www.janitza.de
UMG 604-PRO
72
Address
Designation
Setting range
Unit
Default
100
Collect TFTP configuration file
automatically
0 = deactivated
x = file number
0 to 9999
-
0
101
TFTP error handling
0 = in the event of an error, the
configuration menu is shown on
the display.
1 = TFTP error handling in the
device is deactivated
0 to 1
-
0
110
Current transformer switch
(L1 to L3)
0 = three current transformers
1 = two current transformers
(Aron circuit)
0 to 1
-
0
111
Voltage measurement network
configuration
0 = three-phase 4-conductor
system (TT, TN network)
1 = three-phase 3-conductor
system (IT network)
0 to 1
-
0
112
Deletes all active energy counters,
apparent energy counters and S0
counters (1 = delete)
0 to 1
-
0
113
Deletes all reactive energy
counters (1 = delete)
0 to 1
-
0
114
Resets all min. and max. values
(1 = reset)
0 to 1
-
0
Table Parameter list for measurement settings