Issue: 01.02.2016
Page 4
Specifications
Capacity data
Model
4°C
6°C
8°C
10°C
12°C
12.7°C
14°C
16°C
JCC2 25E
2.70
2.74
2.78
2.82
2.86
2.87
2.90
2.94
JCC2 40E
3.78
3.90
4.02
4.14
4.27
4.31
4.40
4.53
JCC2 50E
4.19
4.32
4.45
4.59
4.73
4.78
4.87
5.02
JCC2 60E
5.29
5.41
5.53
5.65
5.77
5.82
5.90
6.03
Cooling capacities in kW at 32°C ambient temperature
* Room temperature of +4
°
C is only available with pipe lengths of less than 15 metres
System data
Liquid
Suction
Length
Rise
m³/h
m
dB(A)
JCC2 25E
2560
8
48
J5LC15C
1631
n/a
29
JCC2 40E
2270
8
48
J5LC20C
2208
n/a
29
JCC2 50E
2680
8
47
J5LC25C
2480
n/a
32
JCC2 60E
2560
8
47
J5LC28C
2463
n/a
34
4) Indoor unit air throw distance is 8 metres based on final air velocity of 0.4m/s.
Notes:
1) Db(A) Noise levels are sound pressure levels @ 10m free field
2) Cooling capacities are nominal duties @ 12.7°C db / 10°C wb & 32°C ambient
3) The pipe length must include the rise - the rise is not additional to the length
5.82
3/8"
5/8"
25m
8m
4.78
1/4"
5/8"
25m
8m
4.31
1/4"
1/2"
25m
8m
Noise
Levels
2.87
1/4"
1/2"
25m
5m
Indoor
Airthrow
Unit Model
Cooling
Capacity
Kw
System Pipe Sizes
Maximum Pipe Run
Unit
Airflows
Important
For applications where the system pipe run
exceeds 15m
up to the maximum of 25m, the following guidelines must be followed:
A condenser fan speed controller (not supplied as standard) should be fitted. See page 23 for details.
The maximum indoor room temperature is restricted to +6°C.
Содержание JCC2
Страница 1: ...JCC2 CELLAR AND PRODUCT COOLERS ISSUE 01 02 2016 CELLAR COOLER RANGE TECHNICAL MANUAL ...
Страница 17: ...Issue 01 02 2016 Page 17 Drawings Indoor unit dimensions 25E 40E ...
Страница 18: ...Issue 01 02 2016 Page 18 Drawings Indoor unit dimensions 50E 60E ...
Страница 24: ...Issue 01 02 2016 Page 24 Certification ...
Страница 25: ...Issue 01 02 2016 Page 25 THIS PAGE IS LEFT BLANK INTENTIONALLY ...