12
8
8
JÄSPI Inverter Nordic
3 x 400 V
3 x 400 V
1 x 230 V
Voltage
Output data according to EN 14 511, partial load
1
7.35 / 2.43 / 3.02
5.17 / 1.72 / 3.00
5.17 / 1.72 / 3.00
-7 / 35 °C
Heating
Capacity / power input / COP (kW/kW/-) at nominal flow
Outdoor temp: / Supply temp.
5.21 / 1.22 / 4.27
4.03 / 0.91 / 4.43
4.03 / 0.91 / 4.43
2 / 35 °C
5.27 / 1.49 / 3.54
4.07 / 1.16 / 3.51
4.07 / 1.16 / 3.51
2 / 45 °C
3.54 / 0.69 / 5.12
3.57 / 0.78 / 4.57
3.57 / 0.78 / 4.57
7 / 35 °C
3.64 / 0.91 / 4.00
3.66 / 0.98 / 3.74
3.66 / 0.98 / 3.74
7 / 45 °C
4.69 / 1.70 / 2.76
3.80 / 1.28 / 2.97
3.80 / 1.28 / 2.97
35 / 7 °C
Cooling
Capacity / power input / EER (kW/kW/-) at maximum flow
Outdoor temp: / Supply temp.
5.44 / 1.73 / 3.15
5.10 / 1.37 / 3.73
5.10 / 1.37 / 3.73
35 / 18 °C
SCOP according to EN 14825
8.00 / 4.83
5.90 / 4.80
5.90 / 4.80
kW
Nominal heat output (P
designh
) average climate 35 °C / 55 °C (Europe)
8.30 / 3.78
6.30 / 3.75
6.30 / 3.75
kW
Nominal heat output (P
designh
) cold climate 35 °C / 55 °C
9.30 / 4.05
6.80 / 4.03
6.80 / 4.03
kW
Nominal heat output (P
designh
) warm climate 35 °C / 55 °C
9.80 / 3.33
7.40 / 3.33
7.40 / 3.33
SCOP average climate, 35 °C / 55 °C (Europe)
9.20 / 5.48
5.90 / 5.43
5.90 / 5.43
SCOP cold climate, 35 °C / 55 °C
9.20 / 4.48
6.30 / 4.35
6.30 / 4.35
SCOP warm climate, 35 °C / 55 °C
Energy rating, average climate
2
A+++ / A+++
The product’s room heating efficiency class 35 °C / 55 °C
3
A+++ / A+++
The system’s room heating efficiency class 35 °C / 55 °C
4
Electrical data
400 V 3N ~ 50 Hz
400 V 3N ~ 50 Hz
230 V ~ 50 Hz
Rated voltage
7
6
14
A
rms
Max operating current, heat pump
6
5
13
A
rms
Max operating current, compressor
45
40
40
W
Max. power, fan
10
10
16
A
rms
Fuse
IP24
Enclosure class
Refrigerant circuit
R410A
Type of refrigerant
2,088
GWP refrigerant
2.6
2.4
2.4
kg
Volume
Scroll
Type of compressor
5.43
5.01
5.01
t
CO
2
-equivalent (The cooling circuit is hermetically sealed.)
4.5
MPa
Cut-out value pressure switch HP (BP1)
0.7
MPa
Difference pressostat HP
0.12
MPa
Cut-out value pressure switch LP (BP2)
0.7
MPa
Difference pressostat LP
Airflow
3,400
2,400
2,400
m
3
/h
Max airflow
Working area
-25 / 38
°C
Min./max. air temperature, heating
15 / 43
°C
Min./max. air temperature, cooling
Reverse cycle
Defrosting system
Heating medium circuit
0.45 (4.5)
MPa
Max system pressure heating medium
-
MPa
Cut-off pressure, heating medium
0.11 – 0.44
0.08 – 0.32
0.08 – 0.32
l/s
Recommended flow interval, heating operation
0.35
0.27
0.27
l/s
Min. design flow, defrosting (100% pump speed)
26 / 65
°C
Min./max. HM temp, continuous operation
G1 1/4” external thread
Connection heating medium JÄSPI Inverter Nordic
G1” external thread
G1” external thread
G1” external thread
Connection heating medium flex pipe
25 (28)
20 (22)
20 (22)
DN (mm)
Min. recommended pipe dimension (system)
Dimensions and weight
1,280
1,130
1,130
mm
Width
612
610
610
mm
Depth
1,165
1,070
1,070
mm
Height
180
170
153
kg
Weight
Miscellaneous
47
Chapter 11 |
Technical data
JÄSPI Inverter Nordic