11. 10 PTP configuration
The device supports the
Precision Time Protocol
(
PTP
) in accordance with the Standard An-
nex J IEEE 1588-2008
PTP Default Profile
.
The PTP protocol is executed in a logical area known as the domain. The time specified by the
protocol in one domain is independent of the times in other domains.
The PTP protocol enables precise time synchronization in the network from the time server
(master) to the clients (slaves). The prerequisite for this is the PTP capability of the client. The
reference time for the system is determined by what is known as the Grandmaster Clock (see
section "Example: PTP timing according to IEEE 1588-2008 and clock types")
Time synchronization in a network is achieved by the exchange of PTP time control messages.
Clients use the time control information in the PTP messages to set their time to that of the time
server (master) in their part of the hierarchy.
While NTP uses the client-server model – each client must be configured with a name or the IP
address – the system configures itself according to the default PTP profile.
For the
Device
(as of firmware version 5.017), activate PTP (or NTP):
·In the GridVis software (device configuration).
·Via the parameter
_MODE_NTP (
the Modbus address can be found in the Modbus address
list of your device at www.janitza.de)
.
11.10.1 Important Modbus parameters for the PTP configuration of the device
Modbus parameters have the following meaning:
Parameter name
Data type
Permission
Entry (range)
_MODE_NTP
(cf. section 1.1.2 “PTP parameters”
_MODE_
NTP
)
int
RD/WR
NTP/PTP activation
_PTP_DOMAIN
1)
byte
RD/WR
Default = 0 (0 - 127)
_PTP_ANNOUNCE_RECEIPT_TIMEOUT
2)
byte
RD/WR
Default = 3 (2 - 10)
_PTP_MANAGEMENT_INTERFACE
3)
short
RD/WR
Default = 0 (0 - 1)
1. Domain number (default domain = 0). A PTP domain is a range of PTP clocks (devices) which synchronize
themselves with each other using the PTP protocol.
2. Selects the PTP Announce Receipt Timeout. This parameter specifies the number of intervals that are
allowed to elapse without receipt of an announce message (default = 3).
3. 0 (default) – Device supports PTP configuration via the Modbus.
1 - Alternative method of configuration (enables a comprehensive configuration via the interface).
11.10.2 PTP parameter _MODE_NTP
In this context, the entries have the following functions:
Parameter _MODE_NTP
Entry Description
TIME_PROTOCOL_NONE
= 0
No time protocol is active. Manual time configuration.
TIME_PROTOCOL_NTP_BROADCAST
= 1
NTP mode “Listen”, PTP deactivated.
TIME_PROTOCOL_NTP_ACTIVE
= 2
NTP mode “Active”, PTP deactivated.
TIME_PROTOCOL_PTP
= 3
PTP mode is activated, NTP deactivated.
Содержание UMG 604-PRO
Страница 7: ...www janitza de UMG 604 PRO 2...
Страница 19: ...www janitza de UMG 604 PRO 14...
Страница 33: ...www janitza de UMG 604 PRO 28...
Страница 37: ...www janitza de UMG 604 PRO 32...
Страница 51: ...www janitza de UMG 604 PRO 46...
Страница 55: ...www janitza de UMG 604 PRO 50...
Страница 65: ...www janitza de UMG 604 PRO 60...
Страница 75: ...www janitza de UMG 604 PRO 70...
Страница 81: ...www janitza de UMG 604 PRO 76...
Страница 85: ...www janitza de UMG 604 PRO 80...