UMG 604-PRO
www.janitza.de
31
8. 3
Digital outputs
The device has 2 transistor switching outputs
that are galvanically separated from the
analysis electronics using opto couplers.
The digital outputs:
• can switch DC or AC loads.
• can switch loads depending on the supply
voltage's polarity.
c
c
CAUTION!
Transmission errors and
damage to property due to
electrical faults
If the line is longer than 30 m, there is
an increased probability of transmission
errors and damage to the device due to
atmospheric discharge.
Use a shielded cable for connection to
the digital outputs.
24V
DC
+
-
Fig. Connection example of digital outputs.
Fig. Connection of a DC voltage relay to the digital
outputs.
16
17
Digital
Output 1
UMG 604-PRO
Digital outputs
K2
K1
+
-
24V
DC
18
Digital
Output 2
Fig. Connection of an AC voltage relay to the digital
outputs.
16
17
Digital
Output 1
UMG 604-PRO
Digital outputs
K2
K1
~
24V
AC
18
Digital
Output 2
~
c
c
CAUTION!
Damage to property due
to connection errors
The digital outputs are not short-circuit
proof! Connection errors can therefore
cause damage to the connections.
Ensure that the wiring is correct when
connecting the outputs.
m
m
CAUTION!
Measurement errors when
using as a pulse output
When using the digital outputs as pulse
outputs, measurement errors may arise due
to the residual ripple.
Therefore, use a mains adapter for the
supply voltage for the digital inputs and
outputs, which has a residual ripple of
less than 5% of the supply voltage.
Содержание UMG 604-PRO
Страница 7: ...www janitza de UMG 604 PRO 2...
Страница 19: ...www janitza de UMG 604 PRO 14...
Страница 33: ...www janitza de UMG 604 PRO 28...
Страница 37: ...www janitza de UMG 604 PRO 32...
Страница 51: ...www janitza de UMG 604 PRO 46...
Страница 55: ...www janitza de UMG 604 PRO 50...
Страница 65: ...www janitza de UMG 604 PRO 60...
Страница 75: ...www janitza de UMG 604 PRO 70...
Страница 81: ...www janitza de UMG 604 PRO 76...
Страница 85: ...www janitza de UMG 604 PRO 80...