Page 19
= Peak value
= Minimum value
= Supply
Usage as switching output
If a measured value, but not energy, is assigned to the outputs K1 or
K2, the output energys as a switching output. The following values
for programming are at your disposal:
Limit
Decimal point
Measured value
Sign
Exceeding / underscoring
Mean value
Phase
The selected measured value is compared to the set limit. If this limit
is exceeded or underscored, depending on your programming, the
corresponding output switches.
In order to avoid a too frequent switching, a minimum connection
time of one second is fixely programmed.
Programming as switching output
In programming mode, scroll to output
K1
or
K2
by pressing key 2.
Confirm selection with key 1.
The first cipher of the selected limit flashes.
Scroll to the next symbol or value with key 1. Flashing symbols or
values can be changed using key 2.
If the symbol
PRG
is flashing, a selection of the phases can be
carried out.
If the complete number is flashing, the decimal point can be moved.
If the flashing symbols for the sign and mean value are longer on
than off, they are selected and remain on after proceeding with key 1.
If no symbol is flashing anymore, you can change over to the next
menu by using key 2.
Diagr. Switching output with external relay in
minus.
PRG
A
L1
L2
L3
K1
Attention!
The programmed values for the outputs can only
partially be checked, if they are plausible.
PRG
A
L1
L2
L3
K1
Exceeding
Limit
Phase = L1
Measured value = Current
Switching output no. = K1,
Switching output, condition = On
Diagr. Switching output with external relay in
plus..
m
11
12
30V
10210290
+24V
11
12
30V
10210140
+24V