48
–
switch the thermostat off with the “
“ button
–
To go to the menu, press the “M” and “+” buttons simultaneously for 10 sec. until “ ” appears. Adjust
the settings with the “+” or “-“ buttons.
–
scroll through the menu with the “M” button.
MENU
DESCRIPTION
ADJUSTABLE
01
Temp. Offset
-8°C . +8°C (+0,5°C)
04
Maximum temperature
+10 °C . +40°C (+0,5°C)
05
Minimum temperature
+10 °C . +40°C (+0,5°C)
06
Display mode
Room / Set / Room set
07
Frost protection
+10 °C . +20°C (+0,5°C)
11
Dead Band
0°C . +3°C (+0,5°C)
12
Display mode
Room / floor / Room vloer
13
2-pipes/4-pipes select
‘2’: 2-pipe connection / ‘4’: 4-pipe connection
14
(0-10V) select dead band or not
‘0’: With dead band / ‘1’: Without dead band
15
Reboot memory
‘OF’: do not save / ‘LA’: save
16
Mode
Heating / Cooling / Heating + Cooling / Auto select
( 4-pipe only )
17
Fanspeed
80% - 90% - 100% / Auto mode
18
Maximum fan speed
80% . 100%
19
Medium fan speed
45% . 75%
20
Low fan speed
20% . 40%
21
Factory reset
rE
After selecting “rE”, press the ““ button to go to the
startup window. Recovery was successful.
10dA
Software version
10dA - Version 21
Parameter settings
Содержание BRIZA 12 - JFCC
Страница 1: ...BRIZA 12 JFCC MANU L...
Страница 2: ...CZ SK DE EN STR 3 STR 16 PG 29 PG 42 2...
Страница 55: ...55 EN BRIZA 12 JFCC MANUAL 2021 01 07 NOTES...