Control conditions
Control conditions defrosting
■
If the temperature of the evaporator sensor (BT16) is
below the start temperature for the defrosting func-
tion, JÄSPI Inverter Nordic counts the time to "active
defrosting" for each minute that the compressor is
running, to create a defrosting requirement.
■
Time until "active defrosting" is shown in minutes on
the indoor module / control module. Defrosting starts
when this value is 0 minutes.
■
"Passive defrosting" is started, if the compressor require-
ment has been fulfilled, at the same time as there is a
defrosting requirement and the outdoor temperature
(BT28)is greater than 4 °C.
■
Defrosting occurs actively (with compressor on and
fan off) or passively (with compressor off and fan on).
■
If the evaporator is too cold, a "safety defrost" starts.
This defrosting can start earlier than the normal de-
frosting. If the safety defrosting occurs ten times in a
row, the evaporator (EP1) on JÄSPI Inverter Nordic
must be checked, which is indicated by an alarm.
■
If "de-icing fan" is activated in the indoor module/con-
trol module, "de-icing fan" starts at the next "active
defrosting". "De-icing fan" removes the build-up of ice
on the fan blades and the front fan grille.
Active defrosting:
1. The four way valve shifts to defrosting.
2. The fan stops and the compressor continues to run.
3. When defrosting is complete, the four-way valve
switches back to heating operation. The compressor
speed is locked for a short period.
4. The ambient temperature is locked and the high re-
turn temperature alarm is blocked for two minutes
after defrosting.
Passive defrosting:
1. If there is no compressor demand, passive defrosting
can start.
2. The four-way valve does not shift.
3. Fan runs at high speed.
4. If there is a compressor demand, passive defrosting
stops and the compressor starts.
5. When passive defrosting is complete, the fan stops.
6. The ambient temperature is locked and the high re-
turn temperature alarm is blocked for two minutes
after defrosting.
There are several possible reasons for an active
defrosting to end:
■
If the temperature of the evaporator sensor has
reached its stop value (normal stop).
■
When defrosting has gone on for longer than 15
minutes. This may be due to too little energy in the
heat source, too strong a wind effect on the evaporator
and/or that the sensor on the evaporator is not correct
and therefore displays too low a temperature (at cold
outdoor air).
■
When the temperature on the return line sensor, BT3,
falls below 10 °C.
■
If the temperature of the evaporator (BP8) falls below
its lowest permitted value. After failing to defrost ten
times, JÄSPI Inverter Nordic must be checked. This is
indicated by an alarm.