INSTALLATION MANUAL

Heater “Short Cycling” Prevention

When the heater is activated and the desired 
temperature is reached, heater will turn off and remain 

off for three (3) minutes, even if the temperature falls 
below the desired temperature. This feature prevents 

heater short cycling (in other words, the heater turning 

off and on in rapid succession).

Cleaner Lockout

The pool cleaner will only activate if the system is in 

pool mode and water is circulating. The pool cleaner 
requires that water is circulating to the pool in order 

for it to operate. Return to pool mode to activate the 

cleaner.

Spillover Lockout

The spillover will only activate if the system is in pool 

mode and water is circulating. The spillover requires 

that water is circulating to the pool in order for it to 

operate. Return to pool mode to activate the waterfall. 
Also, if the pool cleaner is on, it will turn off during 
spillover operation.

Spillover

The spillover is disabled while the spa is on. A message 

is displayed when spillover is turned on while in 

spa mode (water is circulating to spa). The spillover 
requires that water circulation is to pool in order to 
operate. The spillover will activate when the system 

switches back to pool mode.

Enabled

When activated allows the function to work.

Disabled

When activated does not allow the function to work.

SECTION 11.  GLOSSARIES

11.1  GLOSSARY OF SAFETY DELAYS  

AND LOCKOUTS

Lockouts

Any device can be locked out. This will prevent the 
locked out device from being turned on manually. 

However, the device will turn on/off when it is being 

controlled by a schedule.

Pool/Spa Switching Filter Pump Delay

The filter pump turns off while valves rotate between 

pool and spa to prevent damage to the pool equipment. 
The valves take 35 seconds to rotate between pool and 

spa; the filter pump will activate as soon as the valves 
have finished turning.

Heater Cool Down Delay

When the system is heating (water is circulating to 

the spa) and the Spa button is pressed, the system 
will remain in Spa Mode for five (5) minutes, and will 

continue to circulate the water. This delay allows water 
to cool the heater down by circulating water through it, 

preventing equipment damage. The five (5) minute delay 

starts counting down when the heater goes off. If the 
heater has been off for five (5) minutes or more, prior 

to turning off the Spa, there will not be a delay. 

Heater Start-up

The heater will only come on if the water is circulating 

(for example, the filter pump is on and has been 
circulating for 15 seconds) to the corresponding body 
of water (for example, spa for spa heater) and the 
actual water temperature is below the temperature you 

set with Temp Set in the Menu. If these conditions are 

not met, the heater will be enabled (ready to go), but 
will not fire. 

Содержание JAUTP

Страница 1: ...arning notices and instructions that accompany this product Failure to follow warning notices and instructions may result in property damage personal injury or death Improper installation and or opera...

Страница 2: ...s if applicable 11 Section 6 Section System Setup Programming and Testing 11 6 1 Basic Navigation 11 6 2 Set the Clock 12 6 3 Define Equipment ON OFF Schedules 12 6 4 Test the JAUTPS JAUTP 13 Section...

Страница 3: ...adult Lower water temperatures are recommended for young children and when spa use exceeds 10 minutes b Since excessive water temperatures have a high potential for causing fetal damage during the ear...

Страница 4: ...for complete details WARNING People with infectious diseases should not use a spa or hot tub To avoid injury exercise care when entering or exiting the spa or hot tub Do not use drugs or alcohol befor...

Страница 5: ...ng Bracket for remotely installing UI Installation Manual Owner s Manual JAUTPS Four Function Controller with removeable User Interface UI Jandy Valve Actuators 2 Water Temperature Sensor Kit Mounting...

Страница 6: ...ust be followed exactly Read through the Important Safety Information section completely before beginning installation and before operating the equipment Before you begin installation make sure you ha...

Страница 7: ...Section 4 HIGHVOLTAGE WIRING WARNING Potentially high voltages in the JAUTPS JAUTP controller can create dangerous electrical hazards possibly causing death serious injury or property damage Turn off...

Страница 8: ...VDC output JVA Sockets 24 VAC output Intake Return Solar Spare Input Low Voltage Heater Green Terminal Bar RS485 Network Red Terminal Bar User Interface Connector Black Modular Connector 24 VAC power...

Страница 9: ...equipment requiring a ground should also be bonded to the common approved bonding point There should be one bonding connection to the controller In Canada the Canadian Electrical Code CEC dictates th...

Страница 10: ...LAR SENSOR IF APPLICABLE If there is a solar panel in the equipment configuration wire the solar panel temperature sensor to the 10 pin green connector The solar sensor should be installed adjacent to...

Страница 11: ...manual included in the JVA packaging 3 Install intake JVA and return JVA on equipment lines according to installation instructions in the owner s manual 4 Feed intake JVA wire through the black low vo...

Страница 12: ...tes flash 5 Scroll up down to display desired minutes Press Select 6 3 DEFINE EQUIPMENT ON OFF SCHEDULES MAIN SETTINGS SCHEDULES Define automatic ON and OFF times for equipment You may set a total of...

Страница 13: ...f Spa Pump On Pool Heat Off Spa heat Off Solar Heat Off More 12 40PM Pool Mode On Pool Heater 80 F Spa Mode Off Spa Heater Off Settings Devices Service Mode Devices Filter Pump Off Spa Pump On Pool He...

Страница 14: ...me for about 5 seconds 12 40PM Pool Mode On Pool Heater 80 F Aux1 Off Aux2 Off Settings Devices INSTALL SETTINGS Freeze Protect Units Language Clear Memory Pump More INSTALL SETTINGS Color Light Label...

Страница 15: ...ZE PROTECT EQUIPMENT Filter Pump Aux1 Aux2 Aux3 FREEZE PROTECT Set Temp Equipment FREEZE PROTECT EQUIPMENT Filter Pump Aux1 Aux2 Aux3 FREEZE PROTECT Set Temp Equipment 7 2 UNITS INSTALL SETTINGS UNITS...

Страница 16: ...2 Speed VSP VSP Setup INSTALL SETTINGS Freeze Protect Units Language Clear Memory Pump More VSP SETUP Model Assign Speeds Prime Min Max Freeze VSP SETUP Model Assign Speeds Prime Min Max Freeze SET P...

Страница 17: ...ty Assign JVA LABEL AUX Aux1 Aux2 Aux3 Label Aux2 Default Aerator Air Blower Backwash Chlorinator More Label Aux2 Swim Jet Valve s Wtr Feature Waterfalls Whirlpool More More INSTALL SETTINGS Color Lig...

Страница 18: ...xiliary on the JAUTPS JAUTP controller so that when you select this auxiliary the valve turns Assigning JVAs lets the pool owner control certain features like diverting water to a waterfall or bank of...

Страница 19: ...CES AQP 100 FFC 100 iAL 100 SWC 100 VSP 100 DIAGNOSTICS Revisions Alerts RS 485 Devices More INSTALL SETTINGS Diagnostics RS 485 DEVICES AQP 100 FFC 100 iAL 100 SWC 100 VSP 100 REVISIONS UI 1 3 Bootlo...

Страница 20: ...es that all equipment is turned off until system is manually turned to Auto by service technician Timeout Indicates that all equipment will remain turned off for three 3 hours and then resume running...

Страница 21: ...Heat Enabled Set to 102 F Boost OFF ON Low OFF ON Chlor Output Clock Schedules All Off Set Clock Friday 8 12 AM PM Filter Pump Spa Clner Sp3 Spillover Pool Heat Spa Heat Solar Heat AUX 1 AUX 2 AUX 3 o...

Страница 22: ...t Negative Edge Not used Other 1 Other 2 Other 3 Pond Regulations Slide Solar Pump Spa Speed High Speed1 Speed2 Speed3 Speed4 Speed5 Speed6 Speed7 Speed8 Spillover Sprinkler 1 Sprinkler 2 Sprinkler 3...

Страница 23: ...Clock Schedules All Off Set Clock Friday 8 12 AM PM Filter Pump Speed 2 Clner Sp3 Sp4 Temp 1 Temp 2 Solar Heat AUX 1 AUX 2 AUX 3 only shown if installed Pool 20 Spa Low 10 equipment name No Schedules...

Страница 24: ...used Other 1 Other 2 Other 3 Pond Regulations Slide Solar Pump Spa Speed High Speed1 Speed2 Speed3 Speed4 Speed5 Speed6 Speed7 Speed8 Sprinkler 1 Sprinkler 2 Sprinkler 3 Vanishing Edge Swim Jet Valve...

Страница 25: ...hen activated does not allow the function to work Section 11 GLOSSARIES 11 1 GLOSSARY OF SAFETY DELAYS AND LOCKOUTS Lockouts Any device can be locked out This will prevent the locked out device from b...

Страница 26: ...PEN the heater will not fire If message AIR TEMP OPEN is displayed freeze protection will not operate correctly POOL HEATER ENABLED This message indicates that the pool heater is ready to use but is n...

Страница 27: ...gh it preventing equipment damage TIMEOUT MODE TIME OUT mode is used by the pool service person to aid them in servicing the pool The JAUTPS JAUTP user interface will not be functional for three 3 hou...

Страница 28: ...er brands product names company names trade names and trademarks used are the property of their respective owners Jacuzzi may add to change or remove any part of these materials at any time without no...

Отзывы: