![Jay electronique Orion Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/jay-electronique/orion/orion_installation-and-user-technical-manual_635751074.webp)
- 74 -
Orion
- 324501G
FR
DE
EN
6.3.1- Relays : control limitation
he maximum number of relays activated at the same time is
limited to :
Rail DIN
(
ORRD
)
Industrial
(small model)
(
ORRS
)
Industrial
(large model)
(
ORRA
)
he maximum
number of relays
activated at the
same time is
limited to
3 relays :
3 function relays
or
2 function relays
+ 1 RM relay
4 relays :
4 function relays
or
3 function relays
+ 1 RM relay
9 relays :
9 rfunction relays
or
8 function relays
+ 1 RM relay
All commands exceeding the maximum number of relays
which can be activated simultaneously will be ignored.
6.3.2- Relays : technical characteristics
«
RM
» relay and
function
relays :
Contacts
AgNi 0,15
Maximum power at cosphi=1
2000 VA
Maximum current switching
8 A
Maximum voltage switching
400 VAC
Minimum current / voltage advised switching
100 mA / 12 VDC
Switching cycles at 250 VAC, 8 A, cosphi=1
100 000
Switching cycles at 24 VDC, 8 A
50 000
Tests per EN 60947-5-1
DC13 at 0,5 A / 24 VDC
AC15 at 3 A / 250VAC
Number of switching cycles on various contactors :
Contactor
Physical unit switched by relay
Number of switching cycles
(for «RM» relay and function «relays»)
CA2DN
LC1D09
LC1D18
LC2D09
Switching at 230VAC (70VA,cosphi=0,75)
2 x 10
6
Switching at 110VAC, (70VA,cosphi=0,75)
1 x 10
6
Switching at 48VAC (70VA,cosphi=0,75)
0,5 x 10
6
(s
Содержание Orion
Страница 2: ... 2 Orion 324501G ...
Страница 30: ... 30 Orion 324501G FR DE EN ...
Страница 56: ... 56 Orion 324501G ...
Страница 84: ... 84 Orion 324501G FR DE EN ...
Страница 110: ... 110 Orion 324501G ...
Страница 138: ... 138 Orion 324501G FR DE EN ...
Страница 164: ... 164 Orion 324501G ...
Страница 165: ... 165 Orion 324501G Annexes Appendix Anhang ...