C. ROOM THERMOSTAT
Configuration code : FCC.BRE22 / FCC.BRE42
C.1. FACTORY SETTINGS
C1.1. 2-pipe connection
The unit is controlled via the room thermostat. The unit starts as soon as there is a 0-10V control
signal and the set water temperature has been reached.
The unit starts as soon as the room thermostat is on “heat” and / or the water temperature > 28°C.
The unit starts as soon as the room thermostat is on “cool” and / or the water temperature < 18°C.
Speed determined by the room thermostat
C1.2. 4-pipe connection
The unit is controlled via the room thermostat. The unit starts as soon as there is a 0-10V control
signal and the set water temperature has been reached.
The unit starts as soon as the room thermostat is on “heat” and / or the water temperature > 28°C.
The unit starts as soon as the room thermostat is on “cool” and / or the water temperature < 18°C.
Speed determined by the room thermostat
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
N L
15120045
GND
GND
GND
GND
NTC1
V.H.
V.C.
0-10V
0-10V
0-10V +24V
GND 0-10V 24V
GND
24V
GND
24V
+24V
RC
IN/OUT
GND
Tsens 1
CONTROL PANEL
I2C
RS485 A/B
CO2
PC / RF
THERMOSTATE 1
DIPSWITCH
Tsens 2
Tsens 3
Tsens 4
JAGA
1
2
3
4
5
6
7
8
ON
(230V - 50Hz)
[B]
[C]
[D]
MODE
[F]
M
[E]
[J]
[I]
[A]
[G]
[H]
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
N L
15120045
GND
GND
GND
GND
NTC1
V.H.
V.C.
0-10V
0-10V
0-10V +24V
GND 0-10V 24V
GND
24V
GND
24V
+24V
RC
IN/OUT
GND
Tsens 1
CONTROL PANEL
I2C
RS485 A/B
CO2
PC / RF
THERMOSTATE 1
DIPSWITCH
Tsens 2
Tsens 3
Tsens 4
JAGA
1
2
3
4
5
6
7
8
ON
(230V - 50Hz)
[B]
[C]
[D]
MODE
[F]
[E]
[J]
[I]
[A]
[G]
[H]
JRT-100
JRT-100TW
strain relief
strain relief