UMG 604-PRO
www.janitza.de
29
8.
Digital inputs and outputs
8. 1
Digital inputs
The device has 2 digital inputs to which you
can connect one signal generator each.
An input signal is detected on a digital input if
a voltage of at least 10 V and maximum 28 V
DC is applied.
The flowing current is at least 1 mA
and a maximum of 6 mA.
Pay attention to the supply voltage's polarity!
c
c
CAUTION!
Transmission errors and
damage to property due to
electrical faults
If the line is longer than 30 m, there is
an increased probability of transmission
errors and damage to the device due to
atmospheric discharge.
Use a shielded cable for connection to
the digital inputs.
c
c
CAUTION!
Damage to property due
to connection errors
Ensure that the supply voltage:
• is DC voltage.
• has the right polarity.
• is not above the maximum permissible
voltage.
+
-
24V
DC
Fig. Connection example of digital inputs.
Fig. Example for the connection of external switch
contacts S1 and S2 to digital inputs 1 and 2.
+
-
S2
S1
24V
=
UMG 604-PRO
Digital inputs 1-2
4.4k
19
Digital
Input 1
3.9V
3.9V
20
21
Digital
Input 2
4.4k
Содержание UMG 604-PRO
Страница 7: ...www janitza de UMG 604 PRO 2...
Страница 19: ...www janitza de UMG 604 PRO 14...
Страница 33: ...www janitza de UMG 604 PRO 28...
Страница 37: ...www janitza de UMG 604 PRO 32...
Страница 51: ...www janitza de UMG 604 PRO 46...
Страница 55: ...www janitza de UMG 604 PRO 50...
Страница 65: ...www janitza de UMG 604 PRO 60...
Страница 75: ...www janitza de UMG 604 PRO 70...
Страница 81: ...www janitza de UMG 604 PRO 76...
Страница 85: ...www janitza de UMG 604 PRO 80...