manoeuv...

Страница 71: ...ll turn on 4 Press START pushbutton or a programmed transmitter to program the maneuver 5 The door opens two seconds and stops 6 The door closes automatically until the closed position 7 The door stops 8 The door opens automatically until a mechanical stop or a limit switch is reached 9 The door stops 10 The door closes automatically until a mechanical stop or a limit switch is reached 11 The door...

Страница 72: ...d will turn on 4 Press START pushbutton or a programmed transmitter to program the maneuver 5 The door opens 6 Press START pushbutton to stop the door at the desired position 7 The door stops 8 Wait to program the desired autoclose time 9 Press START pushbutton to close the door 10 The door closes 11 Press START pushbutton to stop the door at the desired position 12 The door stops 13 The PROG Led ...

Страница 73: ... programming mode 3 The PROG Led will turn on 4 Press START pushbutton or a programmed transmitter to program the maneuver 5 The door opens two seconds and stops 6 The door closes automatically until the closed position 7 The door stops 8 The door opens automatically until a mechanical stop or a limit switch is reached 9 The door stops 10 Wait to program the desired autoclose time 11 Press START p...

Страница 74: ...ed transmitter to program the maneuver 5 The door opens 6 Press START pushbutton at the desired position to move the door at slow speed 7 The door finishes opening at slow speed 8 Press START pushbutton to stop the door at the desired position 9 The door stops 10 Wait to program the desired autoclose time 11 Press START pushbutton to close the door 12 The door closes 13 Press START pushbutton at t...

Страница 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13 ...

Страница 76: ... Led will turn on 4 Press PEDESTRIAN button instead of START pushbutton to program the maneuver 5 The door opens 6 Press PEDESTRIAN button to stop the door at the desired positon 7 The door stops 8 Wait to program the desired autoclose time 9 Press PEDESTRIAN button to close the door 10 The door closes 11 Press PEDESTRIAN button to stop the door at the desired positon 12 The door stops 13 The PROG...

Страница 77: ...7 The door 2 opens 8 Press START pushbutton 9 The door 1 opens at slow speed 10 Press START pushbutton 11 The door 2 opens at slow speed 12 Press START pushbutton 13 The door 1 stops 14 Press START pushbutton 15 The door 2 stops 16 Wait to program the desired autoclose time 17 Press START pushbutton 18 The door 2 closes 19 Press START pushbutton 20 The door 1 closes 21 Press START pushbutton 22 Th...

Страница 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13 ...

Страница 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13 ...

Страница 80: ...y pressing the first two buttons of a transmitter depending on the programming mode the equipment will exit programming mode issuing two 1 sec acoustic signals If on programming a transmitter the equipment memory is full it will issue seven 0 5 sec acoustic signals and exit programming N B Each transmitter channel can be configured independently on the equipment occupying only one memory position ...

Страница 81: ...onds without programming or by quickly pressing the programming button or pressing the first two transmitter buttons the equipment will exit programming mode issuing two 1 sec acoustic signals 9 3 Reset In programming mode the programming button is held down for over 10 sec The equipment will issue 10 short acoustic warning signals followed by others at a faster pace to indicate that the operation...

Страница 82: ...er 20 seconds of inactivity The programmer has an automatic cut off function after 3 minutes to save battery Configuration cables for the new generation control panels are supplied VERSUS 2 TECHNICAL SPECIFICATIONS Frequency 868 35MHz 13 56MHz Power Supply 2x1 5 AA alkaline batteries batteries Rechargable through MINI USB Standby consumption 0 75mW Via cable via proximity operating consumption 300...

Страница 83: ...ue is placed on the centre and the configuration options are at the bottom Using the lateral movement arrow keys and vertical movement arrow keys slider you can navigate through the settings To confirm a setting press the key Intro After changing any parameter from the control panel a complete programming manoeuvre must be performed 4 1 2 READ CONF FROM C PANEL Allows reading and saving different ...

Страница 84: ...ppearance parameters LCD contrast vibration sound slider active slider sensitivity and battery type 4 3 3 BATTERY TYPE Allows choosing if the programmer batteries are re chargeable or not When a charge of the rechargeable batteries is required the programmer recharges the batteries slowly If you want to load them quickly remove the batteries and recharge them with an external charger Attention Do ...

Страница 85: ...st be without power supply Note In case of installation with the box upside turn up the card and then the frontal buttons will be reconfigured to the new position of the control panel OPERATING Modify the values of the potenciometers always with the door stopped Notes The values depend on the control panel and only will be taken into account when the door is opened stopped or closed The card keeps...

Страница 86: ... to the new position of the control panel OPERATING 1 STANDBY MODE 2 DOOR STATE INDICATION MODE DOOR OPENED DOOR CLOSED DOOR OPENING DOOR CLOSING ERROR ERROR NUMBER When the door is in movement the control panel indicates the state of the door opened closed or moving You also can access to visualize the state of the door pressing any of the buttons of the display card during 2 seconds The display ...

Страница 87: ... control panel The numeric parameters have a scale factor according to the maximum number that they can adopt See the section 5 of the GAMMA VERSUS MANUAL for finding this scale factor named as DPLAY factor Being in Door state indication mode press the MODE button during 5 seconds PR will appear on the display indicating that the control panel has entered programming mode Once finished the program...

Страница 88: ...be introduced to access 3 and 4 modes Programming and Parameter Configuration modes respectively For example if the password is 1234 follow the steps below PRESS TP ENTER VALUE 12 PRESS TO ENTER VALUE 34 P1 APPEARS ON THE SCREEN PRESS MODE TO VALIDATE VALUE 12 P2 APPEARS ON THE SCREEN PRESS MODE TO VALIDATE VALUE 34 IF PASSWORD ERROR AN ERROR APPEARS ...

Страница 89: ...guaranteed for directly activating equipment other than that specified The manufacturer reserves the right to change the specification of the equipment without prior warning IMPORTANT ANNEX Disconnect the power supply whenever you proceed to the installation or repair of the control panel In accordance with the European low voltage directive you are informed of the following requirements For perma...

Страница 90: ...e of the espanding card TL CARD V The configuration of the card will depend on function assignation done from control panel Select trough the switch the desired address for the plugged card SWITCH SELECTOR Switch 1 Switch 2 Outputs address 1x1 1x2 1x3 1x4 OFF OFF 101 102 103 104 OFF ON 111 112 113 114 ON OFF 121 122 123 124 OFF OFF 131 132 133 134 Notes The functions of each output of the TL CARD ...

Страница 91: ...nel is power supplied the V LCD is on standby mode and the following message will appear on the screen of the V LCD Operating modes Being on standby mode press PROG button to select the operation mode Every time you press PROG button you will pass from one mode to the next The operation modes are detailed below Door status mode The first line indicates the status of the door CLOSED OPENING OPENED ...

Страница 92: ... PRESS START BUTTON PRESS PLUS MINUS 2s PRESS BUTTON KEPT PRESS PLUS PROG TO PRESS BUTTON KEPT PRESS MINUS PROG TO TO OPEN DOOR STORE OPENING POSITION TO CLOSE DOOR STORE CLOSING POSITION Example 2 Programming sequence without absolute encoder BEING ON STANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PLUS MINUS 2s PRESS START BUTTON PRESS START BUTTON PRESS START BUTTON PRESS START BUTTON DO...

Страница 93: ...TANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PLUS MINUS 2s TO PRESS MINUS BUTTON TO PRESS PROG BUTTON TO WAIT ENTER MENU GO DOWN THE MENU SELECT THE OPTION PRESS PROG BUTTON PRESS MINUS BUTTON TO PRESS PROG BUTTON TO GO DOWN THE MENU SELECT THE DESIRED OPTION Example 2 EDIT NUMERICALS BEING ON STANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON ...

Страница 94: ...TER MENU GO DOWN THE MENU SELECT THE OPTION PRESS PROG BUTTON PRESS PLUS BUTTON TO PRESS MINUS BUTTON TO PRESS PROG BUTTON TO SELECT A DIGIT POSITION CHANGE THE NUMBER VALIDATE Diagnostics mode It allows checking all the parameters of the control panel Example BEING ON STANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON ...

Страница 95: ...TO SEE THE FUNCTION THAT HAS THIS OUTPUT Language config mode It allows changing the language of the V LCD There are three available languages in each control panel different languages depending on the customization Example BEING ON STANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS MINUS BUTTON TO PRESS PLUS MINUS TO GO DOWN THE MENU SELEC...

Страница 96: ...EING ON STANDBY MODE PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PROG BUTTON PRESS PLUS MINUS 2s TO ENTER MENU PRESS PLUS BUTTON TO PRESS PROG BUTTON TO PRESS MINUS BUTTON TO PRESS PLUS BUTTON TO CHANGE LINE 2 SELECT THE LETTER CHANGE THE LETTER CHANGE POSITION PRESS PROG BUTTON TO VALIDATE ...

Страница 97: ...DIOSENS system is designed for Fast doors and Flat slat rolling shutters in an Industrial Commercial or Residential environment RADIOSENS is an impact detection system installed at the principal edge of the door It works detecting any obstacle before the strength exceeds regulations limits and then inverting door movement RADIOSENS is a wireless system based on an RF transmitter and a receiver car...

Страница 98: ... and RB3 systems are not compatible so it cannot be stored in the same receiver In addition a transmitter may be memorized only in one receiver Memorizing RS3 Receiver only keeps a RS3 transmitter in memory at the same time This is stored always as security on closing PRESS RPROG PUSHBUTTON LED TURNS ON PRESS TRANSMITTER PROG ONE BEEP AND PROGRAMMED PRESS RPROG PUSHBUTTON LED TURNS OFF AND END PRO...

Страница 99: ...mitter perform the programming of the control panel with the security element memorized See programming section on control panel user s manual Note If you change the position of transmitter RS3 you must perform the system programming again otherwise RS3 will indicate a safety error and the door will not work properly Maintenance Table of message error indication beeps and leds LEDs perform a flash...

Страница 100: ... the D green led indicates a coverage failure too Perform another system check until the result is correct Press the safety edges Nº flashes check led Signal coverage Result of check Solution Three consecutive beeps are heard 1 Very weak Safety edge failure Change the orientation of the transmitting receiving aerials or install an AED 868 or FLAT 868 outdoor aerial to ensure the desired range 2 We...

Страница 101: ...tly connected equipments an easy access connection device must be provided This system must only be installed by qualified persons with experience in automatic doors gates installations and with knowledge of the applicable EU standards The instructions for use of this equipment must always remain in the possession of the user System s work frequency does not interfere with the 868 MHz remote contr...

Страница 102: ...en select on the Device Selection option the device that you want to update the firmware If it is a receiver of 500 codes an access control unit or the Prog man portable programmer you should insert the updating memory card in the Updator for the firmware to be downloaded to the card 3 Press the Connect to Updator and if the connection is correct at the bottom of the window you will see the serial...

Страница 103: ...ol panel via the RJ45 connector UNPLUG POWER SUPPLY CONNECT UPDATOR PLUG POWER SUPPLY LED S FLASHES WAIT 10S UPGRADING OK UPGRADING VERSUS PROG PORTABLE PROGRAMMER To download the latest version of firmware on a handheld programmer connect the Versus Prog through a USB cable Type A Mini B to your PC and follow the prompts 1 Run the software Firmware update tool from the PC 2 On the main screen sel...

Страница 104: ...n Download file to download the chosen file to the device Updator Wait until you finish the download process the state is indicated by the bar Download Status After the process in the bottom of the window Download OK is indicated UPGRADING V LCD ACCESSORY To update the firmware of the V LCD accessory with the version loaded on the Updator the V LCD must be connected to the control panel Connect Up...

Страница 105: ...M accessory with the version loaded on the Updator the V GSM must be connected to the control panel Connect Updator through an Ethernet cable to the control panel via the RJ45 connector UNPLUG POWER SUPPLY CONNECT UPDATOR PRESS THE V GSM RIGHT BUTTON PLUG POWER SUPPLY FLASHES DURING UPGRADING END UPGRADING LEDS OFF PROCESS ...

Страница 106: ...y edge this must never be activated when the door is fully closed It is wise to install the ends of run before activating the edge This equipment can only be handled by a specialist fitter by maintenance staff or by a suitably trained operator To connect the power supply and motor wiring 2 5 mm2 section terminals must be used Use protective goggles when handling the equipment Fuses must only be ha...

Страница 107: ...en or closed Precaution when operating the manual unlocking device as the door may suddenly fall due to the bad condition of the springs or door unbalance Details on how to use the manual unlocking device must be provided by the manufacturer or the device installer Examine the installation frequently especially the cables springs and supports to detect signs of wear damage or unbalance Do not use ...

Страница 108: ...GAMMA VERSUS MANUAL 108 COD 1257066 Gamma VERSUS Manual v1 13 13 SAFETY INSTRUCTIONS FOR MAINTENANCE ...

Страница 109: ...e related symbology that is used in this manual Connections Normally closed contact Normally open contact 8k2 resistive safety edge Optical safety edge 8k2 Optical safety edge Light Single phase motor connection Three phase motor connection Drawings Courtesy light Flash Motor Stop pushbutton Pedestrian pushbutton ...

Страница 110: ...a VERSUS Manual v1 13 Parachute Electrolock Transmitter photocell Receiver photocell Opening safety edge Closing safety edge Autoclosing time Lock Unlock Writen indication Led turned on One beep One beep long Several beeps Screw units metric ...

Страница 111: ...GAMMA VERSUS MANUAL 111 COD 1257066 Gamma VERSUS Manual v1 13 Movement arrows Slow movement arrow Pedestrian entry Vehicle entry Industrial entry ...

Отзывы: