Issue: 01.02.2016
Page 16
F-Gas Information
From 1/1/2015, a new F-Gas Regulation (EC 517/2014) comes into force replacing the old Regulation (EC 842/2006. This will affect
system labelling, information supplied within documentation and also the way in which thresholds for frequency of leak testing
refrigeration systems are calculated. Please be aware of the following:
The outdoor unit models covered in this Technical Manual contains fluorinated greenhouse gases.
The indoor unit models come from the factory pressurized with OFN (Oxygen Free Nitrogen) only.
The GWP (Global Warming Potential) values of refrigerants which are specified for use in this equipment along with the three
new thresholds for leak testing requirements based on TCO
₂
Eq (Tonnes CO
₂
Equivalent) are as follows:
Refrigerant Charge ‐ kg
5T
50T
500T
Refrigerant
GWP
CO₂Eq
CO₂Eq
CO₂Eq
R410A
2087.5
2.4
23.9
239
Changes to leak testing requirements are as follows:
OLD LEGISLATION
NEW LEGISLATION
LEAK CHECKING FREQUENCY
3‐30 kgs
5‐50 TCO₂Eq
Every 12 months but can be increased to 24 months if
fitted with a fixed leak detection system.
30‐300 kgs
50‐500 TCO₂Eq
Every 6 months but can be increased to 12 months if
fitted with a fixed leak detection system.
300+ kgs
500+ TCO₂Eq
Every 6 months ‐ however automatic leak detection
system is mandatory which requires servicing every 12
months
Please note:
For systems with a charge below 3kg, the changes to the leak checking regime will not apply until 2017. Currently, there is
no requirement for regular leak testing of systems with a total charge below 3kg.
A refrigerant charge label is supplied with each unit manufactured from January 2015. The refrigerant charge for the system must be
entered on the label with indelible ink and must be adhered in the proximity of the product charging port.
①
= Unit refrigerant pre-charge amount
②
= Additional refrigerant charge added at site (if required)
① + ② =
Total system refrigerant charge
Содержание JCC2
Страница 1: ...JCC2 CELLAR AND PRODUCT COOLERS ISSUE 01 02 2016 CELLAR COOLER RANGE TECHNICAL MANUAL ...
Страница 17: ...Issue 01 02 2016 Page 17 Drawings Indoor unit dimensions 25E 40E ...
Страница 18: ...Issue 01 02 2016 Page 18 Drawings Indoor unit dimensions 50E 60E ...
Страница 24: ...Issue 01 02 2016 Page 24 Certification ...
Страница 25: ...Issue 01 02 2016 Page 25 THIS PAGE IS LEFT BLANK INTENTIONALLY ...