44
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
N L
15120045
GND
GND
GND
GND
NTC1
V.H.
V.C.
0-10V
0-10V
0-10V +24V
GND 0-10V 24V
GND
24V
GND
24V
+24V
RC
IN/OUT
GND
Tsens 1
CONTROL PANEL
I2C
RS485 A/B
CO2
PC / RF
THERMOSTATE 1
DIPSWITCH
Tsens 2
Tsens 3
Tsens 4
JAGA
1
2
3
4
5
6
7
8
ON
(230V - 50Hz)
[B]
[C]
[D]
MODE
[F]
[I]
[A]
B. 0 - 10V BMS WITH WATER- AND ROOM TEMPERATURE MONITORING
(AUTO-CHANGE-OVER)
Configuration code : FCC.BRC42 / FCC.BRC62 / FCC.BRC64
4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and thermostat head for heating
and cooling
This device is not equipped with dew point control. This must be installed in the most critical place
by the installer! Condensing cooling due to a dew point control malfunction may damage the device
and its surroundings.
The device automatically enters the cooling mode as soon as the water temperature is 2
°
C lower
than the room temperature. If the water temperature is less than 1
°
C lower than the room temperature,
the device will automatically switch to standby.
The unit is in standby. The unit automatically starts a new cycle as soon as the set temperature
has been reached.
The device automatically enters the heating mode as soon as the water temperature is 4
°
C higher
than the room temperature. If the water temperature is less than 1
°
C higher than the room temperatu-
re, the device will automatically switch to standby.
strain relief
Содержание BRIZA 12 - JFCC
Страница 1: ...BRIZA 12 JFCC MANU L...
Страница 2: ...CZ SK DE EN STR 3 STR 16 PG 29 PG 42 2...
Страница 55: ...55 EN BRIZA 12 JFCC MANUAL 2021 01 07 NOTES...